Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 12:05
Tabular Output Report in Format: HTML
Building: Edificio terciario - Guía de aplicación DB HE 2019. EJEMPLOS (V)
Environment: RUNPERIOD 1 ** D3_peninsula - ESP CTE_DB_HE WMO#=
Simulation Timestamp: 2026-07-17 12:05:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Values gathered over 8760.00 hours| Total Energy [kWh] | Energy Per Total Building Area [kWh/m2] | Energy Per Conditioned Building Area [kWh/m2] | |
| Total Site Energy | 228445.25 | 125.52 | 125.52 |
| Net Site Energy | 228445.25 | 125.52 | 125.52 |
| Total Source Energy | 617395.48 | 339.23 | 339.23 |
| Net Source Energy | 617395.48 | 339.23 | 339.23 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 1819.97 |
| Net Conditioned Building Area | 1819.97 |
| Unconditioned Building Area | 0.00 |
| Electricity [kWh] | Natural Gas [kWh] | Gasoline [kWh] | Diesel [kWh] | Coal [kWh] | Fuel Oil No 1 [kWh] | Fuel Oil No 2 [kWh] | Propane [kWh] | Other Fuel 1 [kWh] | Other Fuel 2 [kWh] | District Cooling [kWh] | District Heating [kWh] | Water [m3] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91618.83 | 0.00 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70879.34 | 0.00 | 0.00 |
| Interior Lighting | 30914.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 29057.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5974.84 | 109.56 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 59972.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70879.34 | 97593.67 | 109.56 |
| Subcategory | Electricity [kWh] | Natural Gas [kWh] | Gasoline [kWh] | Diesel [kWh] | Coal [kWh] | Fuel Oil No 1 [kWh] | Fuel Oil No 2 [kWh] | Propane [kWh] | Other Fuel 1 [kWh] | Other Fuel 2 [kWh] | District Cooling [kWh] | District Heating [kWh] | Water [m3] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91618.83 | 0.00 |
| Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70879.34 | 0.00 | 0.00 |
| Interior Lighting | 1 | 30914.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | General | 29057.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5974.84 | 109.56 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [kWh] | Natural Gas [kWh] | Gasoline [kWh] | Diesel [kWh] | Coal [kWh] | Fuel Oil No 1 [kWh] | Fuel Oil No 2 [kWh] | Propane [kWh] | Other Fuel 1 [kWh] | Other Fuel 2 [kWh] | District Cooling [kWh] | District Heating [kWh] | Water [m3] | |
| Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91618.83 | 0.00 |
| Cooling | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70879.34 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 30914.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 29057.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5974.84 | 109.56 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [kWh/m2] | Natural Gas Intensity [kWh/m2] | Gasoline Intensity [kWh/m2] | Diesel Intensity [kWh/m2] | Coal Intensity [kWh/m2] | Fuel Oil No 1 Intensity [kWh/m2] | Fuel Oil No 2 Intensity [kWh/m2] | Propane Intensity [kWh/m2] | Other Fuel 1 Intensity [kWh/m2] | Other Fuel 2 Intensity [kWh/m2] | District Cooling Intensity [kWh/m2] | District Heating Intensity [kWh/m2] | Water Intensity [m3/m2] | |
| Lighting | 16.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 53.62 | 0.06 |
| Other | 15.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 32.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 53.62 | 0.06 |
| Electricity Intensity [kWh/m2] | Natural Gas Intensity [kWh/m2] | Gasoline Intensity [kWh/m2] | Diesel Intensity [kWh/m2] | Coal Intensity [kWh/m2] | Fuel Oil No 1 Intensity [kWh/m2] | Fuel Oil No 2 Intensity [kWh/m2] | Propane Intensity [kWh/m2] | Other Fuel 1 Intensity [kWh/m2] | Other Fuel 2 Intensity [kWh/m2] | District Cooling Intensity [kWh/m2] | District Heating Intensity [kWh/m2] | Water Intensity [m3/m2] | |
| Lighting | 16.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 53.62 | 0.06 |
| Other | 15.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 32.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 53.62 | 0.06 |
| Electricity [kWh] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 59972.228 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 59972.228 | 100.00 |
| Total On-Site and Utility Electric Sources | 59972.228 | 100.00 |
| Total Electricity End Uses | 59972.228 | 100.00 |
| Heat [kWh] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 109.56 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 109.56 | 100.00 |
| Total Water End Uses | 109.56 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 1.00 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 1.00 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 0.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2685.75 |
Table of Contents
TopReport: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
General| Value | |
| Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 12:05 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | D3_peninsula - ESP CTE_DB_HE WMO#= |
| Latitude [deg] | 40.68 |
| Longitude [deg] | -4.1 |
| Elevation [m] | 667.00 |
| Time Zone | 1.00 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1705.82 | 348.87 | 352.36 | 653.11 | 351.48 |
| Above Ground Wall Area [m2] | 1705.82 | 348.87 | 352.36 | 653.11 | 351.48 |
| Window Opening Area [m2] | 564.58 | 39.21 | 173.74 | 177.89 | 173.74 |
| Gross Window-Wall Ratio [%] | 33.10 | 11.24 | 49.31 | 27.24 | 49.43 |
| Above Ground Window-Wall Ratio [%] | 33.10 | 11.24 | 49.31 | 27.24 | 49.43 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1705.82 | 348.87 | 352.36 | 653.11 | 351.48 |
| Above Ground Wall Area [m2] | 1705.82 | 348.87 | 352.36 | 653.11 | 351.48 |
| Window Opening Area [m2] | 564.58 | 39.21 | 173.74 | 177.89 | 173.74 |
| Gross Window-Wall Ratio [%] | 33.10 | 11.24 | 49.31 | 27.24 | 49.43 |
| Above Ground Window-Wall Ratio [%] | 33.10 | 11.24 | 49.31 | 27.24 | 49.43 |
| Total | |
| Gross Roof Area [m2] | 362.81 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| Z01_P02 | 350.94 | Yes | Yes | 1052.82 | 1.00 | 302.51 | 0.00 | 95.20 | 116.92 | 4.9098 | 10.21 | 4.5000 |
| Z02_P03 | 350.94 | Yes | Yes | 1052.82 | 1.00 | 287.51 | 0.00 | 89.76 | 110.16 | 4.9098 | 10.21 | 4.5000 |
| Z03_P04 | 350.94 | Yes | Yes | 1052.82 | 1.00 | 287.55 | 0.00 | 89.76 | 110.16 | 4.9098 | 10.21 | 4.5000 |
| Z04_P05 | 350.94 | Yes | Yes | 1052.82 | 1.00 | 287.55 | 0.00 | 89.76 | 110.16 | 4.9098 | 10.21 | 4.5000 |
| Z05_P06 | 350.94 | Yes | Yes | 1070.52 | 1.00 | 291.34 | 0.00 | 91.23 | 111.91 | 4.9098 | 10.21 | 4.5000 |
| Z06_ESCALERAS | 65.25 | Yes | Yes | 198.99 | 1.00 | 249.36 | 0.00 | 3.42 | 5.25 | 1.5000 | 10.21 | 4.5000 |
| Total | 1819.97 | 5480.79 | 1705.82 | 0.00 | 459.12 | 564.58 | 4.7876 | 10.21 | 4.5000 | |||
| Conditioned Total | 1819.97 | 5480.79 | 1705.82 | 0.00 | 459.12 | 564.58 | 4.7876 | 10.21 | 4.5000 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| Z01_P02 | 350.94 | Yes | Yes | 1.00 | Z01_P02 | GENERAL | Z01_P02 | 4.9098 | 10.21 | 4.5000 | |
| Z02_P03 | 350.94 | Yes | Yes | 1.00 | Z02_P03 | GENERAL | Z02_P03 | 4.9098 | 10.21 | 4.5000 | |
| Z03_P04 | 350.94 | Yes | Yes | 1.00 | Z03_P04 | GENERAL | Z03_P04 | 4.9098 | 10.21 | 4.5000 | |
| Z04_P05 | 350.94 | Yes | Yes | 1.00 | Z04_P05 | GENERAL | Z04_P05 | 4.9098 | 10.21 | 4.5000 | |
| Z05_P06 | 350.94 | Yes | Yes | 1.00 | Z05_P06 | GENERAL | Z05_P06 | 4.9098 | 10.21 | 4.5000 | |
| Z06_ESCALERAS | 65.25 | Yes | Yes | 1.00 | Z06_ESCALERAS | GENERAL | Z06_ESCALERAS | 1.5000 | 10.21 | 4.5000 | |
| Total | 1819.97 | 4.7876 | 10.21 | 4.5000 | |||||||
| Conditioned Total | 1819.97 | 4.7876 | 10.21 | 4.5000 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 1819.97 | 1819.97 | 0.00 | 0.00 | 4.7876 | 10.21 | 4.5000 |
| Total | 1819.97 | 1819.97 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
| Time of Peak | 01-JAN-06:30 | - | - | - | - | - | - | - | - | - | 23-JUL-15:30 | 15-JAN-06:30 | 04-JAN-06:30 |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239239.90 | 0.00 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224790.54 | 0.00 | 0.00 |
| Interior Lighting | 8713.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 8189.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.11 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 16903.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224790.54 | 239995.01 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239239.90 | 0.00 |
| Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224790.54 | 0.00 | 0.00 |
| Interior Lighting | 1 | 8713.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | General | 8189.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 755.11 | 0.00 |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Values gathered over 8760.00 hours| Source Electricity [kWh] | Source Natural Gas [kWh] | Source Gasoline [kWh] | Source Diesel [kWh] | Source Coal [kWh] | Source Fuel Oil No 1 [kWh] | Source Fuel Oil No 2 [kWh] | Source Propane [kWh] | Source Other Fuel 1 [kWh] | Source Other Fuel 2 [kWh] | Source District Cooling [kWh] | Source District Heating [kWh] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331049.38 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74824.96 | 0.00 |
| Interior Lighting | 97906.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 92025.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21589.10 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 189932.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74824.96 | 352638.48 |
| Source Electricity [kWh/m2] | Source Natural Gas [kWh/m2] | Source Gasoline [kWh/m2] | Source Diesel [kWh/m2] | Source Coal [kWh/m2] | Source Fuel Oil No 1 [kWh/m2] | Source Fuel Oil No 2 [kWh/m2] | Source Propane [kWh/m2] | Source Other Fuel 1 [kWh/m2] | Source Other Fuel 2 [kWh/m2] | Source District Cooling [kWh/m2] | Source District Heating [kWh/m2] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.90 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 0.00 |
| Interior Lighting | 53.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 50.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 104.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 193.76 |
| Source Electricity [kWh/m2] | Source Natural Gas [kWh/m2] | Source Gasoline [kWh/m2] | Source Diesel [kWh/m2] | Source Coal [kWh/m2] | Source Fuel Oil No 1 [kWh/m2] | Source Fuel Oil No 2 [kWh/m2] | Source Propane [kWh/m2] | Source Other Fuel 1 [kWh/m2] | Source Other Fuel 2 [kWh/m2] | Source District Cooling [kWh/m2] | Source District Heating [kWh/m2] | |
| Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.90 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 0.00 |
| Interior Lighting | 53.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 50.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 104.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 193.76 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
ZoneHVAC:IdealLoadsAirSystem| User-Specified Maximum Heating Air Flow Rate [m3/s] | User-Specified Maximum Cooling Air Flow Rate [m3/s] | |
| Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
| Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
| Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
| Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
| Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
| Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM | 0.000000 | 0.000000 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E06 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z01_S02_E10 | Z01_S02_E09 | Z01_S04_E07 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E06 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z01_S02_E12 | Z01_S02_E09 | Z01_S04_E07 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E08 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z01_S04_E07 | Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S02_E05 | Z06_S02_E08 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z02_S02_E09 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z02_S02_E11 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z02_S04_E07 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z03_S02_E09 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z03_S02_E11 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z03_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z04_S02_E09 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 | |
| Z04_S02_E11 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z04_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 | |
| Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E06 | |
| Z05_S02_E09 | Z05_S02_E08 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E06 | |
| Z05_S02_E11 | Z05_S02_E08 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E08 | |
| Z05_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S06_E05 | Z06_S06_E08 | |
| Z05_S01_E02 | Z06_S06_E05 | Z06_S06_E06 | Z06_S06_E08 | |
| Z06_S01_E04 | Z01_S02_E09 | Z01_S01_E01 | Z02_S02_E08 | Z03_S02_E08 | Z04_S02_E08 | Z05_S02_E08 | |
| Z06_S01_E05 | Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z01_S01_E01 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S01_E06 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S01_E06 | Z01_S02_E09 | Z01_S02_E10 | Z01_S01_E01 | Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S01_E05 | Z06_S01_E07 | Z06_S02_E05 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 | |
| Z06_S01_E07 | Z01_S02_E10 | Z01_S02_E12 | Z01_S01_E01 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E09 | Z05_S02_E11 | Z06_S01_E06 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S01_E08 | Z01_S02_E12 | Z01_S04_E07 | Z01_S01_E01 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 | |
| Z06_S02_E05 | Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S02_E06 | Z01_S02_E09 | Z01_S02_E10 | Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S02_E05 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 | |
| Z06_S02_E08 | Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 | |
| Z06_S03_E05 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S03_E06 | Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 | |
| Z06_S03_E08 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 | |
| Z06_S04_E05 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S04_E06 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 | |
| Z06_S04_E08 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 | |
| Z06_S05_E05 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S05_E06 | Z06_S06_E06 | |
| Z06_S05_E06 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S05_E05 | Z06_S06_E05 | |
| Z06_S05_E08 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 | |
| Z06_S06_E05 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S06_E06 | |
| Z06_S06_E06 | Z05_S02_E08 | Z05_S02_E09 | Z06_S06_E05 | |
| Z06_S06_E08 | Z05_S02_E11 | Z05_S04_E07 | |
| Possible Shadow Receivers | |
| Z01_S01_E03 | Z01_S01_E03_G1 | |
| Z01_S01_E04 | Z01_S01_E04_G1 | |
| Z01_S01_E05 | Z01_S01_E05_G1 | |
| Z01_S02_E04 | Z01_S02_E04_G1 | Z01_S02_E04_G2 | |
| Z01_S04_E03 | Z01_S04_E03_G1 | |
| Z02_S01_E03 | Z02_S01_E03_G1 | |
| Z02_S01_E04 | Z02_S01_E04_G1 | |
| Z02_S01_E05 | Z02_S01_E05_G1 | |
| Z02_S02_E03 | Z02_S02_E03_G1 | Z02_S03_E05_G1 | |
| Z02_S04_E03 | Z02_S04_E03_G1 | |
| Z03_S01_E03 | Z03_S01_E03_G1 | |
| Z03_S01_E04 | Z03_S01_E04_G1 | |
| Z03_S01_E05 | Z03_S01_E05_G1 | |
| Z03_S02_E03 | Z03_S02_E03_G1 | Z03_S03_E04_G1 | |
| Z03_S04_E03 | Z03_S04_E03_G1 | |
| Z04_S01_E03 | Z04_S01_E03_G1 | |
| Z04_S01_E04 | Z04_S01_E04_G1 | |
| Z04_S01_E05 | Z04_S01_E05_G1 | |
| Z04_S02_E03 | Z04_S02_E03_G1 | Z04_S03_E04_G1 | |
| Z04_S04_E03 | Z04_S04_E03_G1 | |
| Z05_S01_E04 | Z05_S01_E04_G1 | |
| Z05_S01_E05 | Z05_S01_E05_G1 | |
| Z05_S01_E06 | Z05_S01_E06_G1 | |
| Z05_S02_E03 | Z05_S02_E03_G1 | Z05_S03_E04_G1 | |
| Z05_S04_E03 | Z05_S04_E03_G1 | |
| Z06_S02_E03 | Z06_S02_E03_G1 | |
| Z06_S03_E03 | Z06_S03_E03_G1 | |
| Z06_S04_E03 | Z06_S04_E03_G1 | |
| Z06_S05_E03 | Z06_S05_E03_G1 | |
| Z06_S06_E03 | Z06_S06_E03_G1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Version| Version ID | |
| 1 | 23.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 4 | 15 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 4 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 1.000 | 1.000 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 | 13.60 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 | 13.63 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | D3_peninsula - ESP CTE_DB_HE WMO#= | 40.68 | -4.13 | 1.00 | 667.00 | 93565 | 1.1121 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Schedule | SCHED6_WATER_MAINS_TEMP | 0.00 | 0.00 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | Edificio terciario - Guía de aplicación DB HE 2019. EJEMPLOS (V) | 0.000 | Country | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | DOE-2 |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
| 1 | ThirdOrderBackwardDifference | No | No |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.140 | 270.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 6 | 188 | 35 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | Z01_P02 | 0.0 | 0.00 | 0.00 | 0.00 | 5.43 | 2.00 | -7.14E-002 | 1 | 1 | 1 | -10.00 | 185.26 | -10.00 | 10.00 | -24.25 | 3.00 | 3.00 | 1052.82 | TARP | DOE-2 | 350.94 | 302.51 | 185.59 | 95.20 | 18 | 6 | 0 | Yes |
| 2 | Z02_P03 | 0.0 | 0.00 | 0.00 | 0.00 | 3.21 | 2.95 | 3.42 | 1 | 1 | 1 | -10.00 | 137.83 | -10.00 | 10.00 | -24.25 | 6.50 | 3.00 | 1052.82 | TARP | DOE-2 | 350.94 | 287.51 | 177.35 | 89.76 | 18 | 6 | 0 | Yes |
| 3 | Z03_P04 | 0.0 | 0.00 | 0.00 | 0.00 | 3.22 | 2.95 | 6.75 | 1 | 1 | 1 | -10.00 | 137.94 | -10.00 | 10.00 | -24.25 | 10.00 | 3.00 | 1052.82 | TARP | DOE-2 | 350.94 | 287.55 | 177.38 | 89.76 | 18 | 6 | 0 | Yes |
| 4 | Z04_P05 | 0.0 | 0.00 | 0.00 | 0.00 | 3.22 | 2.95 | 10.07 | 1 | 1 | 1 | -10.00 | 137.94 | -10.00 | 10.00 | -24.25 | 13.50 | 3.00 | 1052.82 | TARP | DOE-2 | 350.94 | 287.55 | 177.38 | 89.76 | 18 | 6 | 0 | Yes |
| 5 | Z05_P06 | 0.0 | 0.00 | 0.00 | 0.00 | 1.77 | 2.90 | 13.65 | 1 | 1 | 1 | -10.00 | 68.97 | -10.00 | 10.00 | -25.25 | 17.75 | 3.05 | 1070.52 | TARP | DOE-2 | 350.94 | 291.34 | 179.43 | 91.23 | 20 | 6 | 0 | Yes |
| 6 | Z06_ESCALERAS | 0.0 | 0.00 | 0.00 | 0.00 | 1.16 | 7.75 | 5.00 | 1 | 1 | 1 | -2.81 | 56.07 | 0.00 | 10.00 | -24.25 | 17.30 | 3.05 | 198.99 | TARP | DOE-2 | 65.25 | 249.36 | 244.11 | 3.42 | 51 | 5 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | Z01_P02 | 350.94 | 34.4 | 10.215 | 9.790E-002 | 4.910 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 9.410 | No |
| 2 | Z02_P03 | 350.94 | 34.4 | 10.215 | 9.790E-002 | 4.910 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 9.410 | No |
| 3 | Z03_P04 | 350.94 | 34.4 | 10.215 | 9.790E-002 | 4.910 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 9.410 | No |
| 4 | Z04_P05 | 350.94 | 34.4 | 10.215 | 9.790E-002 | 4.910 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 9.410 | No |
| 5 | Z05_P06 | 350.94 | 34.4 | 10.215 | 9.790E-002 | 4.910 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 9.410 | No |
| 6 | Z06_ESCALERAS | 65.25 | 6.4 | 10.214 | 9.790E-002 | 1.500 | 0.000 | 0.000 | 4.500 | 0.000 | 0.000 | 6.000 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | Z01_P02_IG1 PEOPLE | SCHED4 | Z01_P02 | 350.94 | 34.4 | 34.4 | 9.790E-002 | 10.215 | 0.600 | 0.400 | 0.613 | Z01_P02_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 34 |
| 2 | Z02_P03_IG1 PEOPLE | SCHED4 | Z02_P03 | 350.94 | 34.4 | 34.4 | 9.790E-002 | 10.215 | 0.600 | 0.400 | 0.613 | Z02_P03_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 34 |
| 3 | Z03_P04_IG1 PEOPLE | SCHED4 | Z03_P04 | 350.94 | 34.4 | 34.4 | 9.790E-002 | 10.215 | 0.600 | 0.400 | 0.613 | Z03_P04_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 34 |
| 4 | Z04_P05_IG1 PEOPLE | SCHED4 | Z04_P05 | 350.94 | 34.4 | 34.4 | 9.790E-002 | 10.215 | 0.600 | 0.400 | 0.613 | Z04_P05_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 34 |
| 5 | Z05_P06_IG1 PEOPLE | SCHED4 | Z05_P06 | 350.94 | 34.4 | 34.4 | 9.790E-002 | 10.215 | 0.600 | 0.400 | 0.613 | Z05_P06_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 34 |
| 6 | Z06_ESCALERAS_IG1 PEOPLE | SCHED4 | Z06_ESCALERAS | 65.25 | 6.4 | 6.4 | 9.790E-002 | 10.214 | 0.600 | 0.400 | 0.613 | Z06_ESCALERAS_IG1 ACTIVITYLEVEL | No | 0.0000 | 0 | 6 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | Z01_P02_IG2 LIGHTS | SCHED4 | Z01_P02 | 350.94 | 34.4 | 1438.340 | 4.099 | 41.864 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 1438.340 |
| 2 | Z01_P02_IG3 LIGHTS | SCHED4 | Z01_P02 | 350.94 | 34.4 | 156.461 | 0.446 | 4.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 156.461 |
| 3 | Z01_P02_IG4 LIGHTS | SCHED4 | Z01_P02 | 350.94 | 34.4 | 40.540 | 0.116 | 1.180 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 40.540 |
| 4 | Z01_P02_IG5 LIGHTS | SCHED4 | Z01_P02 | 350.94 | 34.4 | 87.734 | 0.250 | 2.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.734 |
| 5 | Z02_P03_IG2 LIGHTS | SCHED4 | Z02_P03 | 350.94 | 34.4 | 1438.340 | 4.099 | 41.864 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 1438.340 |
| 6 | Z02_P03_IG3 LIGHTS | SCHED4 | Z02_P03 | 350.94 | 34.4 | 109.331 | 0.312 | 3.182 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 109.331 |
| 7 | Z02_P03_IG4 LIGHTS | SCHED4 | Z02_P03 | 350.94 | 34.4 | 87.670 | 0.250 | 2.552 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.670 |
| 8 | Z02_P03_IG5 LIGHTS | SCHED4 | Z02_P03 | 350.94 | 34.4 | 87.734 | 0.250 | 2.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.734 |
| 9 | Z03_P04_IG2 LIGHTS | SCHED4 | Z03_P04 | 350.94 | 34.4 | 1438.340 | 4.099 | 41.864 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 1438.340 |
| 10 | Z03_P04_IG3 LIGHTS | SCHED4 | Z03_P04 | 350.94 | 34.4 | 109.331 | 0.312 | 3.182 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 109.331 |
| 11 | Z03_P04_IG4 LIGHTS | SCHED4 | Z03_P04 | 350.94 | 34.4 | 87.670 | 0.250 | 2.552 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.670 |
| 12 | Z03_P04_IG5 LIGHTS | SCHED4 | Z03_P04 | 350.94 | 34.4 | 87.734 | 0.250 | 2.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.734 |
| 13 | Z04_P05_IG2 LIGHTS | SCHED4 | Z04_P05 | 350.94 | 34.4 | 1438.340 | 4.099 | 41.864 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 1438.340 |
| 14 | Z04_P05_IG3 LIGHTS | SCHED4 | Z04_P05 | 350.94 | 34.4 | 109.331 | 0.312 | 3.182 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 109.331 |
| 15 | Z04_P05_IG4 LIGHTS | SCHED4 | Z04_P05 | 350.94 | 34.4 | 87.670 | 0.250 | 2.552 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.670 |
| 16 | Z04_P05_IG5 LIGHTS | SCHED4 | Z04_P05 | 350.94 | 34.4 | 87.734 | 0.250 | 2.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.734 |
| 17 | Z05_P06_IG2 LIGHTS | SCHED4 | Z05_P06 | 350.94 | 34.4 | 1438.340 | 4.099 | 41.864 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 1438.340 |
| 18 | Z05_P06_IG3 LIGHTS | SCHED4 | Z05_P06 | 350.94 | 34.4 | 109.331 | 0.312 | 3.182 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 109.331 |
| 19 | Z05_P06_IG4 LIGHTS | SCHED4 | Z05_P06 | 350.94 | 34.4 | 87.670 | 0.250 | 2.552 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.670 |
| 20 | Z05_P06_IG5 LIGHTS | SCHED4 | Z05_P06 | 350.94 | 34.4 | 87.734 | 0.250 | 2.554 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 87.734 |
| 21 | Z06_ESCALERAS_IG2 LIGHTS | SCHED4 | Z06_ESCALERAS | 65.25 | 6.4 | 17.288 | 0.265 | 2.706 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 17.288 |
| 22 | Z06_ESCALERAS_IG3 LIGHTS | SCHED4 | Z06_ESCALERAS | 65.25 | 6.4 | 80.592 | 1.235 | 12.616 | 0.000 | 0.656 | 0.180 | 0.164 | 0.000 | 1 | 0.000 | 80.592 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | Z01_P02_IG6 ELECEQ | SCHED4 | Z01_P02 | 350.94 | 34.4 | 1579.244 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 1579.244 |
| 2 | Z02_P03_IG6 ELECEQ | SCHED4 | Z02_P03 | 350.94 | 34.4 | 1579.244 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 1579.244 |
| 3 | Z03_P04_IG6 ELECEQ | SCHED4 | Z03_P04 | 350.94 | 34.4 | 1579.244 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 1579.244 |
| 4 | Z04_P05_IG6 ELECEQ | SCHED4 | Z04_P05 | 350.94 | 34.4 | 1579.244 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 1579.244 |
| 5 | Z05_P06_IG6 ELECEQ | SCHED4 | Z05_P06 | 350.94 | 34.4 | 1579.244 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 1579.244 |
| 6 | Z06_ESCALERAS_IG4 ELECEQ | SCHED4 | Z06_ESCALERAS | 65.25 | 6.4 | 293.639 | 4.500 | 45.965 | 0.000 | 0.700 | 0.000 | 0.300 | 0.000 | 293.639 |
| Zone/Enclosure Name | Original Check Value | Calculated Fixed Check Value | Final Check Value | Number of Iterations | Fixed RowSum Convergence | Used RowSum Convergence | |
| 1 | Z01_P02 | 6.039613E-014 | 8.371192E-004 | 8.371192E-004 | 15 | 8.371192E-004 | 8.371192E-004 |
| 2 | Z02_P03 | 2.131628E-014 | 8.594889E-004 | 8.594889E-004 | 15 | 8.594889E-004 | 8.594889E-004 |
| 3 | Z03_P04 | 2.131628E-014 | 8.594317E-004 | 8.594317E-004 | 15 | 8.594317E-004 | 8.594317E-004 |
| 4 | Z04_P05 | 3.552714E-014 | 8.594317E-004 | 8.594317E-004 | 15 | 8.594317E-004 | 8.594317E-004 |
| 5 | Z05_P06 | 2.842171E-014 | 8.482756E-004 | 8.482756E-004 | 15 | 8.482756E-004 | 8.482756E-004 |
| 6 | Z06_ESCALERAS | 2.131628E-014 | 7.095171E-004 | 7.095171E-004 | 11 | 7.095171E-004 | 7.095171E-004 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Zone/Enclosure Name | Original Check Value | Calculated Fixed Check Value | Final Check Value | Number of Iterations | Fixed RowSum Convergence | Used RowSum Convergence | |
| 1 | Z01_P02 | 6.039613E-014 | 8.371192E-004 | 8.371192E-004 | 15 | 8.371192E-004 | 8.371192E-004 |
| 2 | Z02_P03 | 2.131628E-014 | 8.594889E-004 | 8.594889E-004 | 15 | 8.594889E-004 | 8.594889E-004 |
| 3 | Z03_P04 | 2.131628E-014 | 8.594317E-004 | 8.594317E-004 | 15 | 8.594317E-004 | 8.594317E-004 |
| 4 | Z04_P05 | 3.552714E-014 | 8.594317E-004 | 8.594317E-004 | 15 | 8.594317E-004 | 8.594317E-004 |
| 5 | Z05_P06 | 2.842171E-014 | 8.482756E-004 | 8.482756E-004 | 15 | 8.482756E-004 | 8.482756E-004 |
| 6 | Z06_ESCALERAS | 2.131628E-014 | 7.095171E-004 | 7.095171E-004 | 11 | 7.095171E-004 | 7.095171E-004 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | Z01_S01_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 2 | Z01_S01_E03_G1 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 3 | Z01_S01_E04 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 3 | No | No |
| 4 | Z01_S01_E04_G1 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 5 | Z01_S01_E05 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 6 | Z01_S01_E05_G1 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 7 | Z01_S02_E04 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 8 | Z01_S02_E04_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 9 | Z01_S02_E04_G2 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 10 | Z01_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 11 | Z01_S02_E06 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 12 | Z01_S02_E09 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 13 | Z01_S02_E10 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 14 | Z01_S02_E12 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 15 | Z01_S03_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 16 | Z01_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 3 | No | No |
| 17 | Z01_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 2 | No | No |
| 18 | Z01_S04_E04 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 19 | Z01_S04_E07 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 4 | No | No |
| 20 | Z01_S01_TB02 EF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 3 | No | No |
| 21 | Z01_S01_TB03 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 3 | No | No |
| 22 | Z01_S02_E04_G1_TB2_LATERALES V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 3 | No | No |
| 23 | Z01_S01_E01 | 2 | 343.76 | 83.47 | 0.00 | 2 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 24 | Z01_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 25 | Z01_P02 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 26 | Z01_S01_E06 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 3.26 | 0.31 | 0 | No | No |
| 27 | Z02_S01_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 28 | Z02_S01_E03_G1 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 29 | Z02_S01_E04 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 30 | Z02_S01_E04_G1 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 31 | Z02_S01_E05 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 32 | Z02_S01_E05_G1 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 33 | Z02_S02_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 34 | Z02_S02_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 35 | Z02_S03_E05_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 36 | Z02_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 37 | Z02_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 38 | Z02_S02_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 39 | Z02_S02_E09 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 40 | Z02_S02_E11 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 41 | Z02_S03_E04 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 42 | Z02_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 43 | Z02_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 44 | Z02_S04_E04 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 45 | Z02_S04_E07 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 46 | Z02_S01_TB02 EF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 47 | Z02_S01_TB03 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 48 | Z02_S02_E03_G1_TB1_INFERIOR V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 49 | iz-Z01_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 50 | Z02_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 51 | Z02_P03 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 52 | Z02_S01_E06 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 53 | Z03_S01_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 54 | Z03_S01_E03_G1 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 55 | Z03_S01_E04 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 56 | Z03_S01_E04_G1 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 57 | Z03_S01_E05 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 58 | Z03_S01_E05_G1 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 59 | Z03_S02_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 60 | Z03_S02_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 61 | Z03_S03_E04_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 62 | Z03_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 63 | Z03_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 64 | Z03_S02_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 65 | Z03_S02_E09 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 66 | Z03_S02_E11 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 67 | Z03_S03_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 68 | Z03_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 69 | Z03_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 70 | Z03_S04_E04 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 71 | Z03_S04_E07 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 72 | Z03_S01_TB02 EF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 73 | Z03_S01_TB03 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 74 | Z03_S02_E03_G1_TB1_INFERIOR V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 75 | iz-Z02_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 76 | Z03_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 77 | Z03_P04 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 78 | Z03_S01_E06 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 79 | Z04_S01_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 80 | Z04_S01_E03_G1 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 81 | Z04_S01_E04 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 82 | Z04_S01_E04_G1 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 83 | Z04_S01_E05 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 84 | Z04_S01_E05_G1 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 85 | Z04_S02_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 86 | Z04_S02_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 87 | Z04_S03_E04_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 88 | Z04_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 89 | Z04_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 90 | Z04_S02_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 91 | Z04_S02_E09 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 92 | Z04_S02_E11 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 93 | Z04_S03_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 94 | Z04_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 95 | Z04_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 2 | No | No |
| 96 | Z04_S04_E04 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 97 | Z04_S04_E07 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 4 | No | No |
| 98 | Z04_S01_TB02 EF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 99 | Z04_S01_TB03 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 100 | Z04_S02_E03_G1_TB1_INFERIOR V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.00 | 80.07 | 4.18 | 0.31 | 3 | No | No |
| 101 | iz-Z03_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 102 | Z04_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 103 | Z04_P05 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 104 | Z04_S01_E06 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.00 | 80.07 | 4.18 | 0.31 | 0 | No | No |
| 105 | Z05_S01_E04 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 106 | Z05_S01_E04_G1 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 107 | Z05_S01_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 108 | Z05_S01_E05_G1 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 109 | Z05_S01_E06 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 110 | Z05_S01_E06_G1 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 111 | Z05_S02_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 112 | Z05_S02_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 113 | Z05_S03_E04_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 114 | Z05_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 115 | Z05_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 116 | Z05_S02_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 117 | Z05_S02_E09 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 118 | Z05_S02_E11 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 119 | Z05_S03_E03 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 120 | Z05_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 121 | Z05_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 2 | No | No |
| 122 | Z05_S04_E04 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 123 | Z05_S04_E07 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 4 | No | No |
| 124 | Z05_S01_TB02 EF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 125 | Z05_S01_TB03 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 126 | Z05_S01_TB13 FC | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 127 | Z05_S02_E03_G1_TB1_INFERIOR V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 3 | No | No |
| 128 | iz-Z04_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 129 | Z05_S01_E02 | 2 | 362.81 | 194.47 | 0.00 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 130 | Z05_S01_E03 | 2 | 362.81 | 194.47 | 0.00 | 2 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 131 | Z05_P06 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 132 | Z05_S01_E07 FURNITURE | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 80.37 | 7.09 | 0.31 | 0 | No | No |
| 133 | Z06_S01_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 134 | Z06_S01_E04 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 135 | Z06_S01_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 136 | Z06_S01_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 137 | Z06_S01_E07 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 138 | Z06_S01_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 139 | Z06_S02_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 140 | Z06_S02_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 1 | No | No |
| 141 | Z06_S02_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 142 | Z06_S02_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 143 | Z06_S02_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 144 | Z06_S03_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 145 | Z06_S03_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 2 | No | No |
| 146 | Z06_S03_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 147 | Z06_S03_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 148 | Z06_S03_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 149 | Z06_S04_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 150 | Z06_S04_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 2 | No | No |
| 151 | Z06_S04_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 152 | Z06_S04_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 153 | Z06_S04_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 154 | Z06_S05_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 155 | Z06_S05_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 2 | No | No |
| 156 | Z06_S05_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 157 | Z06_S05_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 158 | Z06_S05_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 159 | Z06_S06_E03 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 160 | Z06_S06_E03_G1 | 2 | 336.21 | 84.54 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 2 | No | No |
| 161 | Z06_S06_E05 | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 162 | Z06_S06_E06 | 2 | 322.24 | 91.19 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 163 | Z06_S06_E08 | 2 | 323.12 | 88.29 | 20.80 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 4 | No | No |
| 164 | Z06_S01_TB03 FS | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 165 | Z06_S01_TB04 FF | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 166 | Z06_S02_E03_G1_TB1_INFERIOR V | 2 | 618.79 | 476.86 | 42.55 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 3 | No | No |
| 167 | iz-Z01_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 168 | iz-Z01_S02_E06 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 169 | iz-Z02_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 170 | iz-Z02_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 171 | iz-Z03_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 172 | iz-Z03_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 173 | iz-Z04_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 174 | iz-Z04_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 175 | iz-Z05_S02_E04 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 176 | iz-Z05_S02_E05 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 177 | Z06_S01_E01 | 2 | 11.53 | 15.47 | 0.00 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 178 | iz-Z06_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 179 | iz-Z06_S02_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 180 | iz-Z06_S03_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 181 | iz-Z06_S04_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 182 | iz-Z06_S05_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 183 | Z06_S01_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 184 | Z06_S02_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 185 | Z06_S03_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 186 | Z06_S04_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 187 | Z06_S05_E02 | 1 | 0.00 | 0.00 | 0.00 | 1 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| 188 | Z06_S06_E02 | 2 | 362.81 | 194.47 | 0.00 | 2 | 3.05 | 74.72 | 1.89 | 1.37E-002 | 0 | No | No |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 84.54 | 20.80 | -9.50 | 9.50 | 0.00 | 10.00 | -3.50 | 17.30 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 88.29 | 20.80 | -2.81 | 10.00 | -9.85 | 9.67 | -3.50 | 17.30 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 476.86 | 42.55 | -9.85 | 185.26 | -10.00 | 7.39 | -25.25 | 17.30 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Perimeter | Height | Xmin | Xmax | Ymin | Ymax | Zmin | Zmax | |
| 1 | 91.19 | 20.80 | -10.00 | 5.30 | -9.85 | 9.67 | -3.50 | 17.30 |
| Area [m2] | Perimeter [m] | Height [m] | Tilt [deg] | Azimuth [deg] | |
| 1 | 362.81 | 194.47 | 0.00 | 0.00 | 182.40! <ZoneInfiltration Airflow Stats Nominal> |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | Z06_ESCALERAS_IG6 VENTIL | SCHED4 | Z06_ESCALERAS | 65.25 | 6.4 | 0.131 | 2.000E-003 | 2.043E-002 | 2.361 | Natural | 0.000 | 1.0 | 1.000 | 0.000 | 0.000 | 0.000 | -50.00 | 100.00 | -50.00 | -50.00 | 100.00 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | Z01_P02 | Mixing/Well-Stirred |
| 2 | Z02_P03 | Mixing/Well-Stirred |
| 3 | Z03_P04 | Mixing/Well-Stirred |
| 4 | Z04_P05 | Mixing/Well-Stirred |
| 5 | Z05_P06 | Mixing/Well-Stirred |
| 6 | Z06_ESCALERAS | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 4 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | Z01_P02 | Cooling | 23260.16776 | 23260.16776 | 1.60324 | 1.60324 | SUMMER | 7/22 17:00:00 | 35.20000 | 8.49777E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 2 | Z01_P02 | Heating | 16961.64680 | 16961.64680 | 0.47130 | 0.70189 | WINTER | 12/27 07:00:00 | -0.30000 | 3.16352E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 3 | Z02_P03 | Cooling | 21811.12862 | 21811.12862 | 1.50678 | 1.50678 | SUMMER | 7/22 17:00:00 | 35.20000 | 8.49777E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 4 | Z02_P03 | Heating | 9737.93503 | 9737.93503 | 0.27400 | 0.70189 | WINTER | 12/27 07:00:00 | -0.30000 | 3.16352E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 5 | Z03_P04 | Cooling | 21755.20904 | 21755.20904 | 1.50307 | 1.50307 | SUMMER | 7/22 17:00:00 | 35.20000 | 8.49777E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 6 | Z03_P04 | Heating | 8865.47554 | 8865.47554 | 0.24999 | 0.70189 | WINTER | 12/23 07:00:00 | -0.60000 | 3.12175E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 7 | Z04_P05 | Cooling | 21773.39364 | 21773.39364 | 1.50422 | 1.50422 | SUMMER | 7/22 17:00:00 | 35.20000 | 8.49777E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 8 | Z04_P05 | Heating | 9421.36798 | 9421.36798 | 0.26521 | 0.70189 | WINTER | 12/27 07:00:00 | -0.30000 | 3.16352E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 9 | Z05_P06 | Cooling | 22167.42650 | 22167.42650 | 1.52534 | 1.52534 | SUMMER | 7/23 17:00:00 | 35.00000 | 8.04844E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| 10 | Z05_P06 | Heating | 12595.89744 | 12595.89744 | 0.35091 | 0.70189 | WINTER | 12/27 07:00:00 | -0.30000 | 3.16352E-003 | 350.94300 | 34.35730 | 0.70189 | 0.00000 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:IdealLoadsAirSystem | Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 2 | ZoneHVAC:IdealLoadsAirSystem | Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| 3 | ZoneHVAC:IdealLoadsAirSystem | Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 4 | ZoneHVAC:IdealLoadsAirSystem | Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| 5 | ZoneHVAC:IdealLoadsAirSystem | Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 6 | ZoneHVAC:IdealLoadsAirSystem | Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| 7 | ZoneHVAC:IdealLoadsAirSystem | Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 8 | ZoneHVAC:IdealLoadsAirSystem | Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| 9 | ZoneHVAC:IdealLoadsAirSystem | Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 10 | ZoneHVAC:IdealLoadsAirSystem | Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| 11 | ZoneHVAC:IdealLoadsAirSystem | Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM | User-Specified Maximum Heating Air Flow Rate [m3/s] | 0.00000 |
| 12 | ZoneHVAC:IdealLoadsAirSystem | Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM | User-Specified Maximum Cooling Air Flow Rate [m3/s] | 0.00000 |
| Zone Name | # Surfaces | |
| 1 | Z01_P02 | 26 |
| 2 | Z02_P03 | 26 |
| 3 | Z03_P04 | 26 |
| 4 | Z04_P05 | 26 |
| 5 | Z05_P06 | 28 |
| 6 | Z06_ESCALERAS | 56 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | Z01_S01_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.18 | 43.81 | 15.01 | 270.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | Z01_S01_E03_G1 | Window | Z01_S01_E03 | Window5 Detailed Fenestration | WINDOW | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 270.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | Z01_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 23.64 | 59.10 | 30.48 | 180.00 | 90.00 | 19.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | Z01_S01_E04_G1 | Window | Z01_S01_E04 | Window5 Detailed Fenestration | WINDOW2 | N/A | 3.004 | No | 28.62 | 28.62 | 28.62 | 180.00 | 90.00 | 14.86 | 1.93 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | Z01_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.17 | 43.81 | 15.01 | 90.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | Z01_S01_E05_G1 | Window | Z01_S01_E05 | Window5 Detailed Fenestration | WINDOW3 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 90.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 7 | Z01_S02_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.48 | 20.08 | 12.14 | 0.00 | 90.00 | 6.69 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | Z01_S02_E04_G1 | Window | Z01_S02_E04 | Window5 Detailed Fenestration | WINDOW4 | N/A | 3.004 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.59 | 2.40 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.68 | 0.32 | 4 |
| 9 | Z01_S02_E04_G2 | Window | Z01_S02_E04 | Window5 Detailed Fenestration | WINDOW5 | N/A | 3.004 | No | 4.14 | 4.14 | 4.14 | 0.00 | 90.00 | 2.06 | 2.01 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.67 | 0.33 | 4 |
| 10 | Z01_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 90.00 | 90.00 | 2.11 | 3.00 | 0.00 | iz-Z01_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 11 | Z01_S02_E06 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 0.00 | 90.00 | 1.09 | 3.00 | 0.00 | iz-Z01_S02_E06 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 12 | Z01_S02_E09 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.94 | 6.22E-002 | 4 | ||
| 13 | Z01_S02_E10 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 0.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.10E-002 | 4 | ||
| 14 | Z01_S02_E12 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.22 | 9.22 | 9.22 | 0.00 | 90.00 | 3.07 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.74 | 0.26 | 4 | ||
| 15 | Z01_S03_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 270.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | Z01_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.01 | 12.61 | 11.57 | 0.00 | 90.00 | 4.20 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 17 | Z01_S04_E03_G1 | Window | Z01_S04_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 18 | Z01_S04_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 90.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | Z01_S04_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 270.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 | ||
| 20 | Z01_S01_TB02 EF | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 3.60 | 3.60 | 3.60 | 180.00 | 90.00 | 0.30 | 12.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | Z01_S01_TB03 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 55.58 | 55.58 | 55.58 | 180.00 | 90.00 | 0.30 | 185.26 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | Z01_S02_E04_G1_TB2_LATERALES V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 5.83 | 5.83 | 5.83 | 180.00 | 90.00 | 0.30 | 19.44 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 23 | Z01_S01_E01 | Floor | CTF - ConductionTransferFunction | SUELO (INV) | 0.535 | 0.473 | 343.76 | 343.76 | 343.76 | 90.00 | 180.00 | 18.54 | 18.54 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | WindExposed | 1.00 | 0.00 | 1.00 | 0.00 | 20 | ||
| 24 | Z01_S01_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 353.73 | 353.73 | 353.73 | 180.00 | 0.00 | 18.81 | 18.81 | 0.00 | iz-Z01_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 12 | ||
| 25 | Z01_P02 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | FURNIT_INTERNALMASS | 3.600 | 3.600 | 175.47 | 175.47 | 175.47 | 0.00 | 90.00 | 175.47 | 1.00 | 0.00 | Z01_P02 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 26 | Z01_S01_E06 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 6.552 | 151.77 | 151.77 | 151.77 | 0.00 | 90.00 | 151.77 | 1.00 | 0.00 | Z01_S01_E06 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 27 | Z02_S01_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.18 | 43.81 | 15.01 | 270.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | Z02_S01_E03_G1 | Window | Z02_S01_E03 | Window5 Detailed Fenestration | WINDOW7 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 270.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 29 | Z02_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 23.64 | 59.10 | 30.48 | 180.00 | 90.00 | 19.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | Z02_S01_E04_G1 | Window | Z02_S01_E04 | Window5 Detailed Fenestration | WINDOW8 | N/A | 3.004 | No | 28.62 | 28.62 | 28.62 | 180.00 | 90.00 | 14.86 | 1.93 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | Z02_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.17 | 43.81 | 15.01 | 90.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 32 | Z02_S01_E05_G1 | Window | Z02_S01_E05 | Window5 Detailed Fenestration | WINDOW9 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 90.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 33 | Z02_S02_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 16.24 | 20.08 | 17.59 | 0.00 | 90.00 | 6.69 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | Z02_S02_E03_G1 | Window | Z02_S02_E03 | Window5 Detailed Fenestration | WINDOW10 | N/A | 3.004 | No | 1.45 | 1.45 | 1.45 | 0.00 | 90.00 | 1.98 | 0.74 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.77 | 0.23 | 4 |
| 35 | Z02_S03_E05_G1 | Window | Z02_S02_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 36 | Z02_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 90.00 | 90.00 | 2.11 | 3.00 | 0.00 | iz-Z02_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 37 | Z02_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 0.00 | 90.00 | 1.09 | 3.00 | 0.00 | iz-Z02_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | Z02_S02_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.94 | 6.23E-002 | 4 | ||
| 39 | Z02_S02_E09 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 0.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.13E-002 | 4 | ||
| 40 | Z02_S02_E11 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.22 | 9.22 | 9.22 | 0.00 | 90.00 | 3.07 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.74 | 0.26 | 4 | ||
| 41 | Z02_S03_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 270.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | Z02_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.01 | 12.61 | 11.57 | 0.00 | 90.00 | 4.20 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 43 | Z02_S04_E03_G1 | Window | Z02_S04_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 44 | Z02_S04_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 90.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 45 | Z02_S04_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 270.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 | ||
| 46 | Z02_S01_TB02 EF | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 3.60 | 3.60 | 3.60 | 180.00 | 90.00 | 0.30 | 12.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | Z02_S01_TB03 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 41.35 | 41.35 | 41.35 | 180.00 | 90.00 | 0.30 | 137.83 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | Z02_S02_E03_G1_TB1_INFERIOR V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 5.06 | 5.06 | 5.06 | 180.00 | 90.00 | 0.30 | 16.88 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | iz-Z01_S01_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 353.73 | 353.73 | 353.73 | 180.00 | 180.00 | 18.81 | 18.81 | 0.00 | Z01_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
| 50 | Z02_S01_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 353.73 | 353.73 | 353.73 | 180.00 | 0.00 | 18.81 | 18.81 | 0.00 | iz-Z02_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 12 | ||
| 51 | Z02_P03 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | FURNIT_INTERNALMASS | 3.600 | 3.600 | 175.47 | 175.47 | 175.47 | 0.00 | 90.00 | 175.47 | 1.00 | 0.00 | Z02_P03 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 52 | Z02_S01_E06 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 6.552 | 151.77 | 151.77 | 151.77 | 0.00 | 90.00 | 151.77 | 1.00 | 0.00 | Z02_S01_E06 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 53 | Z03_S01_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.18 | 43.81 | 15.01 | 270.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | Z03_S01_E03_G1 | Window | Z03_S01_E03 | Window5 Detailed Fenestration | WINDOW11 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 270.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | Z03_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 23.64 | 59.10 | 30.48 | 180.00 | 90.00 | 19.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 56 | Z03_S01_E04_G1 | Window | Z03_S01_E04 | Window5 Detailed Fenestration | WINDOW12 | N/A | 3.004 | No | 28.62 | 28.62 | 28.62 | 180.00 | 90.00 | 14.86 | 1.93 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 57 | Z03_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.17 | 43.81 | 15.01 | 90.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 58 | Z03_S01_E05_G1 | Window | Z03_S01_E05 | Window5 Detailed Fenestration | WINDOW13 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 90.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 59 | Z03_S02_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 16.24 | 20.08 | 17.59 | 0.00 | 90.00 | 6.69 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 60 | Z03_S02_E03_G1 | Window | Z03_S02_E03 | Window5 Detailed Fenestration | WINDOW10 | N/A | 3.004 | No | 1.45 | 1.45 | 1.45 | 0.00 | 90.00 | 1.98 | 0.74 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.77 | 0.23 | 4 |
| 61 | Z03_S03_E04_G1 | Window | Z03_S02_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 62 | Z03_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 90.00 | 90.00 | 2.11 | 3.00 | 0.00 | iz-Z03_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | Z03_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 0.00 | 90.00 | 1.09 | 3.00 | 0.00 | iz-Z03_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | Z03_S02_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.93 | 6.62E-002 | 4 | ||
| 65 | Z03_S02_E09 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 0.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.19E-002 | 4 | ||
| 66 | Z03_S02_E11 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.22 | 9.22 | 9.22 | 0.00 | 90.00 | 3.07 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.74 | 0.26 | 4 | ||
| 67 | Z03_S03_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 270.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 68 | Z03_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.01 | 12.61 | 11.57 | 0.00 | 90.00 | 4.20 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 69 | Z03_S04_E03_G1 | Window | Z03_S04_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 70 | Z03_S04_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 90.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 71 | Z03_S04_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 270.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 | ||
| 72 | Z03_S01_TB02 EF | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 3.60 | 3.60 | 3.60 | 180.00 | 90.00 | 0.30 | 12.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 73 | Z03_S01_TB03 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 41.38 | 41.38 | 41.38 | 180.00 | 90.00 | 0.30 | 137.94 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 74 | Z03_S02_E03_G1_TB1_INFERIOR V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 5.06 | 5.06 | 5.06 | 180.00 | 90.00 | 0.30 | 16.88 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | iz-Z02_S01_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 353.73 | 353.73 | 353.73 | 180.00 | 180.00 | 18.81 | 18.81 | 0.00 | Z02_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
| 76 | Z03_S01_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 353.73 | 353.73 | 353.73 | 180.00 | 0.00 | 18.81 | 18.81 | 0.00 | iz-Z03_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 12 | ||
| 77 | Z03_P04 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | FURNIT_INTERNALMASS | 3.600 | 3.600 | 175.47 | 175.47 | 175.47 | 0.00 | 90.00 | 175.47 | 1.00 | 0.00 | Z03_P04 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 78 | Z03_S01_E06 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 6.552 | 151.77 | 151.77 | 151.77 | 0.00 | 90.00 | 151.77 | 1.00 | 0.00 | Z03_S01_E06 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 79 | Z04_S01_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.18 | 43.81 | 15.01 | 270.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 80 | Z04_S01_E03_G1 | Window | Z04_S01_E03 | Window5 Detailed Fenestration | WINDOW14 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 270.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 81 | Z04_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 23.64 | 59.10 | 30.48 | 180.00 | 90.00 | 19.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | Z04_S01_E04_G1 | Window | Z04_S01_E04 | Window5 Detailed Fenestration | WINDOW15 | N/A | 3.004 | No | 28.62 | 28.62 | 28.62 | 180.00 | 90.00 | 14.86 | 1.93 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 83 | Z04_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.17 | 43.81 | 15.01 | 90.00 | 90.00 | 14.60 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | Z04_S01_E05_G1 | Window | Z04_S01_E05 | Window5 Detailed Fenestration | WINDOW16 | N/A | 2.302 | No | 28.80 | 28.80 | 28.80 | 90.00 | 90.00 | 12.60 | 2.29 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 85 | Z04_S02_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 16.24 | 20.08 | 17.59 | 0.00 | 90.00 | 6.69 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | Z04_S02_E03_G1 | Window | Z04_S02_E03 | Window5 Detailed Fenestration | WINDOW10 | N/A | 3.004 | No | 1.45 | 1.45 | 1.45 | 0.00 | 90.00 | 1.98 | 0.74 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.77 | 0.23 | 4 |
| 87 | Z04_S03_E04_G1 | Window | Z04_S02_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 88 | Z04_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 90.00 | 90.00 | 2.11 | 3.00 | 0.00 | iz-Z04_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 89 | Z04_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 0.00 | 90.00 | 1.09 | 3.00 | 0.00 | iz-Z04_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | Z04_S02_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.93 | 7.30E-002 | 4 | ||
| 91 | Z04_S02_E09 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 0.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.48E-002 | 4 | ||
| 92 | Z04_S02_E11 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.22 | 9.22 | 9.22 | 0.00 | 90.00 | 3.07 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 | ||
| 93 | Z04_S03_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 270.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 94 | Z04_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.01 | 12.61 | 11.57 | 0.00 | 90.00 | 4.20 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 95 | Z04_S04_E03_G1 | Window | Z04_S04_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 96 | Z04_S04_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.91 | 13.91 | 13.91 | 90.00 | 90.00 | 4.64 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | Z04_S04_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 270.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.78 | 0.22 | 4 | ||
| 98 | Z04_S01_TB02 EF | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 3.60 | 3.60 | 3.60 | 180.00 | 90.00 | 0.30 | 12.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | Z04_S01_TB03 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 41.38 | 41.38 | 41.38 | 180.00 | 90.00 | 0.30 | 137.94 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 100 | Z04_S02_E03_G1_TB1_INFERIOR V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 5.06 | 5.06 | 5.06 | 180.00 | 90.00 | 0.30 | 16.88 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 101 | iz-Z03_S01_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 353.73 | 353.73 | 353.73 | 180.00 | 180.00 | 18.81 | 18.81 | 0.00 | Z03_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
| 102 | Z04_S01_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 353.73 | 353.73 | 353.73 | 180.00 | 0.00 | 18.81 | 18.81 | 0.00 | iz-Z04_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 12 | ||
| 103 | Z04_P05 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | FURNIT_INTERNALMASS | 3.600 | 3.600 | 175.47 | 175.47 | 175.47 | 0.00 | 90.00 | 175.47 | 1.00 | 0.00 | Z04_P05 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 104 | Z04_S01_E06 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 6.552 | 151.77 | 151.77 | 151.77 | 0.00 | 90.00 | 151.77 | 1.00 | 0.00 | Z04_S01_E06 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 105 | Z05_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.33 | 44.54 | 15.24 | 270.00 | 90.00 | 14.60 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 106 | Z05_S01_E04_G1 | Window | Z05_S01_E04 | Window5 Detailed Fenestration | WINDOW17 | N/A | 2.302 | No | 29.30 | 29.30 | 29.30 | 270.00 | 90.00 | 12.60 | 2.33 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 107 | Z05_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 24.03 | 60.09 | 30.99 | 180.00 | 90.00 | 19.70 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 108 | Z05_S01_E05_G1 | Window | Z05_S01_E05 | Window5 Detailed Fenestration | WINDOW18 | N/A | 3.004 | No | 29.10 | 29.10 | 29.10 | 180.00 | 90.00 | 14.86 | 1.96 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 109 | Z05_S01_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.33 | 44.54 | 15.24 | 90.00 | 90.00 | 14.60 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | Z05_S01_E06_G1 | Window | Z05_S01_E06 | Window5 Detailed Fenestration | WINDOW19 | N/A | 2.302 | No | 29.30 | 29.30 | 29.30 | 90.00 | 90.00 | 12.60 | 2.33 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 111 | Z05_S02_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 16.58 | 20.42 | 17.92 | 0.00 | 90.00 | 6.69 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 112 | Z05_S02_E03_G1 | Window | Z05_S02_E03 | Window5 Detailed Fenestration | WINDOW10 | N/A | 3.004 | No | 1.45 | 1.45 | 1.45 | 0.00 | 90.00 | 1.98 | 0.74 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.77 | 0.23 | 4 |
| 113 | Z05_S03_E04_G1 | Window | Z05_S02_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 114 | Z05_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.44 | 6.44 | 6.44 | 90.00 | 90.00 | 2.11 | 3.05 | 0.00 | iz-Z05_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 115 | Z05_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.33 | 3.33 | 3.33 | 0.00 | 90.00 | 1.09 | 3.05 | 0.00 | iz-Z05_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
| 116 | Z05_S02_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.98 | 1.98 | 1.98 | 90.00 | 90.00 | 0.65 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.88 | 0.12 | 4 | ||
| 117 | Z05_S02_E09 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.66 | 10.66 | 10.66 | 0.00 | 90.00 | 3.50 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.90 | 0.10 | 4 | ||
| 118 | Z05_S02_E11 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.37 | 9.37 | 9.37 | 0.00 | 90.00 | 3.07 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 | ||
| 119 | Z05_S03_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 14.14 | 14.14 | 14.14 | 270.00 | 90.00 | 4.64 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | Z05_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.22 | 12.82 | 11.78 | 0.00 | 90.00 | 4.20 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 121 | Z05_S04_E03_G1 | Window | Z05_S04_E03 | Window5 Detailed Fenestration | WINDOW6 | N/A | 3.004 | No | 1.04 | 1.04 | 1.04 | 0.00 | 90.00 | 1.36 | 0.76 | 0.48 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 |
| 122 | Z05_S04_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 14.14 | 14.14 | 14.14 | 90.00 | 90.00 | 4.64 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 123 | Z05_S04_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.75 | 8.75 | 8.75 | 270.00 | 90.00 | 2.87 | 3.05 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.70 | 0.30 | 4 | ||
| 124 | Z05_S01_TB02 EF | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 3.66 | 3.66 | 3.66 | 180.00 | 90.00 | 0.30 | 12.20 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | Z05_S01_TB03 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 20.69 | 20.69 | 20.69 | 180.00 | 90.00 | 0.30 | 68.97 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | Z05_S01_TB13 FC | Wall | CTF - ConductionTransferFunction | TBW_0_51667U_ | 1.935 | 1.501 | 20.46 | 20.46 | 20.46 | 180.00 | 90.00 | 0.30 | 68.22 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 127 | Z05_S02_E03_G1_TB1_INFERIOR V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 5.06 | 5.06 | 5.06 | 180.00 | 90.00 | 0.30 | 16.88 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 128 | iz-Z04_S01_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 353.73 | 353.73 | 353.73 | 180.00 | 180.00 | 18.81 | 18.81 | 0.00 | Z04_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
| 129 | Z05_S01_E02 | Roof | CTF - ConductionTransferFunction | CUBIERTA | 0.406 | 0.377 | 7.29 | 7.29 | 7.29 | 180.00 | 0.00 | 2.70 | 2.70 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.00 | 1.00 | 9.99E-016 | 1.00 | 8 | ||
| 130 | Z05_S01_E03 | Roof | CTF - ConductionTransferFunction | CUBIERTA | 0.406 | 0.377 | 345.84 | 345.84 | 345.84 | 180.00 | 0.00 | 18.60 | 18.60 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 12 | ||
| 131 | Z05_P06 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | FURNIT_INTERNALMASS | 3.600 | 3.600 | 175.47 | 175.47 | 175.47 | 0.00 | 90.00 | 175.47 | 1.00 | 0.00 | Z05_P06 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 132 | Z05_S01_E07 FURNITURE | Internal Mass | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 6.552 | 154.30 | 154.30 | 154.30 | 0.00 | 90.00 | 154.30 | 1.00 | 0.00 | Z05_S01_E07 FURNITURE | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 133 | Z06_S01_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 14.09 | 14.09 | 14.09 | 0.00 | 90.00 | 4.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | Z06_S01_E04 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 6.83 | 6.83 | 6.83 | 270.00 | 90.00 | 2.28 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 135 | Z06_S01_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 180.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | ||
| 136 | Z06_S01_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 | ||
| 137 | Z06_S01_E07 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 3.28 | 3.28 | 3.28 | 180.00 | 90.00 | 1.09 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | Z06_S01_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.11 | 9.11 | 9.11 | 90.00 | 90.00 | 3.04 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 139 | Z06_S02_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.04 | 14.09 | 13.41 | 0.00 | 90.00 | 4.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | Z06_S02_E03_G1 | Window | Z06_S02_E03 | Window5 Detailed Fenestration | WINDOW20 | N/A | 3.004 | No | 0.68 | 0.68 | 0.68 | 0.00 | 90.00 | 0.85 | 0.80 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.82 | 0.18 | 4 |
| 141 | Z06_S02_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 180.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.39E-002 | 4 | ||
| 142 | Z06_S02_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 7.83E-002 | 4 | ||
| 143 | Z06_S02_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 90.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 | ||
| 144 | Z06_S03_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.04 | 14.09 | 13.41 | 0.00 | 90.00 | 4.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 145 | Z06_S03_E03_G1 | Window | Z06_S03_E03 | Window5 Detailed Fenestration | WINDOW20 | N/A | 3.004 | No | 0.68 | 0.68 | 0.68 | 0.00 | 90.00 | 0.85 | 0.80 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.82 | 0.18 | 4 |
| 146 | Z06_S03_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 180.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.41E-002 | 4 | ||
| 147 | Z06_S03_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 7.84E-002 | 4 | ||
| 148 | Z06_S03_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 90.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.79 | 0.21 | 4 | ||
| 149 | Z06_S04_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.04 | 14.09 | 13.41 | 0.00 | 90.00 | 4.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | Z06_S04_E03_G1 | Window | Z06_S04_E03 | Window5 Detailed Fenestration | WINDOW20 | N/A | 3.004 | No | 0.68 | 0.68 | 0.68 | 0.00 | 90.00 | 0.85 | 0.80 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.82 | 0.18 | 4 |
| 151 | Z06_S04_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 180.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.45E-002 | 4 | ||
| 152 | Z06_S04_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.92 | 8.02E-002 | 4 | ||
| 153 | Z06_S04_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 90.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.78 | 0.22 | 4 | ||
| 154 | Z06_S05_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 13.04 | 14.09 | 13.41 | 0.00 | 90.00 | 4.70 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 155 | Z06_S05_E03_G1 | Window | Z06_S05_E03 | Window5 Detailed Fenestration | WINDOW20 | N/A | 3.004 | No | 0.68 | 0.68 | 0.68 | 0.00 | 90.00 | 0.85 | 0.80 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.82 | 0.18 | 4 |
| 156 | Z06_S05_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 10.49 | 10.49 | 10.49 | 180.00 | 90.00 | 3.50 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.91 | 8.66E-002 | 4 | ||
| 157 | Z06_S05_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.65 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.91 | 8.54E-002 | 4 | ||
| 158 | Z06_S05_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 8.61 | 8.61 | 8.61 | 90.00 | 90.00 | 2.87 | 3.00 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.77 | 0.23 | 4 | ||
| 159 | Z06_S06_E03 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 14.45 | 15.50 | 14.82 | 0.00 | 90.00 | 4.70 | 3.30 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | Z06_S06_E03_G1 | Window | Z06_S06_E03 | Window5 Detailed Fenestration | WINDOW20 | N/A | 3.004 | No | 0.68 | 0.68 | 0.68 | 0.00 | 90.00 | 0.85 | 0.80 | 0.47 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.82 | 0.18 | 4 |
| 161 | Z06_S06_E05 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 11.54 | 11.54 | 11.54 | 180.00 | 90.00 | 3.50 | 3.30 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.85 | 0.15 | 4 | ||
| 162 | Z06_S06_E06 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 2.15 | 2.15 | 2.15 | 270.00 | 90.00 | 0.65 | 3.30 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.85 | 0.15 | 4 | ||
| 163 | Z06_S06_E08 | Wall | CTF - ConductionTransferFunction | MURO_EXTERIOR | 0.744 | 0.669 | 9.47 | 9.47 | 9.47 | 90.00 | 90.00 | 2.87 | 3.30 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.50 | 0.50 | 0.67 | 0.33 | 4 | ||
| 164 | Z06_S01_TB03 FS | Wall | CTF - ConductionTransferFunction | TBW_1_85U_ | 0.541 | 0.500 | 1.41 | 1.41 | 1.41 | 180.00 | 90.00 | 0.30 | 4.70 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | Z06_S01_TB04 FF | Wall | CTF - ConductionTransferFunction | TBW_0_15577U_ | 6.420 | 3.274 | 16.82 | 16.82 | 16.82 | 180.00 | 90.00 | 0.30 | 56.07 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 166 | Z06_S02_E03_G1_TB1_INFERIOR V | Wall | CTF - ConductionTransferFunction | TBW_0_6U_ | 1.667 | 1.334 | 6.15 | 6.15 | 6.15 | 180.00 | 90.00 | 0.30 | 20.50 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | iz-Z01_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 270.00 | 90.00 | 2.11 | 3.00 | 0.00 | Z01_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 168 | iz-Z01_S02_E06 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 180.00 | 90.00 | 1.09 | 3.00 | 0.00 | Z01_S02_E06 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 169 | iz-Z02_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 270.00 | 90.00 | 2.11 | 3.00 | 0.00 | Z02_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 170 | iz-Z02_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 180.00 | 90.00 | 1.09 | 3.00 | 0.00 | Z02_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | iz-Z03_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 270.00 | 90.00 | 2.11 | 3.00 | 0.00 | Z03_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | iz-Z03_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 180.00 | 90.00 | 1.09 | 3.00 | 0.00 | Z03_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | iz-Z04_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.33 | 6.33 | 6.33 | 270.00 | 90.00 | 2.11 | 3.00 | 0.00 | Z04_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | iz-Z04_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.28 | 3.28 | 3.28 | 180.00 | 90.00 | 1.09 | 3.00 | 0.00 | Z04_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 175 | iz-Z05_S02_E04 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 6.44 | 6.44 | 6.44 | 270.00 | 90.00 | 2.11 | 3.05 | 0.00 | Z05_S02_E04 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 176 | iz-Z05_S02_E05 | Wall | CTF - ConductionTransferFunction | PARTICION_INTERIOR | 6.552 | 3.308 | 3.33 | 3.33 | 3.33 | 180.00 | 90.00 | 1.09 | 3.05 | 0.00 | Z05_S02_E05 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | Z06_S01_E01 | Floor | CTF - ConductionTransferFunction | SUELO (INV) | 0.535 | 0.473 | 11.53 | 11.53 | 11.53 | 90.00 | 180.00 | 3.40 | 3.40 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | NoSun | WindExposed | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 178 | iz-Z06_S01_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 10.75 | 10.75 | 10.75 | 90.00 | 180.00 | 3.28 | 3.28 | 0.00 | Z06_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 179 | iz-Z06_S02_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 10.75 | 10.75 | 10.75 | 90.00 | 180.00 | 3.28 | 3.28 | 0.00 | Z06_S02_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 180 | iz-Z06_S03_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 10.75 | 10.75 | 10.75 | 90.00 | 180.00 | 3.28 | 3.28 | 0.00 | Z06_S03_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 181 | iz-Z06_S04_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 10.75 | 10.75 | 10.75 | 90.00 | 180.00 | 3.28 | 3.28 | 0.00 | Z06_S04_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 182 | iz-Z06_S05_E02 | Floor | CTF - ConductionTransferFunction | iz-FORJADO_INTERIOR | 5.674 | 2.385 | 10.75 | 10.75 | 10.75 | 90.00 | 180.00 | 3.28 | 3.28 | 0.00 | Z06_S05_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
| 183 | Z06_S01_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 10.75 | 10.75 | 10.75 | 270.00 | 0.00 | 3.28 | 3.28 | 0.00 | iz-Z06_S01_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
| 184 | Z06_S02_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 10.75 | 10.75 | 10.75 | 270.00 | 0.00 | 3.28 | 3.28 | 0.00 | iz-Z06_S02_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
| 185 | Z06_S03_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 10.75 | 10.75 | 10.75 | 270.00 | 0.00 | 3.28 | 3.28 | 0.00 | iz-Z06_S03_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
| 186 | Z06_S04_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 10.75 | 10.75 | 10.75 | 270.00 | 0.00 | 3.28 | 3.28 | 0.00 | iz-Z06_S04_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
| 187 | Z06_S05_E02 | Roof | CTF - ConductionTransferFunction | FORJADO_INTERIOR | 5.674 | 2.742 | 10.75 | 10.75 | 10.75 | 270.00 | 0.00 | 3.28 | 3.28 | 0.00 | iz-Z06_S05_E02 | Other/Same Surface Int Conv | User Supplied Value | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
| 188 | Z06_S06_E02 | Roof | CTF - ConductionTransferFunction | CUBIERTA | 0.406 | 0.377 | 9.68 | 9.68 | 9.68 | 270.00 | 0.00 | 3.11 | 3.11 | 0.00 | ExternalEnvironment | User Supplied Value | User Supplied Value | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | |
| 1 | Z01_S01_E03 (191MM) | Frame | Z01_S01_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 2 | Z01_S01_E04 (199MM) | Frame | Z01_S01_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 6.84 | 6.84 | * | N/A | N/A | 0.20 | N/A | |||
| 3 | Z01_S01_E05 (191MM) | Frame | Z01_S01_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 4 | PUERTA_ACCESO_A_EDIFICIO_165_170_ (52MM) | Frame | Z01_S02_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.42 | 0.42 | * | N/A | N/A | 5.20E-002 | N/A | |||
| 5 | N_VESTIBULO_255_260_ (245MM) | Frame | Z01_S02_E04_G2 | Window5 Detailed Fenestration | N/A | N/A | 2.23 | 2.23 | * | N/A | N/A | 0.25 | N/A | |||
| 6 | N_160_165_ (118MM) | Frame | Z01_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 7 | Z02_S01_E03 (191MM) | Frame | Z02_S01_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 8 | Z02_S01_E04 (199MM) | Frame | Z02_S01_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 6.84 | 6.84 | * | N/A | N/A | 0.20 | N/A | |||
| 9 | Z02_S01_E05 (191MM) | Frame | Z02_S01_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 10 | N_220_225_ (132MM) | Frame | Z02_S02_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.79 | 0.79 | * | N/A | N/A | 0.13 | N/A | |||
| 11 | N_160_165_ (118MM) | Frame | Z02_S03_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 12 | N_160_165_ (118MM) | Frame | Z02_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 13 | Z03_S01_E03 (191MM) | Frame | Z03_S01_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 14 | Z03_S01_E04 (199MM) | Frame | Z03_S01_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 6.84 | 6.84 | * | N/A | N/A | 0.20 | N/A | |||
| 15 | Z03_S01_E05 (191MM) | Frame | Z03_S01_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 16 | N_220_225_ (132MM) | Frame | Z03_S02_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.79 | 0.79 | * | N/A | N/A | 0.13 | N/A | |||
| 17 | N_160_165_ (118MM) | Frame | Z03_S03_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 18 | N_160_165_ (118MM) | Frame | Z03_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 19 | Z04_S01_E03 (191MM) | Frame | Z04_S01_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 20 | Z04_S01_E04 (199MM) | Frame | Z04_S01_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 6.84 | 6.84 | * | N/A | N/A | 0.20 | N/A | |||
| 21 | Z04_S01_E05 (191MM) | Frame | Z04_S01_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.83 | 5.83 | * | N/A | N/A | 0.19 | N/A | |||
| 22 | N_220_225_ (132MM) | Frame | Z04_S02_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.79 | 0.79 | * | N/A | N/A | 0.13 | N/A | |||
| 23 | N_160_165_ (118MM) | Frame | Z04_S03_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 24 | N_160_165_ (118MM) | Frame | Z04_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 25 | Z05_S01_E04 (193MM) | Frame | Z05_S01_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.91 | 5.91 | * | N/A | N/A | 0.19 | N/A | |||
| 26 | Z05_S01_E05 (202MM) | Frame | Z05_S01_E05_G1 | Window5 Detailed Fenestration | N/A | N/A | 6.96 | 6.96 | * | N/A | N/A | 0.20 | N/A | |||
| 27 | Z05_S01_E06 (193MM) | Frame | Z05_S01_E06_G1 | Window5 Detailed Fenestration | N/A | N/A | 5.91 | 5.91 | * | N/A | N/A | 0.19 | N/A | |||
| 28 | N_220_225_ (132MM) | Frame | Z05_S02_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.79 | 0.79 | * | N/A | N/A | 0.13 | N/A | |||
| 29 | N_160_165_ (118MM) | Frame | Z05_S03_E04_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 30 | N_160_165_ (118MM) | Frame | Z05_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.56 | 0.56 | * | N/A | N/A | 0.12 | N/A | |||
| 31 | N_105_110_ (99MM) | Frame | Z06_S02_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.37 | 0.37 | * | N/A | N/A | 9.90E-002 | N/A | |||
| 32 | N_105_110_ (99MM) | Frame | Z06_S03_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.37 | 0.37 | * | N/A | N/A | 9.90E-002 | N/A | |||
| 33 | N_105_110_ (99MM) | Frame | Z06_S04_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.37 | 0.37 | * | N/A | N/A | 9.90E-002 | N/A | |||
| 34 | N_105_110_ (99MM) | Frame | Z06_S05_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.37 | 0.37 | * | N/A | N/A | 9.90E-002 | N/A | |||
| 35 | N_105_110_ (99MM) | Frame | Z06_S06_E03_G1 | Window5 Detailed Fenestration | N/A | N/A | 0.37 | 0.37 | * | N/A | N/A | 9.90E-002 | N/A |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2007 | 12/31/2007 | Monday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | WeatherFile | 03/25 | 10/28 |
| NumberofWarmupDays | |
| 1 | 9 |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | Z01_P02 | RunPeriod: RUNPERIOD 1 | 8.2977563601E-002 | 0.3441123818 | Pass | Pass | 0.5872737670 | 2.6263760647 | Pass | Pass |
| 2 | Z02_P03 | RunPeriod: RUNPERIOD 1 | 4.7097984824E-002 | 0.1958609493 | Pass | Pass | 0.2683558164 | 1.1569161062 | Pass | Pass |
| 3 | Z03_P04 | RunPeriod: RUNPERIOD 1 | 4.0496005185E-002 | 0.1753943986 | Pass | Pass | 0.1783848498 | 0.6736087745 | Pass | Pass |
| 4 | Z04_P05 | RunPeriod: RUNPERIOD 1 | 4.4854544493E-002 | 0.1894240137 | Pass | Pass | 0.2111856643 | 0.7844926569 | Pass | Pass |
| 5 | Z05_P06 | RunPeriod: RUNPERIOD 1 | 7.3793068237E-002 | 0.2865553039 | Pass | Pass | 0.2703465749 | 0.9198087925 | Pass | Pass |
| 6 | Z06_ESCALERAS | RunPeriod: RUNPERIOD 1 | 3.4291592330E-002 | 5.7380322332E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Annual Heat Emissions Summary| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [kWh] | 442827.28 | 8116.99 | 0.00 | 0.00 | 0.00 | 450939.21 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7°C, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] | Danger (> 39.4°C, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| Z01_P02 | 7736.75 | 1022.25 | 1.00 | 0.00 | 0.00 |
| Z02_P03 | 7600.25 | 1159.75 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 7555.75 | 1204.25 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 7562.50 | 1197.50 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 7653.00 | 1107.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 7633.50 | 1126.50 | 0.00 | 0.00 | 0.00 |
| Min | 7555.75 | 1022.25 | 0.00 | 0.00 | 0.00 |
| Max | 7736.75 | 1204.25 | 1.00 | 0.00 | 0.00 |
| Average | 7623.62 | 1136.21 | 0.17 | 0.00 | 0.00 |
| Sum | 45741.75 | 6817.25 | 1.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7°C, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] | Danger (> 39.4°C, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| Z01_P02 | 121899.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 121899.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 121899.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 121899.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 121899.70 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 20043.23 | 2622.39 | 0.00 | 0.00 | 0.00 |
| Min | 20043.23 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 121899.70 | 2622.39 | 0.00 | 0.00 | 0.00 |
| Average | 104923.62 | 437.06 | 0.00 | 0.00 | 0.00 |
| Sum | 629541.73 | 2622.39 | 0.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7°C, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] | Danger (> 39.4°C, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| Z01_P02 | 3548.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 3548.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 3548.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 3548.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 3548.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 3137.50 | 410.50 | 0.00 | 0.00 | 0.00 |
| Min | 3137.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 3548.00 | 410.50 | 0.00 | 0.00 | 0.00 |
| Average | 3479.58 | 68.42 | 0.00 | 0.00 | 0.00 |
| Sum | 20877.50 | 410.50 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| Z01_P02 | 7916.50 | 843.50 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 7834.00 | 926.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 7804.25 | 955.75 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 7809.00 | 951.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 7852.00 | 908.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 7673.25 | 1086.75 | 0.00 | 0.00 | 0.00 |
| Min | 7673.25 | 843.50 | 0.00 | 0.00 | 0.00 |
| Max | 7916.50 | 1086.75 | 0.00 | 0.00 | 0.00 |
| Average | 7814.83 | 945.17 | 0.00 | 0.00 | 0.00 |
| Sum | 46889.00 | 5671.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| Z01_P02 | 121453.06 | 446.64 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 121564.72 | 334.98 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 121607.66 | 292.04 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 121624.84 | 274.86 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 121590.48 | 309.22 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 20035.24 | 2630.37 | 0.00 | 0.00 | 0.00 |
| Min | 20035.24 | 274.86 | 0.00 | 0.00 | 0.00 |
| Max | 121624.84 | 2630.37 | 0.00 | 0.00 | 0.00 |
| Average | 104646.00 | 714.69 | 0.00 | 0.00 | 0.00 |
| Sum | 627876.01 | 4288.11 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| Z01_P02 | 3535.00 | 13.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 3538.25 | 9.75 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 3539.50 | 8.50 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 3540.00 | 8.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 3539.00 | 9.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 3136.25 | 411.75 | 0.00 | 0.00 | 0.00 |
| Min | 3136.25 | 8.00 | 0.00 | 0.00 | 0.00 |
| Max | 3540.00 | 411.75 | 0.00 | 0.00 | 0.00 |
| Average | 3471.33 | 76.67 | 0.00 | 0.00 | 0.00 |
| Sum | 20828.00 | 460.00 | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| Z01_P02 | 100.75 | 05-JAN-04:45 | 333.50 | 0.00 | 0.00 |
| Z02_P03 | 171.50 | 08-JAN-03:30 | 60.00 | 0.00 | 0.00 |
| Z03_P04 | 332.50 | 14-JAN-20:30 | 36.25 | 0.00 | 0.00 |
| Z04_P05 | 173.50 | 08-JAN-05:30 | 44.50 | 0.00 | 0.00 |
| Z05_P06 | 169.00 | 08-JAN-01:00 | 187.25 | 0.00 | 0.00 |
| Z06_ESCALERAS | 0.00 | 01-JAN-00:00 | 4310.75 | 11558.00 | 1809.25 |
| Min | 0.00 | - | 36.25 | 0.00 | 0.00 |
| Max | 332.50 | - | 4310.75 | 11558.00 | 1809.25 |
| Average | 157.88 | - | 828.71 | 1926.33 | 301.54 |
| Sum | 947.25 | - | 4972.25 | 11558.00 | 1809.25 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| Z01_P02 | 4118.75 | 21-JUN-14:45 | 106.00 | 0.00 | 0.00 |
| Z02_P03 | 4118.75 | 21-JUN-14:45 | 90.00 | 0.00 | 0.00 |
| Z03_P04 | 4118.75 | 21-JUN-14:45 | 94.25 | 0.00 | 0.00 |
| Z04_P05 | 4118.75 | 21-JUN-14:45 | 96.25 | 0.00 | 0.00 |
| Z05_P06 | 4118.75 | 21-JUN-14:45 | 96.25 | 0.00 | 0.00 |
| Z06_ESCALERAS | 4864.25 | 22-JUL-16:15 | 59.75 | 170.89 | 26.75 |
| Min | 4118.75 | - | 59.75 | 0.00 | 0.00 |
| Max | 4864.25 | - | 106.00 | 170.89 | 26.75 |
| Average | 4243.00 | - | 90.42 | 28.48 | 4.46 |
| Sum | 25458.00 | - | 542.50 | 170.89 | 26.75 |
| Cooling Setpoint Unmet Degree-Hours [°C·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°C·hr] | Heating Setpoint Unmet Degree-Hours [°C·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
| Z01_P02 | 0.18 | 6.27 | 0.18 | 0.20 | 6.73 | 0.20 |
| Z02_P03 | 0.15 | 5.24 | 0.15 | 0.07 | 2.33 | 0.07 |
| Z03_P04 | 0.17 | 5.77 | 0.17 | 0.05 | 1.64 | 0.05 |
| Z04_P05 | 0.17 | 5.81 | 0.17 | 0.06 | 2.07 | 0.06 |
| Z05_P06 | 0.15 | 4.99 | 0.15 | 0.22 | 7.53 | 0.22 |
| Z06_ESCALERAS | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.18 | 6.27 | 0.18 | 0.22 | 7.53 | 0.22 |
| Average | 0.14 | 4.68 | 0.14 | 0.10 | 3.38 | 0.10 |
| Sum | 0.82 | 28.08 | 0.82 | 0.59 | 20.30 | 0.59 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| Z01_P02 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| Z01_P02 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| None |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 0.00 | 0 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| Z01_S01_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.18 | 270.00 | 90.00 | W |
| Z01_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 59.10 | 23.64 | 180.00 | 90.00 | S |
| Z01_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.17 | 90.00 | 90.00 | E |
| Z01_S02_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 20.08 | 9.48 | 0.00 | 90.00 | N |
| Z01_S02_E09 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 90.00 | 90.00 | E |
| Z01_S02_E10 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 0.00 | 90.00 | N |
| Z01_S02_E12 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.22 | 9.22 | 0.00 | 90.00 | N |
| Z01_S03_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 270.00 | 90.00 | W |
| Z01_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 12.61 | 11.01 | 0.00 | 90.00 | N |
| Z01_S04_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 90.00 | 90.00 | E |
| Z01_S04_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 270.00 | 90.00 | W |
| Z01_S01_TB02 EF | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 3.60 | 3.60 | 180.00 | 90.00 | S |
| Z01_S01_TB03 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 55.58 | 55.58 | 180.00 | 90.00 | S |
| Z01_S02_E04_G1_TB2_LATERALES V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 5.83 | 5.83 | 180.00 | 90.00 | S |
| Z01_S01_E01 | SUELO (INV) | 0.40 | 0.485 | 0.535 | 343.76 | 343.76 | 90.00 | 180.00 | |
| Z02_S01_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.18 | 270.00 | 90.00 | W |
| Z02_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 59.10 | 23.64 | 180.00 | 90.00 | S |
| Z02_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.17 | 90.00 | 90.00 | E |
| Z02_S02_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 20.08 | 16.24 | 0.00 | 90.00 | N |
| Z02_S02_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 90.00 | 90.00 | E |
| Z02_S02_E09 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 0.00 | 90.00 | N |
| Z02_S02_E11 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.22 | 9.22 | 0.00 | 90.00 | N |
| Z02_S03_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 270.00 | 90.00 | W |
| Z02_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 12.61 | 11.01 | 0.00 | 90.00 | N |
| Z02_S04_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 90.00 | 90.00 | E |
| Z02_S04_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 270.00 | 90.00 | W |
| Z02_S01_TB02 EF | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 3.60 | 3.60 | 180.00 | 90.00 | S |
| Z02_S01_TB03 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 41.35 | 41.35 | 180.00 | 90.00 | S |
| Z02_S02_E03_G1_TB1_INFERIOR V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 5.06 | 5.06 | 180.00 | 90.00 | S |
| Z03_S01_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.18 | 270.00 | 90.00 | W |
| Z03_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 59.10 | 23.64 | 180.00 | 90.00 | S |
| Z03_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.17 | 90.00 | 90.00 | E |
| Z03_S02_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 20.08 | 16.24 | 0.00 | 90.00 | N |
| Z03_S02_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 90.00 | 90.00 | E |
| Z03_S02_E09 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 0.00 | 90.00 | N |
| Z03_S02_E11 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.22 | 9.22 | 0.00 | 90.00 | N |
| Z03_S03_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 270.00 | 90.00 | W |
| Z03_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 12.61 | 11.01 | 0.00 | 90.00 | N |
| Z03_S04_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 90.00 | 90.00 | E |
| Z03_S04_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 270.00 | 90.00 | W |
| Z03_S01_TB02 EF | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 3.60 | 3.60 | 180.00 | 90.00 | S |
| Z03_S01_TB03 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 41.38 | 41.38 | 180.00 | 90.00 | S |
| Z03_S02_E03_G1_TB1_INFERIOR V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 5.06 | 5.06 | 180.00 | 90.00 | S |
| Z04_S01_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.18 | 270.00 | 90.00 | W |
| Z04_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 59.10 | 23.64 | 180.00 | 90.00 | S |
| Z04_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 43.81 | 9.17 | 90.00 | 90.00 | E |
| Z04_S02_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 20.08 | 16.24 | 0.00 | 90.00 | N |
| Z04_S02_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 90.00 | 90.00 | E |
| Z04_S02_E09 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 0.00 | 90.00 | N |
| Z04_S02_E11 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.22 | 9.22 | 0.00 | 90.00 | N |
| Z04_S03_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 270.00 | 90.00 | W |
| Z04_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 12.61 | 11.01 | 0.00 | 90.00 | N |
| Z04_S04_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 13.91 | 13.91 | 90.00 | 90.00 | E |
| Z04_S04_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 270.00 | 90.00 | W |
| Z04_S01_TB02 EF | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 3.60 | 3.60 | 180.00 | 90.00 | S |
| Z04_S01_TB03 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 41.38 | 41.38 | 180.00 | 90.00 | S |
| Z04_S02_E03_G1_TB1_INFERIOR V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 5.06 | 5.06 | 180.00 | 90.00 | S |
| Z05_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 44.54 | 9.33 | 270.00 | 90.00 | W |
| Z05_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 60.09 | 24.03 | 180.00 | 90.00 | S |
| Z05_S01_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 44.54 | 9.33 | 90.00 | 90.00 | E |
| Z05_S02_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 20.42 | 16.58 | 0.00 | 90.00 | N |
| Z05_S02_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.98 | 1.98 | 90.00 | 90.00 | E |
| Z05_S02_E09 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.66 | 10.66 | 0.00 | 90.00 | N |
| Z05_S02_E11 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.37 | 9.37 | 0.00 | 90.00 | N |
| Z05_S03_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.14 | 14.14 | 270.00 | 90.00 | W |
| Z05_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 12.82 | 11.22 | 0.00 | 90.00 | N |
| Z05_S04_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.14 | 14.14 | 90.00 | 90.00 | E |
| Z05_S04_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.75 | 8.75 | 270.00 | 90.00 | W |
| Z05_S01_TB02 EF | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 3.66 | 3.66 | 180.00 | 90.00 | S |
| Z05_S01_TB03 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 20.69 | 20.69 | 180.00 | 90.00 | S |
| Z05_S01_TB13 FC | TBW_0_51667U_ | 0.40 | 1.501 | 1.935 | 20.46 | 20.46 | 180.00 | 90.00 | S |
| Z05_S02_E03_G1_TB1_INFERIOR V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 5.06 | 5.06 | 180.00 | 90.00 | S |
| Z05_S01_E02 | CUBIERTA | 0.40 | 0.385 | 0.406 | 7.29 | 7.29 | 180.00 | 0.00 | |
| Z05_S01_E03 | CUBIERTA | 0.40 | 0.385 | 0.406 | 345.84 | 345.84 | 180.00 | 0.00 | |
| Z06_S01_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.09 | 14.09 | 0.00 | 90.00 | N |
| Z06_S01_E04 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 6.83 | 6.83 | 270.00 | 90.00 | W |
| Z06_S01_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 180.00 | 90.00 | S |
| Z06_S01_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 270.00 | 90.00 | W |
| Z06_S01_E07 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 3.28 | 3.28 | 180.00 | 90.00 | S |
| Z06_S01_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.11 | 9.11 | 90.00 | 90.00 | E |
| Z06_S02_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.09 | 13.04 | 0.00 | 90.00 | N |
| Z06_S02_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 180.00 | 90.00 | S |
| Z06_S02_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 270.00 | 90.00 | W |
| Z06_S02_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 90.00 | 90.00 | E |
| Z06_S03_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.09 | 13.04 | 0.00 | 90.00 | N |
| Z06_S03_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 180.00 | 90.00 | S |
| Z06_S03_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 270.00 | 90.00 | W |
| Z06_S03_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 90.00 | 90.00 | E |
| Z06_S04_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.09 | 13.04 | 0.00 | 90.00 | N |
| Z06_S04_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 180.00 | 90.00 | S |
| Z06_S04_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 270.00 | 90.00 | W |
| Z06_S04_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 90.00 | 90.00 | E |
| Z06_S05_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 14.09 | 13.04 | 0.00 | 90.00 | N |
| Z06_S05_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 10.49 | 10.49 | 180.00 | 90.00 | S |
| Z06_S05_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 1.95 | 1.95 | 270.00 | 90.00 | W |
| Z06_S05_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 8.61 | 8.61 | 90.00 | 90.00 | E |
| Z06_S06_E03 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 15.50 | 14.45 | 0.00 | 90.00 | N |
| Z06_S06_E05 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 11.54 | 11.54 | 180.00 | 90.00 | S |
| Z06_S06_E06 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 2.15 | 2.15 | 270.00 | 90.00 | W |
| Z06_S06_E08 | MURO_EXTERIOR | 0.40 | 0.669 | 0.744 | 9.47 | 9.47 | 90.00 | 90.00 | E |
| Z06_S01_TB03 FS | TBW_1_85U_ | 0.40 | 0.500 | 0.541 | 1.41 | 1.41 | 180.00 | 90.00 | S |
| Z06_S01_TB04 FF | TBW_0_15577U_ | 0.40 | 3.274 | 6.420 | 16.82 | 16.82 | 180.00 | 90.00 | S |
| Z06_S02_E03_G1_TB1_INFERIOR V | TBW_0_6U_ | 0.40 | 1.334 | 1.667 | 6.15 | 6.15 | 180.00 | 90.00 | S |
| Z06_S01_E01 | SUELO (INV) | 0.40 | 0.485 | 0.535 | 11.53 | 11.53 | 90.00 | 180.00 | |
| Z06_S06_E02 | CUBIERTA | 0.40 | 0.385 | 0.406 | 9.68 | 9.68 | 270.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| Z01_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 90.00 | 90.00 | E |
| Z01_S02_E06 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 0.00 | 90.00 | N |
| Z01_S01_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 0.00 | |
| Z02_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 90.00 | 90.00 | E |
| Z02_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 0.00 | 90.00 | N |
| iz-Z01_S01_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 180.00 | |
| Z02_S01_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 0.00 | |
| Z03_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 90.00 | 90.00 | E |
| Z03_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 0.00 | 90.00 | N |
| iz-Z02_S01_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 180.00 | |
| Z03_S01_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 0.00 | |
| Z04_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 90.00 | 90.00 | E |
| Z04_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 0.00 | 90.00 | N |
| iz-Z03_S01_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 180.00 | |
| Z04_S01_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 0.00 | |
| Z05_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.44 | 6.44 | 90.00 | 90.00 | E |
| Z05_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.33 | 3.33 | 0.00 | 90.00 | N |
| iz-Z04_S01_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 353.73 | 353.73 | 180.00 | 180.00 | |
| iz-Z01_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 270.00 | 90.00 | W |
| iz-Z01_S02_E06 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 180.00 | 90.00 | S |
| iz-Z02_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 270.00 | 90.00 | W |
| iz-Z02_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 180.00 | 90.00 | S |
| iz-Z03_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 270.00 | 90.00 | W |
| iz-Z03_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 180.00 | 90.00 | S |
| iz-Z04_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.33 | 6.33 | 270.00 | 90.00 | W |
| iz-Z04_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.28 | 3.28 | 180.00 | 90.00 | S |
| iz-Z05_S02_E04 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 6.44 | 6.44 | 270.00 | 90.00 | W |
| iz-Z05_S02_E05 | PARTICION_INTERIOR | 0.40 | 2.550 | 6.552 | 3.33 | 3.33 | 180.00 | 90.00 | S |
| iz-Z06_S01_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 90.00 | 180.00 | |
| iz-Z06_S02_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 90.00 | 180.00 | |
| iz-Z06_S03_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 90.00 | 180.00 | |
| iz-Z06_S04_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 90.00 | 180.00 | |
| iz-Z06_S05_E02 | iz-FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 90.00 | 180.00 | |
| Z06_S01_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 270.00 | 0.00 | |
| Z06_S02_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 270.00 | 0.00 | |
| Z06_S03_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 270.00 | 0.00 | |
| Z06_S04_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 270.00 | 0.00 | |
| Z06_S05_E02 | FORJADO_INTERIOR | 0.40 | 2.244 | 5.674 | 10.75 | 10.75 | 270.00 | 0.00 | |
| Z01_P02 FURNITURE | FURNIT_INTERNALMASS | 0.40 | 3.600 | 175.47 | 0.00 | 90.00 | N | ||
| Z01_S01_E06 FURNITURE | PARTICION_INTERIOR | 0.40 | 6.552 | 151.77 | 0.00 | 90.00 | N | ||
| Z02_P03 FURNITURE | FURNIT_INTERNALMASS | 0.40 | 3.600 | 175.47 | 0.00 | 90.00 | N | ||
| Z02_S01_E06 FURNITURE | PARTICION_INTERIOR | 0.40 | 6.552 | 151.77 | 0.00 | 90.00 | N | ||
| Z03_P04 FURNITURE | FURNIT_INTERNALMASS | 0.40 | 3.600 | 175.47 | 0.00 | 90.00 | N | ||
| Z03_S01_E06 FURNITURE | PARTICION_INTERIOR | 0.40 | 6.552 | 151.77 | 0.00 | 90.00 | N | ||
| Z04_P05 FURNITURE | FURNIT_INTERNALMASS | 0.40 | 3.600 | 175.47 | 0.00 | 90.00 | N | ||
| Z04_S01_E06 FURNITURE | PARTICION_INTERIOR | 0.40 | 6.552 | 151.77 | 0.00 | 90.00 | N | ||
| Z05_P06 FURNITURE | FURNIT_INTERNALMASS | 0.40 | 3.600 | 175.47 | 0.00 | 90.00 | N | ||
| Z05_S01_E07 FURNITURE | PARTICION_INTERIOR | 0.40 | 6.552 | 154.30 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| Z01_S01_E03_G1 | WINDOW | Z01_S01_E03 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z01_S01_E03 | 270.00 | 90.00 | W |
| Z01_S01_E04_G1 | WINDOW2 | Z01_S01_E04 (199MM) | 28.62 | 6.84 | 0.00 | 35.46 | 35.46 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 2.420 | 0.499 | 0.424 | Yes | Z01_S01_E04 | 180.00 | 90.00 | S |
| Z01_S01_E05_G1 | WINDOW3 | Z01_S01_E05 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z01_S01_E05 | 90.00 | 90.00 | E |
| Z01_S02_E04_G1 | WINDOW4 | PUERTA_ACCESO_A_EDIFICIO_165_170_ (52MM) | 3.80 | 0.42 | 0.00 | 4.23 | 4.23 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.048 | 0.666 | 0.594 | No | Z01_S02_E04 | 0.00 | 90.00 | N |
| Z01_S02_E04_G2 | WINDOW5 | N_VESTIBULO_255_260_ (245MM) | 4.14 | 2.23 | 0.00 | 6.38 | 6.38 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.086 | 0.470 | 0.377 | No | Z01_S02_E04 | 0.00 | 90.00 | N |
| Z01_S04_E03_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z01_S04_E03 | 0.00 | 90.00 | N |
| Z02_S01_E03_G1 | WINDOW7 | Z02_S01_E03 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z02_S01_E03 | 270.00 | 90.00 | W |
| Z02_S01_E04_G1 | WINDOW8 | Z02_S01_E04 (199MM) | 28.62 | 6.84 | 0.00 | 35.46 | 35.46 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 2.420 | 0.499 | 0.424 | Yes | Z02_S01_E04 | 180.00 | 90.00 | S |
| Z02_S01_E05_G1 | WINDOW9 | Z02_S01_E05 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z02_S01_E05 | 90.00 | 90.00 | E |
| Z02_S02_E03_G1 | WINDOW10 | N_220_225_ (132MM) | 1.45 | 0.79 | 0.00 | 2.24 | 2.24 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.065 | 0.579 | 0.498 | No | Z02_S02_E03 | 0.00 | 90.00 | N |
| Z02_S03_E05_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z02_S02_E03 | 0.00 | 90.00 | N |
| Z02_S04_E03_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z02_S04_E03 | 0.00 | 90.00 | N |
| Z03_S01_E03_G1 | WINDOW11 | Z03_S01_E03 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z03_S01_E03 | 270.00 | 90.00 | W |
| Z03_S01_E04_G1 | WINDOW12 | Z03_S01_E04 (199MM) | 28.62 | 6.84 | 0.00 | 35.46 | 35.46 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 2.420 | 0.499 | 0.424 | Yes | Z03_S01_E04 | 180.00 | 90.00 | S |
| Z03_S01_E05_G1 | WINDOW13 | Z03_S01_E05 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z03_S01_E05 | 90.00 | 90.00 | E |
| Z03_S02_E03_G1 | WINDOW10 | N_220_225_ (132MM) | 1.45 | 0.79 | 0.00 | 2.24 | 2.24 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.065 | 0.579 | 0.498 | No | Z03_S02_E03 | 0.00 | 90.00 | N |
| Z03_S03_E04_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z03_S02_E03 | 0.00 | 90.00 | N |
| Z03_S04_E03_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z03_S04_E03 | 0.00 | 90.00 | N |
| Z04_S01_E03_G1 | WINDOW14 | Z04_S01_E03 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z04_S01_E03 | 270.00 | 90.00 | W |
| Z04_S01_E04_G1 | WINDOW15 | Z04_S01_E04 (199MM) | 28.62 | 6.84 | 0.00 | 35.46 | 35.46 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 2.420 | 0.499 | 0.424 | Yes | Z04_S01_E04 | 180.00 | 90.00 | S |
| Z04_S01_E05_G1 | WINDOW16 | Z04_S01_E05 (191MM) | 28.80 | 5.83 | 0.00 | 34.63 | 34.63 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.929 | 0.462 | 0.393 | Yes | Z04_S01_E05 | 90.00 | 90.00 | E |
| Z04_S02_E03_G1 | WINDOW10 | N_220_225_ (132MM) | 1.45 | 0.79 | 0.00 | 2.24 | 2.24 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.065 | 0.579 | 0.498 | No | Z04_S02_E03 | 0.00 | 90.00 | N |
| Z04_S03_E04_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z04_S02_E03 | 0.00 | 90.00 | N |
| Z04_S04_E03_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z04_S04_E03 | 0.00 | 90.00 | N |
| Z05_S01_E04_G1 | WINDOW17 | Z05_S01_E04 (193MM) | 29.30 | 5.91 | 0.00 | 35.21 | 35.21 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.931 | 0.460 | 0.392 | Yes | Z05_S01_E04 | 270.00 | 90.00 | W |
| Z05_S01_E05_G1 | WINDOW18 | Z05_S01_E05 (202MM) | 29.10 | 6.96 | 0.00 | 36.05 | 36.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 2.425 | 0.497 | 0.421 | Yes | Z05_S01_E05 | 180.00 | 90.00 | S |
| Z05_S01_E06_G1 | WINDOW19 | Z05_S01_E06 (193MM) | 29.30 | 5.91 | 0.00 | 35.21 | 35.21 | 2.302 | 0.671 | 0.601 | 3.777 | 0.000 | CurtainWall | 1.931 | 0.460 | 0.392 | Yes | Z05_S01_E06 | 90.00 | 90.00 | E |
| Z05_S02_E03_G1 | WINDOW10 | N_220_225_ (132MM) | 1.45 | 0.79 | 0.00 | 2.24 | 2.24 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.065 | 0.579 | 0.498 | No | Z05_S02_E03 | 0.00 | 90.00 | N |
| Z05_S03_E04_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z05_S02_E03 | 0.00 | 90.00 | N |
| Z05_S04_E03_G1 | WINDOW6 | N_160_165_ (118MM) | 1.04 | 0.56 | 0.00 | 1.60 | 1.60 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.062 | 0.594 | 0.514 | No | Z05_S04_E03 | 0.00 | 90.00 | N |
| Z06_S02_E03_G1 | WINDOW20 | N_105_110_ (99MM) | 0.68 | 0.37 | 0.00 | 1.05 | 1.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.058 | 0.614 | 0.537 | No | Z06_S02_E03 | 0.00 | 90.00 | N |
| Z06_S03_E03_G1 | WINDOW20 | N_105_110_ (99MM) | 0.68 | 0.37 | 0.00 | 1.05 | 1.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.058 | 0.614 | 0.537 | No | Z06_S03_E03 | 0.00 | 90.00 | N |
| Z06_S04_E03_G1 | WINDOW20 | N_105_110_ (99MM) | 0.68 | 0.37 | 0.00 | 1.05 | 1.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.058 | 0.614 | 0.537 | No | Z06_S04_E03 | 0.00 | 90.00 | N |
| Z06_S05_E03_G1 | WINDOW20 | N_105_110_ (99MM) | 0.68 | 0.37 | 0.00 | 1.05 | 1.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.058 | 0.614 | 0.537 | No | Z06_S05_E03 | 0.00 | 90.00 | N |
| Z06_S06_E03_G1 | WINDOW20 | N_105_110_ (99MM) | 0.68 | 0.37 | 0.00 | 1.05 | 1.05 | 3.004 | 0.727 | 0.661 | 6.122 | 0.000 | CurtainWall | 3.058 | 0.614 | 0.537 | No | Z06_S06_E03 | 0.00 | 90.00 | N |
| Total or Average | 564.58 | 2.572 | 0.693 | 0.624 | |||||||||||||||||
| North Total or Average | 39.21 | 3.004 | 0.727 | 0.661 | |||||||||||||||||
| Non-North Total or Average | 525.37 | 2.539 | 0.690 | 0.621 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| WINDOW:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z01_S01_E03 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW2:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | Z01_S01_E04 (199MM) | 1.946 | 0.711 | 0.434 | CurtainWall | 2.420 | 0.075 | 0.279 |
| WINDOW3:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z01_S01_E05 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW7:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z02_S01_E03 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW8:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | Z02_S01_E04 (199MM) | 1.946 | 0.711 | 0.434 | CurtainWall | 2.420 | 0.075 | 0.279 |
| WINDOW9:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z02_S01_E05 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW11:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z03_S01_E03 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW12:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | Z03_S01_E04 (199MM) | 1.946 | 0.711 | 0.434 | CurtainWall | 2.420 | 0.075 | 0.279 |
| WINDOW13:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z03_S01_E05 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW14:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z04_S01_E03 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW15:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | Z04_S01_E04 (199MM) | 1.946 | 0.711 | 0.434 | CurtainWall | 2.420 | 0.075 | 0.279 |
| WINDOW16:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z04_S01_E05 (191MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.929 | 0.068 | 0.210 |
| WINDOW17:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z05_S01_E04 (193MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.931 | 0.068 | 0.209 |
| WINDOW18:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | Z05_S01_E05 (202MM) | 1.946 | 0.711 | 0.434 | CurtainWall | 2.425 | 0.076 | 0.277 |
| WINDOW19:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | Z05_S01_E06 (193MM) | 1.626 | 0.657 | 0.321 | CurtainWall | 1.931 | 0.068 | 0.209 |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| Z01_S01_E03_G1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Z01_S01_E04_G1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Z01_S01_E05_G1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Z01_S02_E04_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z01_S02_E04_G2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z01_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_S01_E03_G1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Z02_S01_E04_G1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Z02_S01_E05_G1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Z02_S02_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_S03_E05_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_S01_E03_G1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Z03_S01_E04_G1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Z03_S01_E05_G1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Z03_S02_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_S03_E04_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_S01_E03_G1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Z04_S01_E04_G1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Z04_S01_E05_G1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Z04_S02_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_S03_E04_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_S01_E04_G1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Z05_S01_E05_G1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Z05_S01_E06_G1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| Z05_S02_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_S03_E04_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_S02_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_S03_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_S04_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_S05_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_S06_E03_G1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| Z01_S01_E03_G1 | WSC_CTRL_1_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z01_S01_E04_G1 | WSC_CTRL_1_2_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW2:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z01_S01_E05_G1 | WSC_CTRL_1_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW3:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z02_S01_E03_G1 | WSC_CTRL_2_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW7:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z02_S01_E04_G1 | WSC_CTRL_2_2_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW8:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z02_S01_E05_G1 | WSC_CTRL_2_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW9:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z03_S01_E03_G1 | WSC_CTRL_3_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW11:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z03_S01_E04_G1 | WSC_CTRL_3_2_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW12:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z03_S01_E05_G1 | WSC_CTRL_3_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW13:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z04_S01_E03_G1 | WSC_CTRL_4_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW14:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z04_S01_E04_G1 | WSC_CTRL_4_2_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW15:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z04_S01_E05_G1 | WSC_CTRL_4_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW16:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z05_S01_E04_G1 | WSC_CTRL_5_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW17:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z05_S01_E05_G1 | WSC_CTRL_5_2_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW18:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
| Z05_S01_E06_G1 | WSC_CTRL_5_1_FACTOR_SOLAR_VERANO | Interior Shade | WINDOW19:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
| Z01_P02_IG2 LIGHTS | Z01_P02 | Z01_P02 | GENERAL | 4.0985 | 350.94 | 1438.34 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 5103.23 |
| Z01_P02_IG3 LIGHTS | Z01_P02 | Z01_P02 | GENERAL | 0.4458 | 350.94 | 156.46 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 555.12 |
| Z01_P02_IG4 LIGHTS | Z01_P02 | Z01_P02 | GENERAL | 0.1155 | 350.94 | 40.54 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 143.83 |
| Z01_P02_IG5 LIGHTS | Z01_P02 | Z01_P02 | GENERAL | 0.2500 | 350.94 | 87.73 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.28 |
| Z02_P03_IG2 LIGHTS | Z02_P03 | Z02_P03 | GENERAL | 4.0985 | 350.94 | 1438.34 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 5103.23 |
| Z02_P03_IG3 LIGHTS | Z02_P03 | Z02_P03 | GENERAL | 0.3115 | 350.94 | 109.33 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 387.91 |
| Z02_P03_IG4 LIGHTS | Z02_P03 | Z02_P03 | GENERAL | 0.2498 | 350.94 | 87.67 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.05 |
| Z02_P03_IG5 LIGHTS | Z02_P03 | Z02_P03 | GENERAL | 0.2500 | 350.94 | 87.73 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.28 |
| Z03_P04_IG2 LIGHTS | Z03_P04 | Z03_P04 | GENERAL | 4.0985 | 350.94 | 1438.34 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 5103.23 |
| Z03_P04_IG3 LIGHTS | Z03_P04 | Z03_P04 | GENERAL | 0.3115 | 350.94 | 109.33 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 387.91 |
| Z03_P04_IG4 LIGHTS | Z03_P04 | Z03_P04 | GENERAL | 0.2498 | 350.94 | 87.67 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.05 |
| Z03_P04_IG5 LIGHTS | Z03_P04 | Z03_P04 | GENERAL | 0.2500 | 350.94 | 87.73 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.28 |
| Z04_P05_IG2 LIGHTS | Z04_P05 | Z04_P05 | GENERAL | 4.0985 | 350.94 | 1438.34 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 5103.23 |
| Z04_P05_IG3 LIGHTS | Z04_P05 | Z04_P05 | GENERAL | 0.3115 | 350.94 | 109.33 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 387.91 |
| Z04_P05_IG4 LIGHTS | Z04_P05 | Z04_P05 | GENERAL | 0.2498 | 350.94 | 87.67 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.05 |
| Z04_P05_IG5 LIGHTS | Z04_P05 | Z04_P05 | GENERAL | 0.2500 | 350.94 | 87.73 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.28 |
| Z05_P06_IG2 LIGHTS | Z05_P06 | Z05_P06 | GENERAL | 4.0985 | 350.94 | 1438.34 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 5103.23 |
| Z05_P06_IG3 LIGHTS | Z05_P06 | Z05_P06 | GENERAL | 0.3115 | 350.94 | 109.33 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 387.91 |
| Z05_P06_IG4 LIGHTS | Z05_P06 | Z05_P06 | GENERAL | 0.2498 | 350.94 | 87.67 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.05 |
| Z05_P06_IG5 LIGHTS | Z05_P06 | Z05_P06 | GENERAL | 0.2500 | 350.94 | 87.73 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 311.28 |
| Z06_ESCALERAS_IG2 LIGHTS | Z06_ESCALERAS | Z06_ESCALERAS | GENERAL | 0.2649 | 65.25 | 17.29 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 61.34 |
| Z06_ESCALERAS_IG3 LIGHTS | Z06_ESCALERAS | Z06_ESCALERAS | GENERAL | 1.2351 | 65.25 | 80.59 | 1 | SCHED4 | 68.04 | 68.04 | 68.04 | 0.0000 | Y | 285.94 |
| Interior Lighting Total | 1.2187 | 7149.37 | 8713.25 | 30914.64 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
| Exterior Lighting Total | 0.00 | 0.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| None |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| None |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP2 [W/W] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
| None |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| None |
| Coil Type | Rated Total Capacity [W] | Rated Sensible Capacity [W] | Rated Power[W] | Rated COP [W/W] | Rated Air Dry-bulb Temperature [C] | Rated Air Wet-bulb Temperature [C] | Rated Water Temperature [C] | Design Day used for Sizing | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF2 [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| None |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| None |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| None |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| None |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| Z01_P02 | 23260.17 | 23260.17 | 66.28 | 1.603 | 1.603 | SUMMER | 7/22 17:00:00 | 25.00 | 25.00 | 0.00801 | 35.20 | 0.00850 | 0.702 | 0.00 |
| Z02_P03 | 21811.13 | 21811.13 | 62.15 | 1.507 | 1.507 | SUMMER | 7/22 17:00:00 | 25.00 | 25.00 | 0.00803 | 35.20 | 0.00850 | 0.702 | 0.00 |
| Z03_P04 | 21755.21 | 21755.21 | 61.99 | 1.503 | 1.503 | SUMMER | 7/22 17:00:00 | 25.00 | 25.00 | 0.00803 | 35.20 | 0.00850 | 0.702 | 0.00 |
| Z04_P05 | 21773.39 | 21773.39 | 62.04 | 1.504 | 1.504 | SUMMER | 7/22 17:00:00 | 25.00 | 25.00 | 0.00803 | 35.20 | 0.00850 | 0.702 | 0.00 |
| Z05_P06 | 22167.43 | 22167.43 | 63.17 | 1.525 | 1.525 | SUMMER | 7/23 17:00:00 | 25.00 | 25.00 | 0.00803 | 35.00 | 0.00805 | 0.702 | 0.00 |
| Z06_ESCALERAS | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | N/A | N/A | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| Z01_P02 | 16961.65 | 16961.65 | 48.33 | 0.471 | 0.702 | WINTER | 12/27 07:00:00 | 20.00 | 19.98 | 0.01299 | -0.30 | 0.00316 | 0.702 | 0.00 |
| Z02_P03 | 9737.94 | 9737.94 | 27.75 | 0.274 | 0.702 | WINTER | 12/27 07:00:00 | 20.00 | 19.99 | 0.01250 | -0.30 | 0.00316 | 0.702 | 0.00 |
| Z03_P04 | 8865.48 | 8865.48 | 25.26 | 0.250 | 0.702 | WINTER | 12/23 07:00:00 | 20.00 | 19.99 | 0.01300 | -0.60 | 0.00312 | 0.702 | 0.00 |
| Z04_P05 | 9421.37 | 9421.37 | 26.85 | 0.265 | 0.702 | WINTER | 12/27 07:00:00 | 20.00 | 19.99 | 0.01241 | -0.30 | 0.00316 | 0.702 | 0.00 |
| Z05_P06 | 12595.90 | 12595.90 | 35.89 | 0.351 | 0.702 | WINTER | 12/27 07:00:00 | 20.00 | 19.97 | 0.00950 | -0.30 | 0.00316 | 0.702 | 0.00 |
| Z06_ESCALERAS | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | N/A | N/A | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| None |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| None |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| None |
Report: System Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| Z01_P02 | 2758.00 | 2351.25 | 1677.75 |
| Z02_P03 | 2736.25 | 2261.50 | 1551.75 |
| Z03_P04 | 2702.00 | 2243.00 | 1490.50 |
| Z04_P05 | 2739.25 | 2250.25 | 1531.00 |
| Z05_P06 | 2843.75 | 2301.25 | 1674.00 |
| Z06_ESCALERAS | 3016.75 | 3127.00 | 2678.75 |
| Facility | 3511.25 | 3128.00 | 2685.75 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| Z01_P02 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| Z01_P02 | 34.36 | 34.36 | 1052.82 | 2.253 | 0.000 | 0.000 | 0.000 |
| Z02_P03 | 34.36 | 34.36 | 1052.82 | 2.253 | 0.000 | 0.000 | 0.000 |
| Z03_P04 | 34.36 | 34.36 | 1052.82 | 2.253 | 0.000 | 0.000 | 0.000 |
| Z04_P05 | 34.36 | 34.36 | 1052.82 | 2.253 | 0.000 | 0.000 | 0.000 |
| Z05_P06 | 34.36 | 34.36 | 1070.52 | 2.215 | 0.000 | 0.000 | 0.000 |
| Z06_ESCALERAS | 6.39 | 6.39 | 198.99 | 0.000 | 0.000 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| Z01_P02 | 34.36 | 34.36 | 1052.82 | 2.204 | 0.000 | 0.000 | 0.000 |
| Z02_P03 | 34.36 | 34.36 | 1052.82 | 2.209 | 0.000 | 0.000 | 0.000 |
| Z03_P04 | 34.36 | 34.36 | 1052.82 | 2.210 | 0.000 | 0.000 | 0.000 |
| Z04_P05 | 34.36 | 34.36 | 1052.82 | 2.210 | 0.000 | 0.000 | 0.000 |
| Z05_P06 | 34.36 | 34.36 | 1070.52 | 2.172 | 0.000 | 0.000 | 0.000 |
| Z06_ESCALERAS | 6.39 | 6.39 | 198.99 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| Z01_P02 | 34.36 | 34.36 | 1052.82 | 350.94 | 0.000 | ||
| Z02_P03 | 34.36 | 34.36 | 1052.82 | 350.94 | 0.000 | ||
| Z03_P04 | 34.36 | 34.36 | 1052.82 | 350.94 | 0.000 | ||
| Z04_P05 | 34.36 | 34.36 | 1052.82 | 350.94 | 0.000 | ||
| Z05_P06 | 34.36 | 34.36 | 1070.52 | 350.94 | 0.000 | ||
| Z06_ESCALERAS | 6.39 | 6.39 | 198.99 | 65.25 | 0.000 | ||
| Total Facility | 178.17 | 178.17 | 5480.79 | 1819.97 | 0.0000 | 0.000 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| Z01_P02 | 8965049.50 | 0.00 | 8965049.50 | 0.00 | 8965049.50 | 8965049.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Z02_P03 | 8965049.50 | 0.00 | 8965049.50 | 0.00 | 8965049.50 | 8965049.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Z03_P04 | 8965049.50 | 0.00 | 8965049.50 | 0.00 | 8965049.50 | 8965049.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Z04_P05 | 8965049.50 | 0.00 | 8965049.50 | 0.00 | 8965049.50 | 8965049.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Z05_P06 | 8965049.50 | 0.00 | 8965049.50 | 0.00 | 8965049.50 | 8965049.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 44825247.50 | 0.00 | 44825247.50 | 0.00 | 44825247.50 | 44825247.50 | 0.00 | 3548.00 | 0.00 | 0.00 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| Z01_P02 | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.7019 | 0.00 | 3548.00 | 0.00 |
| Z02_P03 | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.7019 | 0.00 | 3548.00 | 0.00 |
| Z03_P04 | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.7019 | 0.00 | 3548.00 | 0.00 |
| Z04_P05 | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.7019 | 0.00 | 3548.00 | 0.00 |
| Z05_P06 | 0.7019 | 0.0000 | 0.7019 | 0.0000 | 0.7019 | 0.7019 | 0.00 | 3548.00 | 0.00 |
| Z06_ESCALERAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.00 | 0.00 | 0.00 |
| Total Facility | 3.5094 | 0.0000 | 3.5094 | 0.0000 | 3.5094 | 3.5094 | 0.00 | 3548.00 | 0.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| None |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| None |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| None |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| None |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Surfaces by Class| Total | Outdoors | |
| Wall | 120 | 100 |
| Floor | 11 | 2 |
| Roof | 12 | 3 |
| Internal Mass | 10 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 35 | 35 |
| Door | 0 | 0 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 0 |
| Conditioned Zones | 6 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 667 |
| Defaulted Fields | 517 |
| Fields with Defaults | 2200 |
| Autosized Fields | 12 |
| Autosizable Fields | 36 |
| Autocalculated Fields | 0 |
| Autocalculatable Fields | 342 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Annual and Peak Values - Electricity| Electricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 01-JAN-06:15 |
| Electricity:Building | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 01-JAN-06:15 |
| Electricity:Zone:Z01_P02 | 11716.63 | 0.00 | 01-JAN-00:15 | 3302.32 | 01-JAN-06:15 |
| Electricity:SpaceType:GENERAL | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 01-JAN-06:15 |
| InteriorLights:Electricity | 30914.64 | 0.00 | 01-JAN-00:15 | 8713.25 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z01_P02 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| InteriorLights:Electricity:SpaceType:GENERAL | 30914.64 | 0.00 | 01-JAN-00:15 | 8713.25 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity | 30914.64 | 0.00 | 01-JAN-00:15 | 8713.25 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z01_P02 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:SpaceType:GENERAL | 30914.64 | 0.00 | 01-JAN-00:15 | 8713.25 | 01-JAN-06:15 |
| Electricity:Zone:Z02_P03 | 11716.63 | 0.00 | 01-JAN-00:15 | 3302.32 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z02_P03 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z02_P03 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| Electricity:Zone:Z03_P04 | 11716.63 | 0.00 | 01-JAN-00:15 | 3302.32 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z03_P04 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z03_P04 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| Electricity:Zone:Z04_P05 | 11716.63 | 0.00 | 01-JAN-00:15 | 3302.32 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z04_P05 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z04_P05 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| Electricity:Zone:Z05_P06 | 11716.63 | 0.00 | 01-JAN-00:15 | 3302.32 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z05_P06 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z05_P06 | 6113.47 | 0.00 | 01-JAN-00:15 | 1723.07 | 01-JAN-06:15 |
| Electricity:Zone:Z06_ESCALERAS | 1389.11 | 0.00 | 01-JAN-00:15 | 391.52 | 01-JAN-06:15 |
| InteriorLights:Electricity:Zone:Z06_ESCALERAS | 347.28 | 0.00 | 01-JAN-00:15 | 97.88 | 01-JAN-06:15 |
| 1:InteriorLights:Electricity:Zone:Z06_ESCALERAS | 347.28 | 0.00 | 01-JAN-00:15 | 97.88 | 01-JAN-06:15 |
| InteriorEquipment:Electricity | 29057.63 | 0.00 | 01-JAN-00:15 | 8189.86 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z01_P02 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 29057.63 | 0.00 | 01-JAN-00:15 | 8189.86 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity | 29057.63 | 0.00 | 01-JAN-00:15 | 8189.86 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z01_P02 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:SpaceType:GENERAL | 29057.63 | 0.00 | 01-JAN-00:15 | 8189.86 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z02_P03 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z02_P03 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z03_P04 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z03_P04 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z04_P05 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z04_P05 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z05_P06 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z05_P06 | 5603.16 | 0.00 | 01-JAN-00:15 | 1579.24 | 01-JAN-06:15 |
| InteriorEquipment:Electricity:Zone:Z06_ESCALERAS | 1041.83 | 0.00 | 01-JAN-00:15 | 293.64 | 01-JAN-06:15 |
| General:InteriorEquipment:Electricity:Zone:Z06_ESCALERAS | 1041.83 | 0.00 | 01-JAN-00:15 | 293.64 | 01-JAN-06:15 |
| Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z01_P02 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z01_P02 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z02_P03 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z02_P03 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z03_P04 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z03_P04 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z04_P05 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z04_P05 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z05_P06 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z05_P06 | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Fans:Electricity:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Ventilation (simple):Fans:Electricity:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| ElectricityPurchased:Facility | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| ElectricityPurchased:Plant | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| Cogeneration:ElectricityPurchased | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| General:Cogeneration:ElectricityPurchased | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| ElectricityNet:Facility | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| ElectricityNet:Plant | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| Cogeneration:ElectricityNet | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| General:Cogeneration:ElectricityNet | 59972.28 | 0.00 | 01-JAN-00:15 | 16903.11 | 04-JAN-06:15 |
| Natural Gas Annual Value [kWh] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Cooling Annual Value [kWh] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| DistrictCooling:Facility | 70879.40 | 0.00 | 01-JAN-00:15 | 224790.54 | 23-JUL-15:15 |
| DistrictCooling:HVAC | 70879.40 | 0.00 | 01-JAN-00:15 | 224790.54 | 23-JUL-15:15 |
| Cooling:DistrictCooling | 70879.40 | 0.00 | 01-JAN-00:15 | 224790.54 | 23-JUL-15:15 |
| General:Cooling:DistrictCooling | 70879.40 | 0.00 | 01-JAN-00:15 | 224790.54 | 23-JUL-15:15 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| Water:Plant | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| WaterSystems:Water | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| General:WaterSystems:Water | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| MainsWater:Facility | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| MainsWater:Plant | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| WaterSystems:MainsWater | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| General:WaterSystems:MainsWater | 109.56 | 0.00 | 05-JAN-06:15 | 0.00 | 04-JAN-06:15 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [kWh] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 123333.68 | 0.00 | 01-JAN-00:15 | 165144.23 | 15-JAN-06:15 |
| EnergyTransfer:Building | 123333.68 | 0.00 | 01-JAN-00:15 | 165144.23 | 15-JAN-06:15 |
| EnergyTransfer:Zone:Z01_P02 | 24687.37 | 0.00 | 01-JAN-00:15 | 41374.12 | 15-JAN-06:15 |
| Heating:EnergyTransfer | 17848.99 | 0.00 | 01-JAN-00:15 | 150951.18 | 15-JAN-06:15 |
| Heating:EnergyTransfer:Zone:Z01_P02 | 5402.24 | 0.00 | 01-JAN-00:15 | 38581.66 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer | 17848.99 | 0.00 | 01-JAN-00:15 | 150951.18 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer:Zone:Z01_P02 | 5402.24 | 0.00 | 01-JAN-00:15 | 38581.66 | 15-JAN-06:15 |
| Cooling:EnergyTransfer | 105484.69 | 0.00 | 01-JAN-00:15 | 156418.78 | 23-JUL-15:15 |
| Cooling:EnergyTransfer:Zone:Z01_P02 | 19285.13 | 0.00 | 01-JAN-00:15 | 31418.59 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer | 105484.69 | 0.00 | 01-JAN-00:15 | 156418.78 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer:Zone:Z01_P02 | 19285.13 | 0.00 | 01-JAN-00:15 | 31418.59 | 23-JUL-15:15 |
| EnergyTransfer:Zone:Z02_P03 | 24488.79 | 0.00 | 01-JAN-00:15 | 32649.19 | 23-JUL-15:15 |
| Heating:EnergyTransfer:Zone:Z02_P03 | 2969.12 | 0.00 | 01-JAN-00:15 | 28537.46 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer:Zone:Z02_P03 | 2969.12 | 0.00 | 01-JAN-00:15 | 28537.46 | 15-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:Z02_P03 | 21519.67 | 0.00 | 01-JAN-00:15 | 31524.81 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer:Zone:Z02_P03 | 21519.67 | 0.00 | 01-JAN-00:15 | 31524.81 | 23-JUL-15:15 |
| EnergyTransfer:Zone:Z03_P04 | 24828.67 | 0.00 | 01-JAN-00:15 | 32377.42 | 23-JUL-15:15 |
| Heating:EnergyTransfer:Zone:Z03_P04 | 2528.43 | 0.00 | 01-JAN-00:15 | 26156.34 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer:Zone:Z03_P04 | 2528.43 | 0.00 | 01-JAN-00:15 | 26156.34 | 15-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:Z03_P04 | 22300.24 | 0.00 | 01-JAN-00:15 | 31252.60 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer:Zone:Z03_P04 | 22300.24 | 0.00 | 01-JAN-00:15 | 31252.60 | 23-JUL-15:15 |
| EnergyTransfer:Zone:Z04_P05 | 24704.91 | 0.00 | 01-JAN-00:15 | 32186.40 | 23-JUL-15:15 |
| Heating:EnergyTransfer:Zone:Z04_P05 | 2792.05 | 0.00 | 01-JAN-00:15 | 26996.77 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer:Zone:Z04_P05 | 2792.05 | 0.00 | 01-JAN-00:15 | 26996.77 | 15-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:Z04_P05 | 21912.86 | 0.00 | 01-JAN-00:15 | 31061.26 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer:Zone:Z04_P05 | 21912.86 | 0.00 | 01-JAN-00:15 | 31061.26 | 23-JUL-15:15 |
| EnergyTransfer:Zone:Z05_P06 | 24623.94 | 0.00 | 01-JAN-00:15 | 33900.76 | 15-JAN-06:15 |
| Heating:EnergyTransfer:Zone:Z05_P06 | 4157.15 | 0.00 | 01-JAN-00:15 | 30678.95 | 15-JAN-06:15 |
| General:Heating:EnergyTransfer:Zone:Z05_P06 | 4157.15 | 0.00 | 01-JAN-00:15 | 30678.95 | 15-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:Z05_P06 | 20466.79 | 0.00 | 01-JAN-00:15 | 31161.52 | 23-JUL-15:15 |
| General:Cooling:EnergyTransfer:Zone:Z05_P06 | 20466.79 | 0.00 | 01-JAN-00:15 | 31161.52 | 23-JUL-15:15 |
| EnergyTransfer:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Heating:EnergyTransfer:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| General:Heating:EnergyTransfer:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| Cooling:EnergyTransfer:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| General:Cooling:EnergyTransfer:Zone:Z06_ESCALERAS | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
| DistrictHeating:Facility | 97593.75 | 580.85 | 02-JUL-13:15 | 239995.01 | 15-JAN-06:15 |
| DistrictHeating:Plant | 5974.85 | 580.85 | 02-JUL-13:15 | 755.11 | 01-JAN-06:15 |
| WaterSystems:DistrictHeating | 5974.85 | 580.85 | 02-JUL-13:15 | 755.11 | 01-JAN-06:15 |
| General:WaterSystems:DistrictHeating | 5974.85 | 580.85 | 02-JUL-13:15 | 755.11 | 01-JAN-06:15 |
| DistrictHeating:HVAC | 91618.91 | 0.00 | 01-JAN-00:15 | 239239.90 | 15-JAN-06:15 |
| Heating:DistrictHeating | 91618.91 | 0.00 | 01-JAN-00:15 | 239239.90 | 15-JAN-06:15 |
| General:Heating:DistrictHeating | 91618.91 | 0.00 | 01-JAN-00:15 | 239239.90 | 15-JAN-06:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [kWh] | HVAC Zone Eq & Other Sensible Air Cooling [kWh] | HVAC Terminal Unit Sensible Air Heating [kWh] | HVAC Terminal Unit Sensible Air Cooling [kWh] | HVAC Input Heated Surface Heating [kWh] | HVAC Input Cooled Surface Cooling [kWh] | People Sensible Heat Addition [kWh] | Lights Sensible Heat Addition [kWh] | Equipment Sensible Heat Addition [kWh] | Window Heat Addition [kWh] | Interzone Air Transfer Heat Addition [kWh] | Infiltration Heat Addition [kWh] | Opaque Surface Conduction and Other Heat Addition [kWh] | Equipment Sensible Heat Removal [kWh] | Window Heat Removal [kWh] | Interzone Air Transfer Heat Removal [kWh] | Infiltration Heat Removal [kWh] | Opaque Surface Conduction and Other Heat Removal [kWh] | |
| Z01_P02 | 5402.256 | -19285.17 | 0.000 | 0.000 | 0.000 | 0.000 | 7472.458 | 6113.473 | 5603.160 | 38294.876 | 0.000 | 3.000 | 1.125 | 0.000 | -12882.76 | 0.000 | -431.26 | -30290.03 |
| Z02_P03 | 2969.131 | -21519.76 | 0.000 | 0.000 | 0.000 | 0.000 | 7472.458 | 6113.473 | 5603.160 | 37428.580 | 0.000 | 5.276 | 1.122 | 0.000 | -12948.94 | 0.000 | -527.98 | -24595.40 |
| Z03_P04 | 2528.438 | -22300.34 | 0.000 | 0.000 | 0.000 | 0.000 | 7472.458 | 6113.473 | 5603.160 | 37302.436 | 0.000 | 5.606 | 2.623 | 0.000 | -13132.63 | 0.000 | -559.59 | -23033.01 |
| Z04_P05 | 2792.057 | -21912.96 | 0.000 | 0.000 | 0.000 | 0.000 | 7472.458 | 6113.473 | 5603.160 | 37345.004 | 0.000 | 5.825 | 1.688 | 0.000 | -13041.96 | 0.000 | -565.62 | -23811.45 |
| Z05_P06 | 4157.279 | -20466.99 | 0.000 | 0.000 | 0.000 | 0.000 | 7472.458 | 6113.473 | 5603.160 | 38227.303 | 0.000 | 31.205 | 0.579 | 0.000 | -12597.30 | 0.000 | -2730.68 | -25809.91 |
| Z06_ESCALERAS | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1389.403 | 347.277 | 1041.830 | 461.046 | 0.000 | 165.911 | 0.020 | 0.000 | -346.46 | 0.000 | -2202.26 | -856.74 |
| Total Facility | 17849.161 | -105485.22 | 0.000 | 0.000 | 0.000 | 0.000 | 38751.692 | 30914.644 | 29057.632 | 189059.243 | 0.000 | 216.822 | 7.157 | 0.000 | -64950.05 | 0.000 | -7017.39 | -128396.54 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| Z01_P02 | 23-JUL-15:15 | 0.00 | -204778.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 12073.98 | 0.00 | 0.00 | 187296.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Z02_P03 | 23-JUL-15:15 | 0.00 | -206857.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 11588.61 | 0.00 | 0.00 | 189860.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Z03_P04 | 23-JUL-15:15 | 0.00 | -205209.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 11599.58 | 0.00 | 0.00 | 188201.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Z04_P05 | 23-JUL-15:15 | 0.00 | -204074.41 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 11605.80 | 0.00 | 0.00 | 187060.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Z05_P06 | 23-JUL-15:15 | 0.00 | -207496.53 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 11784.64 | 0.00 | 0.00 | 190303.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Z06_ESCALERAS | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 23-JUL-15:15 | 0.00 | -1028416.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10922.11 | 8713.25 | 8189.86 | 58940.39 | 0.00 | 743.94 | 940907.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| Z01_P02 | 15-JAN-06:15 | 310974.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3336.13 | 0.00 | 0.00 | -313046.71 |
| Z02_P03 | 15-JAN-06:15 | 236629.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3680.73 | 0.00 | 0.00 | -238357.07 |
| Z03_P04 | 15-JAN-06:15 | 218899.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3818.23 | 0.00 | 0.00 | -220489.71 |
| Z04_P05 | 15-JAN-06:15 | 225246.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3776.74 | 0.00 | 0.00 | -226878.13 |
| Z05_P06 | 15-JAN-06:15 | 257961.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2106.10 | 1723.07 | 1579.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3665.06 | 0.00 | 0.00 | -259705.24 |
| Z06_ESCALERAS | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 15-JAN-06:15 | 1249711.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10922.11 | 8713.25 | 8189.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18372.81 | 0.00 | -1455.25 | -1257708.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| None |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| None |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| None |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| None |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| None |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| None |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| None |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** D3_peninsula - ESP CTE_DB_HE WMO#= |
| Total gross floor area [m2] | 1819.97 |
| Principal Heating Source | District Heat |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| Z01_P02 | 350.94 | 350.94 | 0.00 | 68.04 |
| Z02_P03 | 350.94 | 350.94 | 0.00 | 68.04 |
| Z03_P04 | 350.94 | 350.94 | 0.00 | 68.04 |
| Z04_P05 | 350.94 | 350.94 | 0.00 | 68.04 |
| Z05_P06 | 350.94 | 350.94 | 0.00 | 68.04 |
| Z06_ESCALERAS | 65.25 | 65.25 | 0.00 | 68.04 |
| Totals | 1819.97 | 1819.97 | 0.00 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 0.00 |
| Number of hours not met | 0.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [kWh] | Natural Gas Demand [W] | Gasoline Use [kWh] | Gasoline Demand [W] | Diesel Use [kWh] | Diesel Demand [W] | Coal Use [kWh] | Coal Demand [W] | Fuel Oil No 1 Use [kWh] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [kWh] | Fuel Oil No 2 Demand [W] | Propane Use [kWh] | Propane Demand [W] | Other Fuel 1 Use [kWh] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [kWh] | Other Fuel 2 Demand [W] | District Cooling Use [kWh] | District Cooling Demand [W] | District Heating Use [kWh] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91618.91 | 239239.90 |
| Cooling -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70879.40 | 224790.54 | 0.00 | 0.00 |
| Interior Lighting -- 1 | 30914.64 | 8713.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- General | 29057.63 | 8189.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5974.85 | 755.11 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [kWh] | Total Energy Use [kWh] | |
| Electricity | 29057.63 | 59972.28 |
| Natural Gas | 0.00 | 0.00 |
| Additional | 0.00 | 168473.15 |
| Total | 29057.63 | 228445.43 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [kWh] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [kWh/m2] | |
| Interior Lighting (All) | 16.99 |
| Space Heating | 0.00 |
| Space Cooling | 0.00 |
| Fans (All) | 0.00 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 15.97 |
| Miscellaneous (All) | 32.95 |
| Subtotal | 32.95 |
| Natural Gas [kWh/m2] | |
| Space Heating | 0.00 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 0.00 |
| Subtotal | 0.00 |
| Additional [kWh/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 13.53 |
| Space Heating | 40.11 |
| Space Cooling | 31.03 |
| Fans (All) | 0.00 |
| Service Water Heating | 2.62 |
| Receptacle Equipment | 12.72 |
| Miscellaneous | -0.00 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| SCHED2_FLOW_RATE_FRACTION | 8760. | 8760. |
| SCHED4 | 3548. | 3548. |
| SCHED5 | 5212. | 5212. |
| WORK EFF SCH | 0. | 0. |
| CLOTHING SCH | 8760. | 8760. |
| AIR VELO SCH | 1200. | 8760. |
| SUMMERNIGHTVENTILATION SCH | 976. | 976. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| SCHED0_CTE | THERMOSTAT_Z01_P02 SETPOINT | January | 20.00 | 365 | -50.00 | 365 |
| SCHED1_CTE | THERMOSTAT_Z01_P02 SETPOINT | July | 25.00 | 365 | 100.00 | 365 |
| THERMOSTAT_Z06_ESCALERAS HEATING SETPOINT TEMPERATURE | THERMOSTAT_Z06_ESCALERAS SETPOINT | January | -50.00 | 365 | -50.00 | 365 |
| THERMOSTAT_Z06_ESCALERAS COOLING SETPOINT TEMPERATURE | THERMOSTAT_Z06_ESCALERAS SETPOINT | July | 100.00 | 365 | 100.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2026-07-17 12:05:41
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |