Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 12:05

Tabular Output Report in Format: HTML

Building: Edificio terciario - Guía de aplicación DB HE 2019. EJEMPLOS (V)

Environment: RUNPERIOD 1 ** D3_peninsula - ESP CTE_DB_HE WMO#=

Simulation Timestamp: 2026-07-17 12:05:41


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kWh] Energy Per Total Building Area [kWh/m2] Energy Per Conditioned Building Area [kWh/m2]
Total Site Energy 228445.25 125.52 125.52
Net Site Energy 228445.25 125.52 125.52
Total Source Energy 617395.48 339.23 339.23
Net Source Energy 617395.48 339.23 339.23


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 1819.97
Net Conditioned Building Area 1819.97
Unconditioned Building Area 0.00


End Uses

Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91618.83 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70879.34 0.00 0.00
Interior Lighting 30914.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 29057.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5974.84 109.56
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 59972.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70879.34 97593.67 109.56
Note: District heat appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91618.83 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70879.34 0.00 0.00
Interior Lighting 1 30914.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 29057.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5974.84 109.56
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kWh] Natural Gas [kWh] Gasoline [kWh] Diesel [kWh] Coal [kWh] Fuel Oil No 1 [kWh] Fuel Oil No 2 [kWh] Propane [kWh] Other Fuel 1 [kWh] Other Fuel 2 [kWh] District Cooling [kWh] District Heating [kWh] Water [m3]
Heating Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91618.83 0.00
Cooling Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70879.34 0.00 0.00
Interior Lighting GENERAL 30914.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 29057.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5974.84 109.56
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Gasoline Intensity [kWh/m2] Diesel Intensity [kWh/m2] Coal Intensity [kWh/m2] Fuel Oil No 1 Intensity [kWh/m2] Fuel Oil No 2 Intensity [kWh/m2] Propane Intensity [kWh/m2] Other Fuel 1 Intensity [kWh/m2] Other Fuel 2 Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 16.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.95 53.62 0.06
Other 15.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 32.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.95 53.62 0.06


Utility Use Per Total Floor Area

Electricity Intensity [kWh/m2] Natural Gas Intensity [kWh/m2] Gasoline Intensity [kWh/m2] Diesel Intensity [kWh/m2] Coal Intensity [kWh/m2] Fuel Oil No 1 Intensity [kWh/m2] Fuel Oil No 2 Intensity [kWh/m2] Propane Intensity [kWh/m2] Other Fuel 1 Intensity [kWh/m2] Other Fuel 2 Intensity [kWh/m2] District Cooling Intensity [kWh/m2] District Heating Intensity [kWh/m2] Water Intensity [m3/m2]
Lighting 16.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.95 53.62 0.06
Other 15.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 32.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.95 53.62 0.06


Electric Loads Satisfied

Electricity [kWh] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 59972.228 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 59972.228 100.00
     
Total On-Site and Utility Electric Sources 59972.228 100.00
Total Electricity End Uses 59972.228 100.00


On-Site Thermal Sources

Heat [kWh] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 109.56 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 109.56 100.00
Total Water End Uses 109.56 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 1.00
Tolerance for Zone Cooling Setpoint Not Met Time 1.00


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2685.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2026.07.17 12:05
RunPeriod RUNPERIOD 1
Weather File D3_peninsula - ESP CTE_DB_HE WMO#=
Latitude [deg] 40.68
Longitude [deg] -4.1
Elevation [m] 667.00
Time Zone 1.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1705.82 348.87 352.36 653.11 351.48
Above Ground Wall Area [m2] 1705.82 348.87 352.36 653.11 351.48
Window Opening Area [m2] 564.58 39.21 173.74 177.89 173.74
Gross Window-Wall Ratio [%] 33.10 11.24 49.31 27.24 49.43
Above Ground Window-Wall Ratio [%] 33.10 11.24 49.31 27.24 49.43


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1705.82 348.87 352.36 653.11 351.48
Above Ground Wall Area [m2] 1705.82 348.87 352.36 653.11 351.48
Window Opening Area [m2] 564.58 39.21 173.74 177.89 173.74
Gross Window-Wall Ratio [%] 33.10 11.24 49.31 27.24 49.43
Above Ground Window-Wall Ratio [%] 33.10 11.24 49.31 27.24 49.43


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 362.81
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
Z01_P02 350.94 Yes Yes 1052.82 1.00 302.51 0.00 95.20 116.92 4.9098 10.21 4.5000
Z02_P03 350.94 Yes Yes 1052.82 1.00 287.51 0.00 89.76 110.16 4.9098 10.21 4.5000
Z03_P04 350.94 Yes Yes 1052.82 1.00 287.55 0.00 89.76 110.16 4.9098 10.21 4.5000
Z04_P05 350.94 Yes Yes 1052.82 1.00 287.55 0.00 89.76 110.16 4.9098 10.21 4.5000
Z05_P06 350.94 Yes Yes 1070.52 1.00 291.34 0.00 91.23 111.91 4.9098 10.21 4.5000
Z06_ESCALERAS 65.25 Yes Yes 198.99 1.00 249.36 0.00 3.42 5.25 1.5000 10.21 4.5000
Total 1819.97     5480.79   1705.82 0.00 459.12 564.58 4.7876 10.21 4.5000
Conditioned Total 1819.97     5480.79   1705.82 0.00 459.12 564.58 4.7876 10.21 4.5000
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
Z01_P02 350.94 Yes Yes 1.00 Z01_P02 GENERAL Z01_P02 4.9098 10.21 4.5000  
Z02_P03 350.94 Yes Yes 1.00 Z02_P03 GENERAL Z02_P03 4.9098 10.21 4.5000  
Z03_P04 350.94 Yes Yes 1.00 Z03_P04 GENERAL Z03_P04 4.9098 10.21 4.5000  
Z04_P05 350.94 Yes Yes 1.00 Z04_P05 GENERAL Z04_P05 4.9098 10.21 4.5000  
Z05_P06 350.94 Yes Yes 1.00 Z05_P06 GENERAL Z05_P06 4.9098 10.21 4.5000  
Z06_ESCALERAS 65.25 Yes Yes 1.00 Z06_ESCALERAS GENERAL Z06_ESCALERAS 1.5000 10.21 4.5000  
Total 1819.97             4.7876 10.21 4.5000  
Conditioned Total 1819.97             4.7876 10.21 4.5000  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 1819.97 1819.97 0.00 0.00 4.7876 10.21 4.5000
Total 1819.97 1819.97 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 01-JAN-06:30 - - - - - - - - - 23-JUL-15:30 15-JAN-06:30 04-JAN-06:30
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239239.90 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224790.54 0.00 0.00
Interior Lighting 8713.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 8189.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 755.11 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 16903.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224790.54 239995.01 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239239.90 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 224790.54 0.00 0.00
Interior Lighting 1 8713.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 8189.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 755.11 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kWh] Source Natural Gas [kWh] Source Gasoline [kWh] Source Diesel [kWh] Source Coal [kWh] Source Fuel Oil No 1 [kWh] Source Fuel Oil No 2 [kWh] Source Propane [kWh] Source Other Fuel 1 [kWh] Source Other Fuel 2 [kWh] Source District Cooling [kWh] Source District Heating [kWh]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 331049.38
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74824.96 0.00
Interior Lighting 97906.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 92025.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21589.10
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 189932.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74824.96 352638.48


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kWh/m2] Source Natural Gas [kWh/m2] Source Gasoline [kWh/m2] Source Diesel [kWh/m2] Source Coal [kWh/m2] Source Fuel Oil No 1 [kWh/m2] Source Fuel Oil No 2 [kWh/m2] Source Propane [kWh/m2] Source Other Fuel 1 [kWh/m2] Source Other Fuel 2 [kWh/m2] Source District Cooling [kWh/m2] Source District Heating [kWh/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.90
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.11 0.00
Interior Lighting 53.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 50.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.86
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 104.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.11 193.76


Source Energy End Use Components Per Total Floor Area

Source Electricity [kWh/m2] Source Natural Gas [kWh/m2] Source Gasoline [kWh/m2] Source Diesel [kWh/m2] Source Coal [kWh/m2] Source Fuel Oil No 1 [kWh/m2] Source Fuel Oil No 2 [kWh/m2] Source Propane [kWh/m2] Source Other Fuel 1 [kWh/m2] Source Other Fuel 2 [kWh/m2] Source District Cooling [kWh/m2] Source District Heating [kWh/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.90
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.11 0.00
Interior Lighting 53.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 50.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.86
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 104.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.11 193.76



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

ZoneHVAC:IdealLoadsAirSystem

User-Specified Maximum Heating Air Flow Rate [m3/s] User-Specified Maximum Cooling Air Flow Rate [m3/s]
Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM 0.000000 0.000000
Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM 0.000000 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
Z01_S02_E09 Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E06 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z01_S02_E10 Z01_S02_E09 | Z01_S04_E07 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E06 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z01_S02_E12 Z01_S02_E09 | Z01_S04_E07 | Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S02_E05 | Z06_S02_E08 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z01_S04_E07 Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S02_E05 | Z06_S02_E08 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z02_S02_E08 Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z02_S02_E09 Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E06 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z02_S02_E11 Z02_S02_E08 | Z02_S04_E07 | Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z02_S04_E07 Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S03_E05 | Z06_S03_E08 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z03_S02_E08 Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z03_S02_E09 Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E06 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z03_S02_E11 Z03_S02_E08 | Z03_S04_E07 | Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z03_S04_E07 Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S04_E05 | Z06_S04_E08 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z04_S02_E08 Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z04_S02_E09 Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E06 | Z06_S06_E05 | Z06_S06_E06 |
Z04_S02_E11 Z04_S02_E08 | Z04_S04_E07 | Z05_S02_E08 | Z05_S04_E07 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z04_S04_E07 Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S05_E05 | Z06_S05_E08 | Z06_S06_E05 | Z06_S06_E08 |
Z05_S02_E08 Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E06 |
Z05_S02_E09 Z05_S02_E08 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E06 |
Z05_S02_E11 Z05_S02_E08 | Z05_S04_E07 | Z06_S06_E05 | Z06_S06_E08 |
Z05_S04_E07 Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z06_S06_E05 | Z06_S06_E08 |
Z05_S01_E02 Z06_S06_E05 | Z06_S06_E06 | Z06_S06_E08 |
Z06_S01_E04 Z01_S02_E09 | Z01_S01_E01 | Z02_S02_E08 | Z03_S02_E08 | Z04_S02_E08 | Z05_S02_E08 |
Z06_S01_E05 Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z01_S01_E01 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S01_E06 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S01_E06 Z01_S02_E09 | Z01_S02_E10 | Z01_S01_E01 | Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S01_E05 | Z06_S01_E07 | Z06_S02_E05 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 |
Z06_S01_E07 Z01_S02_E10 | Z01_S02_E12 | Z01_S01_E01 | Z02_S02_E09 | Z02_S02_E11 | Z03_S02_E09 | Z03_S02_E11 | Z04_S02_E09 | Z04_S02_E11 | Z05_S02_E09 | Z05_S02_E11 | Z06_S01_E06 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S01_E08 Z01_S02_E12 | Z01_S04_E07 | Z01_S01_E01 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 |
Z06_S02_E05 Z01_S02_E09 | Z01_S02_E10 | Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S02_E06 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S02_E06 Z01_S02_E09 | Z01_S02_E10 | Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S02_E05 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 |
Z06_S02_E08 Z01_S02_E12 | Z01_S04_E07 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 |
Z06_S03_E05 Z02_S02_E08 | Z02_S02_E09 | Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S03_E06 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S03_E06 Z02_S02_E08 | Z02_S02_E09 | Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S03_E05 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 |
Z06_S03_E08 Z02_S02_E11 | Z02_S04_E07 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 |
Z06_S04_E05 Z03_S02_E08 | Z03_S02_E09 | Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S04_E06 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S04_E06 Z03_S02_E08 | Z03_S02_E09 | Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S04_E05 | Z06_S05_E05 | Z06_S06_E05 |
Z06_S04_E08 Z03_S02_E11 | Z03_S04_E07 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 |
Z06_S05_E05 Z04_S02_E08 | Z04_S02_E09 | Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S05_E06 | Z06_S06_E06 |
Z06_S05_E06 Z04_S02_E08 | Z04_S02_E09 | Z05_S02_E08 | Z05_S02_E09 | Z06_S05_E05 | Z06_S06_E05 |
Z06_S05_E08 Z04_S02_E11 | Z04_S04_E07 | Z05_S02_E11 | Z05_S04_E07 |
Z06_S06_E05 Z05_S02_E08 | Z05_S02_E09 | Z05_S02_E11 | Z05_S04_E07 | Z06_S06_E06 |
Z06_S06_E06 Z05_S02_E08 | Z05_S02_E09 | Z06_S06_E05 |
Z06_S06_E08 Z05_S02_E11 | Z05_S04_E07 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
Z01_S01_E03 Z01_S01_E03_G1 |
Z01_S01_E04 Z01_S01_E04_G1 |
Z01_S01_E05 Z01_S01_E05_G1 |
Z01_S02_E04 Z01_S02_E04_G1 | Z01_S02_E04_G2 |
Z01_S04_E03 Z01_S04_E03_G1 |
Z02_S01_E03 Z02_S01_E03_G1 |
Z02_S01_E04 Z02_S01_E04_G1 |
Z02_S01_E05 Z02_S01_E05_G1 |
Z02_S02_E03 Z02_S02_E03_G1 | Z02_S03_E05_G1 |
Z02_S04_E03 Z02_S04_E03_G1 |
Z03_S01_E03 Z03_S01_E03_G1 |
Z03_S01_E04 Z03_S01_E04_G1 |
Z03_S01_E05 Z03_S01_E05_G1 |
Z03_S02_E03 Z03_S02_E03_G1 | Z03_S03_E04_G1 |
Z03_S04_E03 Z03_S04_E03_G1 |
Z04_S01_E03 Z04_S01_E03_G1 |
Z04_S01_E04 Z04_S01_E04_G1 |
Z04_S01_E05 Z04_S01_E05_G1 |
Z04_S02_E03 Z04_S02_E03_G1 | Z04_S03_E04_G1 |
Z04_S04_E03 Z04_S04_E03_G1 |
Z05_S01_E04 Z05_S01_E04_G1 |
Z05_S01_E05 Z05_S01_E05_G1 |
Z05_S01_E06 Z05_S01_E06_G1 |
Z05_S02_E03 Z05_S02_E03_G1 | Z05_S03_E04_G1 |
Z05_S04_E03 Z05_S04_E03_G1 |
Z06_S02_E03 Z06_S02_E03_G1 |
Z06_S03_E03 Z06_S03_E03_G1 |
Z06_S04_E03 Z06_S04_E03_G1 |
Z06_S05_E03 Z06_S05_E03_G1 |
Z06_S06_E03 Z06_S06_E03_G1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 4 15


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 4 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 1.000 1.000


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.60 13.60 13.60 13.60 13.60 13.60 13.60 13.60 13.60 13.60 13.60 13.60


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.63 13.63 13.63 13.63 13.63 13.63 13.63 13.63 13.63 13.63 13.63 13.63


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 D3_peninsula - ESP CTE_DB_HE WMO#= 40.68 -4.13 1.00 667.00 93565 1.1121


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Schedule SCHED6_WATER_MAINS_TEMP 0.00 0.00 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Edificio terciario - Guía de aplicación DB HE 2019. EJEMPLOS (V) 0.000 Country 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.140 270.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 188 35


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 Z01_P02 0.0 0.00 0.00 0.00 5.43 2.00 -7.14E-002 1 1 1 -10.00 185.26 -10.00 10.00 -24.25 3.00 3.00 1052.82 TARP DOE-2 350.94 302.51 185.59 95.20 18 6 0 Yes
2 Z02_P03 0.0 0.00 0.00 0.00 3.21 2.95 3.42 1 1 1 -10.00 137.83 -10.00 10.00 -24.25 6.50 3.00 1052.82 TARP DOE-2 350.94 287.51 177.35 89.76 18 6 0 Yes
3 Z03_P04 0.0 0.00 0.00 0.00 3.22 2.95 6.75 1 1 1 -10.00 137.94 -10.00 10.00 -24.25 10.00 3.00 1052.82 TARP DOE-2 350.94 287.55 177.38 89.76 18 6 0 Yes
4 Z04_P05 0.0 0.00 0.00 0.00 3.22 2.95 10.07 1 1 1 -10.00 137.94 -10.00 10.00 -24.25 13.50 3.00 1052.82 TARP DOE-2 350.94 287.55 177.38 89.76 18 6 0 Yes
5 Z05_P06 0.0 0.00 0.00 0.00 1.77 2.90 13.65 1 1 1 -10.00 68.97 -10.00 10.00 -25.25 17.75 3.05 1070.52 TARP DOE-2 350.94 291.34 179.43 91.23 20 6 0 Yes
6 Z06_ESCALERAS 0.0 0.00 0.00 0.00 1.16 7.75 5.00 1 1 1 -2.81 56.07 0.00 10.00 -24.25 17.30 3.05 198.99 TARP DOE-2 65.25 249.36 244.11 3.42 51 5 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 Z01_P02 350.94 34.4 10.215 9.790E-002 4.910 0.000 0.000 4.500 0.000 0.000 9.410 No
2 Z02_P03 350.94 34.4 10.215 9.790E-002 4.910 0.000 0.000 4.500 0.000 0.000 9.410 No
3 Z03_P04 350.94 34.4 10.215 9.790E-002 4.910 0.000 0.000 4.500 0.000 0.000 9.410 No
4 Z04_P05 350.94 34.4 10.215 9.790E-002 4.910 0.000 0.000 4.500 0.000 0.000 9.410 No
5 Z05_P06 350.94 34.4 10.215 9.790E-002 4.910 0.000 0.000 4.500 0.000 0.000 9.410 No
6 Z06_ESCALERAS 65.25 6.4 10.214 9.790E-002 1.500 0.000 0.000 4.500 0.000 0.000 6.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 Z01_P02_IG1 PEOPLE SCHED4 Z01_P02 350.94 34.4 34.4 9.790E-002 10.215 0.600 0.400 0.613 Z01_P02_IG1 ACTIVITYLEVEL No 0.0000 0 34
2 Z02_P03_IG1 PEOPLE SCHED4 Z02_P03 350.94 34.4 34.4 9.790E-002 10.215 0.600 0.400 0.613 Z02_P03_IG1 ACTIVITYLEVEL No 0.0000 0 34
3 Z03_P04_IG1 PEOPLE SCHED4 Z03_P04 350.94 34.4 34.4 9.790E-002 10.215 0.600 0.400 0.613 Z03_P04_IG1 ACTIVITYLEVEL No 0.0000 0 34
4 Z04_P05_IG1 PEOPLE SCHED4 Z04_P05 350.94 34.4 34.4 9.790E-002 10.215 0.600 0.400 0.613 Z04_P05_IG1 ACTIVITYLEVEL No 0.0000 0 34
5 Z05_P06_IG1 PEOPLE SCHED4 Z05_P06 350.94 34.4 34.4 9.790E-002 10.215 0.600 0.400 0.613 Z05_P06_IG1 ACTIVITYLEVEL No 0.0000 0 34
6 Z06_ESCALERAS_IG1 PEOPLE SCHED4 Z06_ESCALERAS 65.25 6.4 6.4 9.790E-002 10.214 0.600 0.400 0.613 Z06_ESCALERAS_IG1 ACTIVITYLEVEL No 0.0000 0 6


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 Z01_P02_IG2 LIGHTS SCHED4 Z01_P02 350.94 34.4 1438.340 4.099 41.864 0.000 0.656 0.180 0.164 0.000 1 0.000 1438.340
2 Z01_P02_IG3 LIGHTS SCHED4 Z01_P02 350.94 34.4 156.461 0.446 4.554 0.000 0.656 0.180 0.164 0.000 1 0.000 156.461
3 Z01_P02_IG4 LIGHTS SCHED4 Z01_P02 350.94 34.4 40.540 0.116 1.180 0.000 0.656 0.180 0.164 0.000 1 0.000 40.540
4 Z01_P02_IG5 LIGHTS SCHED4 Z01_P02 350.94 34.4 87.734 0.250 2.554 0.000 0.656 0.180 0.164 0.000 1 0.000 87.734
5 Z02_P03_IG2 LIGHTS SCHED4 Z02_P03 350.94 34.4 1438.340 4.099 41.864 0.000 0.656 0.180 0.164 0.000 1 0.000 1438.340
6 Z02_P03_IG3 LIGHTS SCHED4 Z02_P03 350.94 34.4 109.331 0.312 3.182 0.000 0.656 0.180 0.164 0.000 1 0.000 109.331
7 Z02_P03_IG4 LIGHTS SCHED4 Z02_P03 350.94 34.4 87.670 0.250 2.552 0.000 0.656 0.180 0.164 0.000 1 0.000 87.670
8 Z02_P03_IG5 LIGHTS SCHED4 Z02_P03 350.94 34.4 87.734 0.250 2.554 0.000 0.656 0.180 0.164 0.000 1 0.000 87.734
9 Z03_P04_IG2 LIGHTS SCHED4 Z03_P04 350.94 34.4 1438.340 4.099 41.864 0.000 0.656 0.180 0.164 0.000 1 0.000 1438.340
10 Z03_P04_IG3 LIGHTS SCHED4 Z03_P04 350.94 34.4 109.331 0.312 3.182 0.000 0.656 0.180 0.164 0.000 1 0.000 109.331
11 Z03_P04_IG4 LIGHTS SCHED4 Z03_P04 350.94 34.4 87.670 0.250 2.552 0.000 0.656 0.180 0.164 0.000 1 0.000 87.670
12 Z03_P04_IG5 LIGHTS SCHED4 Z03_P04 350.94 34.4 87.734 0.250 2.554 0.000 0.656 0.180 0.164 0.000 1 0.000 87.734
13 Z04_P05_IG2 LIGHTS SCHED4 Z04_P05 350.94 34.4 1438.340 4.099 41.864 0.000 0.656 0.180 0.164 0.000 1 0.000 1438.340
14 Z04_P05_IG3 LIGHTS SCHED4 Z04_P05 350.94 34.4 109.331 0.312 3.182 0.000 0.656 0.180 0.164 0.000 1 0.000 109.331
15 Z04_P05_IG4 LIGHTS SCHED4 Z04_P05 350.94 34.4 87.670 0.250 2.552 0.000 0.656 0.180 0.164 0.000 1 0.000 87.670
16 Z04_P05_IG5 LIGHTS SCHED4 Z04_P05 350.94 34.4 87.734 0.250 2.554 0.000 0.656 0.180 0.164 0.000 1 0.000 87.734
17 Z05_P06_IG2 LIGHTS SCHED4 Z05_P06 350.94 34.4 1438.340 4.099 41.864 0.000 0.656 0.180 0.164 0.000 1 0.000 1438.340
18 Z05_P06_IG3 LIGHTS SCHED4 Z05_P06 350.94 34.4 109.331 0.312 3.182 0.000 0.656 0.180 0.164 0.000 1 0.000 109.331
19 Z05_P06_IG4 LIGHTS SCHED4 Z05_P06 350.94 34.4 87.670 0.250 2.552 0.000 0.656 0.180 0.164 0.000 1 0.000 87.670
20 Z05_P06_IG5 LIGHTS SCHED4 Z05_P06 350.94 34.4 87.734 0.250 2.554 0.000 0.656 0.180 0.164 0.000 1 0.000 87.734
21 Z06_ESCALERAS_IG2 LIGHTS SCHED4 Z06_ESCALERAS 65.25 6.4 17.288 0.265 2.706 0.000 0.656 0.180 0.164 0.000 1 0.000 17.288
22 Z06_ESCALERAS_IG3 LIGHTS SCHED4 Z06_ESCALERAS 65.25 6.4 80.592 1.235 12.616 0.000 0.656 0.180 0.164 0.000 1 0.000 80.592


OtherEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 Z01_P02_IG6 ELECEQ SCHED4 Z01_P02 350.94 34.4 1579.244 4.500 45.965 0.000 0.700 0.000 0.300 0.000 1579.244
2 Z02_P03_IG6 ELECEQ SCHED4 Z02_P03 350.94 34.4 1579.244 4.500 45.965 0.000 0.700 0.000 0.300 0.000 1579.244
3 Z03_P04_IG6 ELECEQ SCHED4 Z03_P04 350.94 34.4 1579.244 4.500 45.965 0.000 0.700 0.000 0.300 0.000 1579.244
4 Z04_P05_IG6 ELECEQ SCHED4 Z04_P05 350.94 34.4 1579.244 4.500 45.965 0.000 0.700 0.000 0.300 0.000 1579.244
5 Z05_P06_IG6 ELECEQ SCHED4 Z05_P06 350.94 34.4 1579.244 4.500 45.965 0.000 0.700 0.000 0.300 0.000 1579.244
6 Z06_ESCALERAS_IG4 ELECEQ SCHED4 Z06_ESCALERAS 65.25 6.4 293.639 4.500 45.965 0.000 0.700 0.000 0.300 0.000 293.639


Solar View Factor Check Values

Zone/Enclosure Name Original Check Value Calculated Fixed Check Value Final Check Value Number of Iterations Fixed RowSum Convergence Used RowSum Convergence
1 Z01_P02 6.039613E-014 8.371192E-004 8.371192E-004 15 8.371192E-004 8.371192E-004
2 Z02_P03 2.131628E-014 8.594889E-004 8.594889E-004 15 8.594889E-004 8.594889E-004
3 Z03_P04 2.131628E-014 8.594317E-004 8.594317E-004 15 8.594317E-004 8.594317E-004
4 Z04_P05 3.552714E-014 8.594317E-004 8.594317E-004 15 8.594317E-004 8.594317E-004
5 Z05_P06 2.842171E-014 8.482756E-004 8.482756E-004 15 8.482756E-004 8.482756E-004
6 Z06_ESCALERAS 2.131628E-014 7.095171E-004 7.095171E-004 11 7.095171E-004 7.095171E-004


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Surface View Factor Check Values

Zone/Enclosure Name Original Check Value Calculated Fixed Check Value Final Check Value Number of Iterations Fixed RowSum Convergence Used RowSum Convergence
1 Z01_P02 6.039613E-014 8.371192E-004 8.371192E-004 15 8.371192E-004 8.371192E-004
2 Z02_P03 2.131628E-014 8.594889E-004 8.594889E-004 15 8.594889E-004 8.594889E-004
3 Z03_P04 2.131628E-014 8.594317E-004 8.594317E-004 15 8.594317E-004 8.594317E-004
4 Z04_P05 3.552714E-014 8.594317E-004 8.594317E-004 15 8.594317E-004 8.594317E-004
5 Z05_P06 2.842171E-014 8.482756E-004 8.482756E-004 15 8.482756E-004 8.482756E-004
6 Z06_ESCALERAS 2.131628E-014 7.095171E-004 7.095171E-004 11 7.095171E-004 7.095171E-004


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 Z01_S01_E03 2 322.24 91.19 20.80 2 3.00 80.07 3.26 0.31 4 No No
2 Z01_S01_E03_G1 2 322.24 91.19 20.80 2 3.00 80.07 3.26 0.31 2 No No
3 Z01_S01_E04 2 618.79 476.86 42.55 2 3.00 80.07 3.26 0.31 3 No No
4 Z01_S01_E04_G1 2 618.79 476.86 42.55 2 3.00 80.07 3.26 0.31 2 No No
5 Z01_S01_E05 2 323.12 88.29 20.80 2 3.00 80.07 3.26 0.31 4 No No
6 Z01_S01_E05_G1 2 323.12 88.29 20.80 2 3.00 80.07 3.26 0.31 2 No No
7 Z01_S02_E04 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 4 No No
8 Z01_S02_E04_G1 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 2 No No
9 Z01_S02_E04_G2 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 2 No No
10 Z01_S02_E05 1 0.00 0.00 0.00 1 3.00 80.07 3.26 0.31 0 No No
11 Z01_S02_E06 1 0.00 0.00 0.00 1 3.00 80.07 3.26 0.31 0 No No
12 Z01_S02_E09 2 323.12 88.29 20.80 2 3.00 80.07 3.26 0.31 4 No No
13 Z01_S02_E10 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 4 No No
14 Z01_S02_E12 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 4 No No
15 Z01_S03_E03 2 322.24 91.19 20.80 2 3.00 80.07 3.26 0.31 4 No No
16 Z01_S04_E03 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 3 No No
17 Z01_S04_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 3.26 0.31 2 No No
18 Z01_S04_E04 2 323.12 88.29 20.80 2 3.00 80.07 3.26 0.31 4 No No
19 Z01_S04_E07 2 322.24 91.19 20.80 2 3.00 80.07 3.26 0.31 4 No No
20 Z01_S01_TB02 EF 2 618.79 476.86 42.55 2 3.00 80.07 3.26 0.31 3 No No
21 Z01_S01_TB03 FF 2 618.79 476.86 42.55 2 3.00 80.07 3.26 0.31 3 No No
22 Z01_S02_E04_G1_TB2_LATERALES V 2 618.79 476.86 42.55 2 3.00 80.07 3.26 0.31 3 No No
23 Z01_S01_E01 2 343.76 83.47 0.00 2 3.00 80.07 3.26 0.31 0 No No
24 Z01_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 3.26 0.31 0 No No
25 Z01_P02 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 3.26 0.31 0 No No
26 Z01_S01_E06 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 3.26 0.31 0 No No
27 Z02_S01_E03 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
28 Z02_S01_E03_G1 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 2 No No
29 Z02_S01_E04 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
30 Z02_S01_E04_G1 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 2 No No
31 Z02_S01_E05 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 3 No No
32 Z02_S01_E05_G1 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 2 No No
33 Z02_S02_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
34 Z02_S02_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
35 Z02_S03_E05_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
36 Z02_S02_E04 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
37 Z02_S02_E05 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
38 Z02_S02_E08 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
39 Z02_S02_E09 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
40 Z02_S02_E11 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
41 Z02_S03_E04 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
42 Z02_S04_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
43 Z02_S04_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
44 Z02_S04_E04 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
45 Z02_S04_E07 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
46 Z02_S01_TB02 EF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
47 Z02_S01_TB03 FF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
48 Z02_S02_E03_G1_TB1_INFERIOR V 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
49 iz-Z01_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
50 Z02_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
51 Z02_P03 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
52 Z02_S01_E06 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
53 Z03_S01_E03 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
54 Z03_S01_E03_G1 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 2 No No
55 Z03_S01_E04 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 4 No No
56 Z03_S01_E04_G1 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 2 No No
57 Z03_S01_E05 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
58 Z03_S01_E05_G1 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 2 No No
59 Z03_S02_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
60 Z03_S02_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
61 Z03_S03_E04_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
62 Z03_S02_E04 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
63 Z03_S02_E05 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
64 Z03_S02_E08 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
65 Z03_S02_E09 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
66 Z03_S02_E11 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
67 Z03_S03_E03 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
68 Z03_S04_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
69 Z03_S04_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
70 Z03_S04_E04 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
71 Z03_S04_E07 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
72 Z03_S01_TB02 EF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
73 Z03_S01_TB03 FF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
74 Z03_S02_E03_G1_TB1_INFERIOR V 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
75 iz-Z02_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
76 Z03_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
77 Z03_P04 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
78 Z03_S01_E06 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
79 Z04_S01_E03 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
80 Z04_S01_E03_G1 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 2 No No
81 Z04_S01_E04 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
82 Z04_S01_E04_G1 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 2 No No
83 Z04_S01_E05 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 3 No No
84 Z04_S01_E05_G1 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 2 No No
85 Z04_S02_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
86 Z04_S02_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
87 Z04_S03_E04_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
88 Z04_S02_E04 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
89 Z04_S02_E05 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
90 Z04_S02_E08 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
91 Z04_S02_E09 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
92 Z04_S02_E11 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 4 No No
93 Z04_S03_E03 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
94 Z04_S04_E03 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 3 No No
95 Z04_S04_E03_G1 2 336.21 84.54 20.80 2 3.00 80.07 4.18 0.31 2 No No
96 Z04_S04_E04 2 323.12 88.29 20.80 2 3.00 80.07 4.18 0.31 4 No No
97 Z04_S04_E07 2 322.24 91.19 20.80 2 3.00 80.07 4.18 0.31 4 No No
98 Z04_S01_TB02 EF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
99 Z04_S01_TB03 FF 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
100 Z04_S02_E03_G1_TB1_INFERIOR V 2 618.79 476.86 42.55 2 3.00 80.07 4.18 0.31 3 No No
101 iz-Z03_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
102 Z04_S01_E02 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
103 Z04_P05 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
104 Z04_S01_E06 FURNITURE 1 0.00 0.00 0.00 1 3.00 80.07 4.18 0.31 0 No No
105 Z05_S01_E04 2 322.24 91.19 20.80 2 3.05 80.37 7.09 0.31 3 No No
106 Z05_S01_E04_G1 2 322.24 91.19 20.80 2 3.05 80.37 7.09 0.31 2 No No
107 Z05_S01_E05 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 4 No No
108 Z05_S01_E05_G1 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 2 No No
109 Z05_S01_E06 2 323.12 88.29 20.80 2 3.05 80.37 7.09 0.31 3 No No
110 Z05_S01_E06_G1 2 323.12 88.29 20.80 2 3.05 80.37 7.09 0.31 2 No No
111 Z05_S02_E03 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 3 No No
112 Z05_S02_E03_G1 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 2 No No
113 Z05_S03_E04_G1 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 2 No No
114 Z05_S02_E04 1 0.00 0.00 0.00 1 3.05 80.37 7.09 0.31 0 No No
115 Z05_S02_E05 1 0.00 0.00 0.00 1 3.05 80.37 7.09 0.31 0 No No
116 Z05_S02_E08 2 323.12 88.29 20.80 2 3.05 80.37 7.09 0.31 4 No No
117 Z05_S02_E09 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 4 No No
118 Z05_S02_E11 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 4 No No
119 Z05_S03_E03 2 322.24 91.19 20.80 2 3.05 80.37 7.09 0.31 4 No No
120 Z05_S04_E03 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 3 No No
121 Z05_S04_E03_G1 2 336.21 84.54 20.80 2 3.05 80.37 7.09 0.31 2 No No
122 Z05_S04_E04 2 323.12 88.29 20.80 2 3.05 80.37 7.09 0.31 4 No No
123 Z05_S04_E07 2 322.24 91.19 20.80 2 3.05 80.37 7.09 0.31 4 No No
124 Z05_S01_TB02 EF 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 3 No No
125 Z05_S01_TB03 FF 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 3 No No
126 Z05_S01_TB13 FC 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 3 No No
127 Z05_S02_E03_G1_TB1_INFERIOR V 2 618.79 476.86 42.55 2 3.05 80.37 7.09 0.31 3 No No
128 iz-Z04_S01_E02 1 0.00 0.00 0.00 1 3.05 80.37 7.09 0.31 0 No No
129 Z05_S01_E02 2 362.81 194.47 0.00 2 3.05 80.37 7.09 0.31 0 No No
130 Z05_S01_E03 2 362.81 194.47 0.00 2 3.05 80.37 7.09 0.31 0 No No
131 Z05_P06 FURNITURE 1 0.00 0.00 0.00 1 3.05 80.37 7.09 0.31 0 No No
132 Z05_S01_E07 FURNITURE 1 0.00 0.00 0.00 1 3.05 80.37 7.09 0.31 0 No No
133 Z06_S01_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
134 Z06_S01_E04 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
135 Z06_S01_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
136 Z06_S01_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
137 Z06_S01_E07 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
138 Z06_S01_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
139 Z06_S02_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
140 Z06_S02_E03_G1 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 1 No No
141 Z06_S02_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
142 Z06_S02_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
143 Z06_S02_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
144 Z06_S03_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
145 Z06_S03_E03_G1 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 2 No No
146 Z06_S03_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 4 No No
147 Z06_S03_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
148 Z06_S03_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
149 Z06_S04_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
150 Z06_S04_E03_G1 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 2 No No
151 Z06_S04_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 4 No No
152 Z06_S04_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
153 Z06_S04_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
154 Z06_S05_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
155 Z06_S05_E03_G1 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 2 No No
156 Z06_S05_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 4 No No
157 Z06_S05_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
158 Z06_S05_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
159 Z06_S06_E03 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 3 No No
160 Z06_S06_E03_G1 2 336.21 84.54 20.80 2 3.05 74.72 1.89 1.37E-002 2 No No
161 Z06_S06_E05 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 4 No No
162 Z06_S06_E06 2 322.24 91.19 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
163 Z06_S06_E08 2 323.12 88.29 20.80 2 3.05 74.72 1.89 1.37E-002 4 No No
164 Z06_S01_TB03 FS 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
165 Z06_S01_TB04 FF 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
166 Z06_S02_E03_G1_TB1_INFERIOR V 2 618.79 476.86 42.55 2 3.05 74.72 1.89 1.37E-002 3 No No
167 iz-Z01_S02_E05 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
168 iz-Z01_S02_E06 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
169 iz-Z02_S02_E04 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
170 iz-Z02_S02_E05 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
171 iz-Z03_S02_E04 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
172 iz-Z03_S02_E05 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
173 iz-Z04_S02_E04 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
174 iz-Z04_S02_E05 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
175 iz-Z05_S02_E04 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
176 iz-Z05_S02_E05 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
177 Z06_S01_E01 2 11.53 15.47 0.00 2 3.05 74.72 1.89 1.37E-002 0 No No
178 iz-Z06_S01_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
179 iz-Z06_S02_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
180 iz-Z06_S03_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
181 iz-Z06_S04_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
182 iz-Z06_S05_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
183 Z06_S01_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
184 Z06_S02_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
185 Z06_S03_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
186 Z06_S04_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
187 Z06_S05_E02 1 0.00 0.00 0.00 1 3.05 74.72 1.89 1.37E-002 0 No No
188 Z06_S06_E02 2 362.81 194.47 0.00 2 3.05 74.72 1.89 1.37E-002 0 No No


Building Convection Parameters:North Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 84.54 20.80 -9.50 9.50 0.00 10.00 -3.50 17.30


Building Convection Parameters:Northeast Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:East Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 88.29 20.80 -2.81 10.00 -9.85 9.67 -3.50 17.30


Building Convection Parameters:Southeast Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:South Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 476.86 42.55 -9.85 185.26 -10.00 7.39 -25.25 17.30


Building Convection Parameters:Southwest Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Building Convection Parameters:West Facade

Perimeter Height Xmin Xmax Ymin Ymax Zmin Zmax
1 91.19 20.80 -10.00 5.30 -9.85 9.67 -3.50 17.30


Building Convection Parameters:Roof

Area [m2] Perimeter [m] Height [m] Tilt [deg] Azimuth [deg]
1 362.81 194.47 0.00 0.00 182.40! <ZoneInfiltration Airflow Stats Nominal>


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 Z06_ESCALERAS_IG6 VENTIL SCHED4 Z06_ESCALERAS 65.25 6.4 0.131 2.000E-003 2.043E-002 2.361 Natural 0.000 1.0 1.000 0.000 0.000 0.000 -50.00 100.00 -50.00 -50.00 100.00 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 Z01_P02 Mixing/Well-Stirred
2 Z02_P03 Mixing/Well-Stirred
3 Z03_P04 Mixing/Well-Stirred
4 Z04_P05 Mixing/Well-Stirred
5 Z05_P06 Mixing/Well-Stirred
6 Z06_ESCALERAS Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 4


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 Z01_P02 Cooling 23260.16776 23260.16776 1.60324 1.60324 SUMMER 7/22 17:00:00 35.20000 8.49777E-003 350.94300 34.35730 0.70189 0.00000
2 Z01_P02 Heating 16961.64680 16961.64680 0.47130 0.70189 WINTER 12/27 07:00:00 -0.30000 3.16352E-003 350.94300 34.35730 0.70189 0.00000
3 Z02_P03 Cooling 21811.12862 21811.12862 1.50678 1.50678 SUMMER 7/22 17:00:00 35.20000 8.49777E-003 350.94300 34.35730 0.70189 0.00000
4 Z02_P03 Heating 9737.93503 9737.93503 0.27400 0.70189 WINTER 12/27 07:00:00 -0.30000 3.16352E-003 350.94300 34.35730 0.70189 0.00000
5 Z03_P04 Cooling 21755.20904 21755.20904 1.50307 1.50307 SUMMER 7/22 17:00:00 35.20000 8.49777E-003 350.94300 34.35730 0.70189 0.00000
6 Z03_P04 Heating 8865.47554 8865.47554 0.24999 0.70189 WINTER 12/23 07:00:00 -0.60000 3.12175E-003 350.94300 34.35730 0.70189 0.00000
7 Z04_P05 Cooling 21773.39364 21773.39364 1.50422 1.50422 SUMMER 7/22 17:00:00 35.20000 8.49777E-003 350.94300 34.35730 0.70189 0.00000
8 Z04_P05 Heating 9421.36798 9421.36798 0.26521 0.70189 WINTER 12/27 07:00:00 -0.30000 3.16352E-003 350.94300 34.35730 0.70189 0.00000
9 Z05_P06 Cooling 22167.42650 22167.42650 1.52534 1.52534 SUMMER 7/23 17:00:00 35.00000 8.04844E-003 350.94300 34.35730 0.70189 0.00000
10 Z05_P06 Heating 12595.89744 12595.89744 0.35091 0.70189 WINTER 12/27 07:00:00 -0.30000 3.16352E-003 350.94300 34.35730 0.70189 0.00000


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:IdealLoadsAirSystem Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
2 ZoneHVAC:IdealLoadsAirSystem Z01_P02-UT2_ZONE1_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
3 ZoneHVAC:IdealLoadsAirSystem Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
4 ZoneHVAC:IdealLoadsAirSystem Z02_P03-UT2_ZONE2_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
5 ZoneHVAC:IdealLoadsAirSystem Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
6 ZoneHVAC:IdealLoadsAirSystem Z03_P04-UT2_ZONE3_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
7 ZoneHVAC:IdealLoadsAirSystem Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
8 ZoneHVAC:IdealLoadsAirSystem Z04_P05-UT2_ZONE4_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
9 ZoneHVAC:IdealLoadsAirSystem Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
10 ZoneHVAC:IdealLoadsAirSystem Z05_P06-UT2_ZONE5_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000
11 ZoneHVAC:IdealLoadsAirSystem Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM User-Specified Maximum Heating Air Flow Rate [m3/s] 0.00000
12 ZoneHVAC:IdealLoadsAirSystem Z06_ESCALERAS-UT2_ZONE6_IDEALLOADSAIRSYSTEM User-Specified Maximum Cooling Air Flow Rate [m3/s] 0.00000


Zone Surfaces

Zone Name # Surfaces
1 Z01_P02 26
2 Z02_P03 26
3 Z03_P04 26
4 Z04_P05 26
5 Z05_P06 28
6 Z06_ESCALERAS 56


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 Z01_S01_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.18 43.81 15.01 270.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 Z01_S01_E03_G1 Window Z01_S01_E03 Window5 Detailed Fenestration WINDOW N/A 2.302 No 28.80 28.80 28.80 270.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 Z01_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   23.64 59.10 30.48 180.00 90.00 19.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 Z01_S01_E04_G1 Window Z01_S01_E04 Window5 Detailed Fenestration WINDOW2 N/A 3.004 No 28.62 28.62 28.62 180.00 90.00 14.86 1.93 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 Z01_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.17 43.81 15.01 90.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 Z01_S01_E05_G1 Window Z01_S01_E05 Window5 Detailed Fenestration WINDOW3 N/A 2.302 No 28.80 28.80 28.80 90.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 Z01_S02_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.48 20.08 12.14 0.00 90.00 6.69 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
8 Z01_S02_E04_G1 Window Z01_S02_E04 Window5 Detailed Fenestration WINDOW4 N/A 3.004 No 3.80 3.80 3.80 0.00 90.00 1.59 2.40 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.68 0.32 4
9 Z01_S02_E04_G2 Window Z01_S02_E04 Window5 Detailed Fenestration WINDOW5 N/A 3.004 No 4.14 4.14 4.14 0.00 90.00 2.06 2.01 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.67 0.33 4
10 Z01_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 90.00 90.00 2.11 3.00 0.00 iz-Z01_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
11 Z01_S02_E06 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 0.00 90.00 1.09 3.00 0.00 iz-Z01_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
12 Z01_S02_E09 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 90.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.94 6.22E-002 4
13 Z01_S02_E10 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 0.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.10E-002 4
14 Z01_S02_E12 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.22 9.22 9.22 0.00 90.00 3.07 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.74 0.26 4
15 Z01_S03_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 270.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 Z01_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.01 12.61 11.57 0.00 90.00 4.20 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 Z01_S04_E03_G1 Window Z01_S04_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
18 Z01_S04_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 90.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 Z01_S04_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 270.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
20 Z01_S01_TB02 EF Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   3.60 3.60 3.60 180.00 90.00 0.30 12.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
21 Z01_S01_TB03 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   55.58 55.58 55.58 180.00 90.00 0.30 185.26 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
22 Z01_S02_E04_G1_TB2_LATERALES V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   5.83 5.83 5.83 180.00 90.00 0.30 19.44 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
23 Z01_S01_E01 Floor   CTF - ConductionTransferFunction SUELO (INV) 0.535 0.473   343.76 343.76 343.76 90.00 180.00 18.54 18.54 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun WindExposed 1.00 0.00 1.00 0.00 20
24 Z01_S01_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   353.73 353.73 353.73 180.00 0.00 18.81 18.81 0.00 iz-Z01_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 12
25 Z01_P02 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   175.47 175.47 175.47 0.00 90.00 175.47 1.00 0.00 Z01_P02 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
26 Z01_S01_E06 FURNITURE Internal Mass   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 6.552   151.77 151.77 151.77 0.00 90.00 151.77 1.00 0.00 Z01_S01_E06 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
27 Z02_S01_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.18 43.81 15.01 270.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
28 Z02_S01_E03_G1 Window Z02_S01_E03 Window5 Detailed Fenestration WINDOW7 N/A 2.302 No 28.80 28.80 28.80 270.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
29 Z02_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   23.64 59.10 30.48 180.00 90.00 19.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
30 Z02_S01_E04_G1 Window Z02_S01_E04 Window5 Detailed Fenestration WINDOW8 N/A 3.004 No 28.62 28.62 28.62 180.00 90.00 14.86 1.93 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
31 Z02_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.17 43.81 15.01 90.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 Z02_S01_E05_G1 Window Z02_S01_E05 Window5 Detailed Fenestration WINDOW9 N/A 2.302 No 28.80 28.80 28.80 90.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 Z02_S02_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   16.24 20.08 17.59 0.00 90.00 6.69 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 Z02_S02_E03_G1 Window Z02_S02_E03 Window5 Detailed Fenestration WINDOW10 N/A 3.004 No 1.45 1.45 1.45 0.00 90.00 1.98 0.74 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.77 0.23 4
35 Z02_S03_E05_G1 Window Z02_S02_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
36 Z02_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 90.00 90.00 2.11 3.00 0.00 iz-Z02_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
37 Z02_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 0.00 90.00 1.09 3.00 0.00 iz-Z02_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
38 Z02_S02_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 90.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.94 6.23E-002 4
39 Z02_S02_E09 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 0.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.13E-002 4
40 Z02_S02_E11 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.22 9.22 9.22 0.00 90.00 3.07 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.74 0.26 4
41 Z02_S03_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 270.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 Z02_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.01 12.61 11.57 0.00 90.00 4.20 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 Z02_S04_E03_G1 Window Z02_S04_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
44 Z02_S04_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 90.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
45 Z02_S04_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 270.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
46 Z02_S01_TB02 EF Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   3.60 3.60 3.60 180.00 90.00 0.30 12.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
47 Z02_S01_TB03 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   41.35 41.35 41.35 180.00 90.00 0.30 137.83 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
48 Z02_S02_E03_G1_TB1_INFERIOR V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   5.06 5.06 5.06 180.00 90.00 0.30 16.88 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
49 iz-Z01_S01_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   353.73 353.73 353.73 180.00 180.00 18.81 18.81 0.00 Z01_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 12
50 Z02_S01_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   353.73 353.73 353.73 180.00 0.00 18.81 18.81 0.00 iz-Z02_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 12
51 Z02_P03 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   175.47 175.47 175.47 0.00 90.00 175.47 1.00 0.00 Z02_P03 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
52 Z02_S01_E06 FURNITURE Internal Mass   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 6.552   151.77 151.77 151.77 0.00 90.00 151.77 1.00 0.00 Z02_S01_E06 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
53 Z03_S01_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.18 43.81 15.01 270.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 Z03_S01_E03_G1 Window Z03_S01_E03 Window5 Detailed Fenestration WINDOW11 N/A 2.302 No 28.80 28.80 28.80 270.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 Z03_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   23.64 59.10 30.48 180.00 90.00 19.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 Z03_S01_E04_G1 Window Z03_S01_E04 Window5 Detailed Fenestration WINDOW12 N/A 3.004 No 28.62 28.62 28.62 180.00 90.00 14.86 1.93 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 Z03_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.17 43.81 15.01 90.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 Z03_S01_E05_G1 Window Z03_S01_E05 Window5 Detailed Fenestration WINDOW13 N/A 2.302 No 28.80 28.80 28.80 90.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
59 Z03_S02_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   16.24 20.08 17.59 0.00 90.00 6.69 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
60 Z03_S02_E03_G1 Window Z03_S02_E03 Window5 Detailed Fenestration WINDOW10 N/A 3.004 No 1.45 1.45 1.45 0.00 90.00 1.98 0.74 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.77 0.23 4
61 Z03_S03_E04_G1 Window Z03_S02_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
62 Z03_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 90.00 90.00 2.11 3.00 0.00 iz-Z03_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
63 Z03_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 0.00 90.00 1.09 3.00 0.00 iz-Z03_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
64 Z03_S02_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 90.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.93 6.62E-002 4
65 Z03_S02_E09 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 0.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.19E-002 4
66 Z03_S02_E11 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.22 9.22 9.22 0.00 90.00 3.07 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.74 0.26 4
67 Z03_S03_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 270.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 Z03_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.01 12.61 11.57 0.00 90.00 4.20 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 Z03_S04_E03_G1 Window Z03_S04_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
70 Z03_S04_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 90.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 Z03_S04_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 270.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
72 Z03_S01_TB02 EF Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   3.60 3.60 3.60 180.00 90.00 0.30 12.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
73 Z03_S01_TB03 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   41.38 41.38 41.38 180.00 90.00 0.30 137.94 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
74 Z03_S02_E03_G1_TB1_INFERIOR V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   5.06 5.06 5.06 180.00 90.00 0.30 16.88 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
75 iz-Z02_S01_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   353.73 353.73 353.73 180.00 180.00 18.81 18.81 0.00 Z02_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 12
76 Z03_S01_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   353.73 353.73 353.73 180.00 0.00 18.81 18.81 0.00 iz-Z03_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 12
77 Z03_P04 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   175.47 175.47 175.47 0.00 90.00 175.47 1.00 0.00 Z03_P04 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
78 Z03_S01_E06 FURNITURE Internal Mass   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 6.552   151.77 151.77 151.77 0.00 90.00 151.77 1.00 0.00 Z03_S01_E06 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
79 Z04_S01_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.18 43.81 15.01 270.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
80 Z04_S01_E03_G1 Window Z04_S01_E03 Window5 Detailed Fenestration WINDOW14 N/A 2.302 No 28.80 28.80 28.80 270.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
81 Z04_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   23.64 59.10 30.48 180.00 90.00 19.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 Z04_S01_E04_G1 Window Z04_S01_E04 Window5 Detailed Fenestration WINDOW15 N/A 3.004 No 28.62 28.62 28.62 180.00 90.00 14.86 1.93 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 Z04_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.17 43.81 15.01 90.00 90.00 14.60 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 Z04_S01_E05_G1 Window Z04_S01_E05 Window5 Detailed Fenestration WINDOW16 N/A 2.302 No 28.80 28.80 28.80 90.00 90.00 12.60 2.29 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 Z04_S02_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   16.24 20.08 17.59 0.00 90.00 6.69 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 Z04_S02_E03_G1 Window Z04_S02_E03 Window5 Detailed Fenestration WINDOW10 N/A 3.004 No 1.45 1.45 1.45 0.00 90.00 1.98 0.74 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.77 0.23 4
87 Z04_S03_E04_G1 Window Z04_S02_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
88 Z04_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 90.00 90.00 2.11 3.00 0.00 iz-Z04_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
89 Z04_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 0.00 90.00 1.09 3.00 0.00 iz-Z04_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
90 Z04_S02_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 90.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.93 7.30E-002 4
91 Z04_S02_E09 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 0.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.48E-002 4
92 Z04_S02_E11 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.22 9.22 9.22 0.00 90.00 3.07 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.73 0.27 4
93 Z04_S03_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 270.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 Z04_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.01 12.61 11.57 0.00 90.00 4.20 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 Z04_S04_E03_G1 Window Z04_S04_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
96 Z04_S04_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.91 13.91 13.91 90.00 90.00 4.64 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 Z04_S04_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 270.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.78 0.22 4
98 Z04_S01_TB02 EF Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   3.60 3.60 3.60 180.00 90.00 0.30 12.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
99 Z04_S01_TB03 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   41.38 41.38 41.38 180.00 90.00 0.30 137.94 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
100 Z04_S02_E03_G1_TB1_INFERIOR V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   5.06 5.06 5.06 180.00 90.00 0.30 16.88 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
101 iz-Z03_S01_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   353.73 353.73 353.73 180.00 180.00 18.81 18.81 0.00 Z03_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 12
102 Z04_S01_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   353.73 353.73 353.73 180.00 0.00 18.81 18.81 0.00 iz-Z04_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 12
103 Z04_P05 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   175.47 175.47 175.47 0.00 90.00 175.47 1.00 0.00 Z04_P05 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
104 Z04_S01_E06 FURNITURE Internal Mass   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 6.552   151.77 151.77 151.77 0.00 90.00 151.77 1.00 0.00 Z04_S01_E06 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
105 Z05_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.33 44.54 15.24 270.00 90.00 14.60 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 Z05_S01_E04_G1 Window Z05_S01_E04 Window5 Detailed Fenestration WINDOW17 N/A 2.302 No 29.30 29.30 29.30 270.00 90.00 12.60 2.33 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 Z05_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   24.03 60.09 30.99 180.00 90.00 19.70 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 Z05_S01_E05_G1 Window Z05_S01_E05 Window5 Detailed Fenestration WINDOW18 N/A 3.004 No 29.10 29.10 29.10 180.00 90.00 14.86 1.96 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
109 Z05_S01_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.33 44.54 15.24 90.00 90.00 14.60 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
110 Z05_S01_E06_G1 Window Z05_S01_E06 Window5 Detailed Fenestration WINDOW19 N/A 2.302 No 29.30 29.30 29.30 90.00 90.00 12.60 2.33 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
111 Z05_S02_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   16.58 20.42 17.92 0.00 90.00 6.69 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 Z05_S02_E03_G1 Window Z05_S02_E03 Window5 Detailed Fenestration WINDOW10 N/A 3.004 No 1.45 1.45 1.45 0.00 90.00 1.98 0.74 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.77 0.23 4
113 Z05_S03_E04_G1 Window Z05_S02_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
114 Z05_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.44 6.44 6.44 90.00 90.00 2.11 3.05 0.00 iz-Z05_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
115 Z05_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.33 3.33 3.33 0.00 90.00 1.09 3.05 0.00 iz-Z05_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 0.50 0.50 4
116 Z05_S02_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.98 1.98 1.98 90.00 90.00 0.65 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.88 0.12 4
117 Z05_S02_E09 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.66 10.66 10.66 0.00 90.00 3.50 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.90 0.10 4
118 Z05_S02_E11 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.37 9.37 9.37 0.00 90.00 3.07 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.69 0.31 4
119 Z05_S03_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   14.14 14.14 14.14 270.00 90.00 4.64 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 Z05_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.22 12.82 11.78 0.00 90.00 4.20 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 Z05_S04_E03_G1 Window Z05_S04_E03 Window5 Detailed Fenestration WINDOW6 N/A 3.004 No 1.04 1.04 1.04 0.00 90.00 1.36 0.76 0.48 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
122 Z05_S04_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   14.14 14.14 14.14 90.00 90.00 4.64 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 Z05_S04_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.75 8.75 8.75 270.00 90.00 2.87 3.05 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.70 0.30 4
124 Z05_S01_TB02 EF Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   3.66 3.66 3.66 180.00 90.00 0.30 12.20 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
125 Z05_S01_TB03 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   20.69 20.69 20.69 180.00 90.00 0.30 68.97 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
126 Z05_S01_TB13 FC Wall   CTF - ConductionTransferFunction TBW_0_51667U_ 1.935 1.501   20.46 20.46 20.46 180.00 90.00 0.30 68.22 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
127 Z05_S02_E03_G1_TB1_INFERIOR V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   5.06 5.06 5.06 180.00 90.00 0.30 16.88 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
128 iz-Z04_S01_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   353.73 353.73 353.73 180.00 180.00 18.81 18.81 0.00 Z04_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 12
129 Z05_S01_E02 Roof   CTF - ConductionTransferFunction CUBIERTA 0.406 0.377   7.29 7.29 7.29 180.00 0.00 2.70 2.70 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.00 1.00 9.99E-016 1.00 8
130 Z05_S01_E03 Roof   CTF - ConductionTransferFunction CUBIERTA 0.406 0.377   345.84 345.84 345.84 180.00 0.00 18.60 18.60 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.00 1.00 0.00 1.00 12
131 Z05_P06 FURNITURE Internal Mass   CTF - ConductionTransferFunction FURNIT_INTERNALMASS 3.600 3.600   175.47 175.47 175.47 0.00 90.00 175.47 1.00 0.00 Z05_P06 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
132 Z05_S01_E07 FURNITURE Internal Mass   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 6.552   154.30 154.30 154.30 0.00 90.00 154.30 1.00 0.00 Z05_S01_E07 FURNITURE Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 0.50 1.00 0.00 0
133 Z06_S01_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   14.09 14.09 14.09 0.00 90.00 4.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
134 Z06_S01_E04 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   6.83 6.83 6.83 270.00 90.00 2.28 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
135 Z06_S01_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 180.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.58 0.42 4
136 Z06_S01_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 270.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.73 0.27 4
137 Z06_S01_E07 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   3.28 3.28 3.28 180.00 90.00 1.09 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 Z06_S01_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.11 9.11 9.11 90.00 90.00 3.04 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.60 0.40 4
139 Z06_S02_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.04 14.09 13.41 0.00 90.00 4.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 Z06_S02_E03_G1 Window Z06_S02_E03 Window5 Detailed Fenestration WINDOW20 N/A 3.004 No 0.68 0.68 0.68 0.00 90.00 0.85 0.80 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.82 0.18 4
141 Z06_S02_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 180.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.39E-002 4
142 Z06_S02_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 270.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 7.83E-002 4
143 Z06_S02_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 90.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
144 Z06_S03_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.04 14.09 13.41 0.00 90.00 4.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 Z06_S03_E03_G1 Window Z06_S03_E03 Window5 Detailed Fenestration WINDOW20 N/A 3.004 No 0.68 0.68 0.68 0.00 90.00 0.85 0.80 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.82 0.18 4
146 Z06_S03_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 180.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.41E-002 4
147 Z06_S03_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 270.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 7.84E-002 4
148 Z06_S03_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 90.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.79 0.21 4
149 Z06_S04_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.04 14.09 13.41 0.00 90.00 4.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
150 Z06_S04_E03_G1 Window Z06_S04_E03 Window5 Detailed Fenestration WINDOW20 N/A 3.004 No 0.68 0.68 0.68 0.00 90.00 0.85 0.80 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.82 0.18 4
151 Z06_S04_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 180.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.45E-002 4
152 Z06_S04_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 270.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.92 8.02E-002 4
153 Z06_S04_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 90.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.78 0.22 4
154 Z06_S05_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   13.04 14.09 13.41 0.00 90.00 4.70 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 Z06_S05_E03_G1 Window Z06_S05_E03 Window5 Detailed Fenestration WINDOW20 N/A 3.004 No 0.68 0.68 0.68 0.00 90.00 0.85 0.80 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.82 0.18 4
156 Z06_S05_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   10.49 10.49 10.49 180.00 90.00 3.50 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.91 8.66E-002 4
157 Z06_S05_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   1.95 1.95 1.95 270.00 90.00 0.65 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.91 8.54E-002 4
158 Z06_S05_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   8.61 8.61 8.61 90.00 90.00 2.87 3.00 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.77 0.23 4
159 Z06_S06_E03 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   14.45 15.50 14.82 0.00 90.00 4.70 3.30 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.50 0.50 4
160 Z06_S06_E03_G1 Window Z06_S06_E03 Window5 Detailed Fenestration WINDOW20 N/A 3.004 No 0.68 0.68 0.68 0.00 90.00 0.85 0.80 0.47 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.82 0.18 4
161 Z06_S06_E05 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   11.54 11.54 11.54 180.00 90.00 3.50 3.30 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.85 0.15 4
162 Z06_S06_E06 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   2.15 2.15 2.15 270.00 90.00 0.65 3.30 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.85 0.15 4
163 Z06_S06_E08 Wall   CTF - ConductionTransferFunction MURO_EXTERIOR 0.744 0.669   9.47 9.47 9.47 90.00 90.00 2.87 3.30 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.50 0.50 0.67 0.33 4
164 Z06_S01_TB03 FS Wall   CTF - ConductionTransferFunction TBW_1_85U_ 0.541 0.500   1.41 1.41 1.41 180.00 90.00 0.30 4.70 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
165 Z06_S01_TB04 FF Wall   CTF - ConductionTransferFunction TBW_0_15577U_ 6.420 3.274   16.82 16.82 16.82 180.00 90.00 0.30 56.07 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
166 Z06_S02_E03_G1_TB1_INFERIOR V Wall   CTF - ConductionTransferFunction TBW_0_6U_ 1.667 1.334   6.15 6.15 6.15 180.00 90.00 0.30 20.50 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
167 iz-Z01_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 270.00 90.00 2.11 3.00 0.00 Z01_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
168 iz-Z01_S02_E06 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 180.00 90.00 1.09 3.00 0.00 Z01_S02_E06 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
169 iz-Z02_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 270.00 90.00 2.11 3.00 0.00 Z02_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
170 iz-Z02_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 180.00 90.00 1.09 3.00 0.00 Z02_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
171 iz-Z03_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 270.00 90.00 2.11 3.00 0.00 Z03_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
172 iz-Z03_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 180.00 90.00 1.09 3.00 0.00 Z03_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
173 iz-Z04_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.33 6.33 6.33 270.00 90.00 2.11 3.00 0.00 Z04_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
174 iz-Z04_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.28 3.28 3.28 180.00 90.00 1.09 3.00 0.00 Z04_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
175 iz-Z05_S02_E04 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   6.44 6.44 6.44 270.00 90.00 2.11 3.05 0.00 Z05_S02_E04 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
176 iz-Z05_S02_E05 Wall   CTF - ConductionTransferFunction PARTICION_INTERIOR 6.552 3.308   3.33 3.33 3.33 180.00 90.00 1.09 3.05 0.00 Z05_S02_E05 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.50 0.50 0.50 0.50 4
177 Z06_S01_E01 Floor   CTF - ConductionTransferFunction SUELO (INV) 0.535 0.473   11.53 11.53 11.53 90.00 180.00 3.40 3.40 0.00 ExternalEnvironment User Supplied Value User Supplied Value NoSun WindExposed 1.00 0.00 1.00 0.00 6
178 iz-Z06_S01_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   10.75 10.75 10.75 90.00 180.00 3.28 3.28 0.00 Z06_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 6
179 iz-Z06_S02_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   10.75 10.75 10.75 90.00 180.00 3.28 3.28 0.00 Z06_S02_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 6
180 iz-Z06_S03_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   10.75 10.75 10.75 90.00 180.00 3.28 3.28 0.00 Z06_S03_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 6
181 iz-Z06_S04_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   10.75 10.75 10.75 90.00 180.00 3.28 3.28 0.00 Z06_S04_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 6
182 iz-Z06_S05_E02 Floor   CTF - ConductionTransferFunction iz-FORJADO_INTERIOR 5.674 2.385   10.75 10.75 10.75 90.00 180.00 3.28 3.28 0.00 Z06_S05_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 1.00 0.00 1.00 0.00 6
183 Z06_S01_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   10.75 10.75 10.75 270.00 0.00 3.28 3.28 0.00 iz-Z06_S01_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
184 Z06_S02_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   10.75 10.75 10.75 270.00 0.00 3.28 3.28 0.00 iz-Z06_S02_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
185 Z06_S03_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   10.75 10.75 10.75 270.00 0.00 3.28 3.28 0.00 iz-Z06_S03_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
186 Z06_S04_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   10.75 10.75 10.75 270.00 0.00 3.28 3.28 0.00 iz-Z06_S04_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
187 Z06_S05_E02 Roof   CTF - ConductionTransferFunction FORJADO_INTERIOR 5.674 2.742   10.75 10.75 10.75 270.00 0.00 3.28 3.28 0.00 iz-Z06_S05_E02 Other/Same Surface Int Conv User Supplied Value NoSun NoWind 0.00 1.00 0.00 1.00 6
188 Z06_S06_E02 Roof   CTF - ConductionTransferFunction CUBIERTA 0.406 0.377   9.68 9.68 9.68 270.00 0.00 3.11 3.11 0.00 ExternalEnvironment User Supplied Value User Supplied Value SunExposed WindExposed 0.00 1.00 0.00 1.00 6


Frame/Divider Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m}
1 Z01_S01_E03 (191MM) Frame Z01_S01_E03_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
2 Z01_S01_E04 (199MM) Frame Z01_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   6.84 6.84 * N/A N/A 0.20 N/A  
3 Z01_S01_E05 (191MM) Frame Z01_S01_E05_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
4 PUERTA_ACCESO_A_EDIFICIO_165_170_ (52MM) Frame Z01_S02_E04_G1 Window5 Detailed Fenestration   N/A N/A   0.42 0.42 * N/A N/A 5.20E-002 N/A  
5 N_VESTIBULO_255_260_ (245MM) Frame Z01_S02_E04_G2 Window5 Detailed Fenestration   N/A N/A   2.23 2.23 * N/A N/A 0.25 N/A  
6 N_160_165_ (118MM) Frame Z01_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
7 Z02_S01_E03 (191MM) Frame Z02_S01_E03_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
8 Z02_S01_E04 (199MM) Frame Z02_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   6.84 6.84 * N/A N/A 0.20 N/A  
9 Z02_S01_E05 (191MM) Frame Z02_S01_E05_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
10 N_220_225_ (132MM) Frame Z02_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.79 0.79 * N/A N/A 0.13 N/A  
11 N_160_165_ (118MM) Frame Z02_S03_E05_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
12 N_160_165_ (118MM) Frame Z02_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
13 Z03_S01_E03 (191MM) Frame Z03_S01_E03_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
14 Z03_S01_E04 (199MM) Frame Z03_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   6.84 6.84 * N/A N/A 0.20 N/A  
15 Z03_S01_E05 (191MM) Frame Z03_S01_E05_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
16 N_220_225_ (132MM) Frame Z03_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.79 0.79 * N/A N/A 0.13 N/A  
17 N_160_165_ (118MM) Frame Z03_S03_E04_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
18 N_160_165_ (118MM) Frame Z03_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
19 Z04_S01_E03 (191MM) Frame Z04_S01_E03_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
20 Z04_S01_E04 (199MM) Frame Z04_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   6.84 6.84 * N/A N/A 0.20 N/A  
21 Z04_S01_E05 (191MM) Frame Z04_S01_E05_G1 Window5 Detailed Fenestration   N/A N/A   5.83 5.83 * N/A N/A 0.19 N/A  
22 N_220_225_ (132MM) Frame Z04_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.79 0.79 * N/A N/A 0.13 N/A  
23 N_160_165_ (118MM) Frame Z04_S03_E04_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
24 N_160_165_ (118MM) Frame Z04_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
25 Z05_S01_E04 (193MM) Frame Z05_S01_E04_G1 Window5 Detailed Fenestration   N/A N/A   5.91 5.91 * N/A N/A 0.19 N/A  
26 Z05_S01_E05 (202MM) Frame Z05_S01_E05_G1 Window5 Detailed Fenestration   N/A N/A   6.96 6.96 * N/A N/A 0.20 N/A  
27 Z05_S01_E06 (193MM) Frame Z05_S01_E06_G1 Window5 Detailed Fenestration   N/A N/A   5.91 5.91 * N/A N/A 0.19 N/A  
28 N_220_225_ (132MM) Frame Z05_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.79 0.79 * N/A N/A 0.13 N/A  
29 N_160_165_ (118MM) Frame Z05_S03_E04_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
30 N_160_165_ (118MM) Frame Z05_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.56 0.56 * N/A N/A 0.12 N/A  
31 N_105_110_ (99MM) Frame Z06_S02_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.37 0.37 * N/A N/A 9.90E-002 N/A  
32 N_105_110_ (99MM) Frame Z06_S03_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.37 0.37 * N/A N/A 9.90E-002 N/A  
33 N_105_110_ (99MM) Frame Z06_S04_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.37 0.37 * N/A N/A 9.90E-002 N/A  
34 N_105_110_ (99MM) Frame Z06_S05_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.37 0.37 * N/A N/A 9.90E-002 N/A  
35 N_105_110_ (99MM) Frame Z06_S06_E03_G1 Window5 Detailed Fenestration   N/A N/A   0.37 0.37 * N/A N/A 9.90E-002 N/A  


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2007 12/31/2007 Monday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes WeatherFile 03/25 10/28


Environment:WarmupDays

NumberofWarmupDays
1 9


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 Z01_P02 RunPeriod: RUNPERIOD 1 8.2977563601E-002 0.3441123818 Pass Pass 0.5872737670 2.6263760647 Pass Pass
2 Z02_P03 RunPeriod: RUNPERIOD 1 4.7097984824E-002 0.1958609493 Pass Pass 0.2683558164 1.1569161062 Pass Pass
3 Z03_P04 RunPeriod: RUNPERIOD 1 4.0496005185E-002 0.1753943986 Pass Pass 0.1783848498 0.6736087745 Pass Pass
4 Z04_P05 RunPeriod: RUNPERIOD 1 4.4854544493E-002 0.1894240137 Pass Pass 0.2111856643 0.7844926569 Pass Pass
5 Z05_P06 RunPeriod: RUNPERIOD 1 7.3793068237E-002 0.2865553039 Pass Pass 0.2703465749 0.9198087925 Pass Pass
6 Z06_ESCALERAS RunPeriod: RUNPERIOD 1 3.4291592330E-002 5.7380322332E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kWh] 442827.28 8116.99 0.00 0.00 0.00 450939.21



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_P02 7736.75 1022.25 1.00 0.00 0.00
Z02_P03 7600.25 1159.75 0.00 0.00 0.00
Z03_P04 7555.75 1204.25 0.00 0.00 0.00
Z04_P05 7562.50 1197.50 0.00 0.00 0.00
Z05_P06 7653.00 1107.00 0.00 0.00 0.00
Z06_ESCALERAS 7633.50 1126.50 0.00 0.00 0.00
Min 7555.75 1022.25 0.00 0.00 0.00
Max 7736.75 1204.25 1.00 0.00 0.00
Average 7623.62 1136.21 0.17 0.00 0.00
Sum 45741.75 6817.25 1.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_P02 121899.70 0.00 0.00 0.00 0.00
Z02_P03 121899.70 0.00 0.00 0.00 0.00
Z03_P04 121899.70 0.00 0.00 0.00 0.00
Z04_P05 121899.70 0.00 0.00 0.00 0.00
Z05_P06 121899.70 0.00 0.00 0.00 0.00
Z06_ESCALERAS 20043.23 2622.39 0.00 0.00 0.00
Min 20043.23 0.00 0.00 0.00 0.00
Max 121899.70 2622.39 0.00 0.00 0.00
Average 104923.62 437.06 0.00 0.00 0.00
Sum 629541.73 2622.39 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7°C, ≤ 32.2°C) [hr] Extreme Caution (> 32.2°C, ≤ 39.4°C) [hr] Danger (> 39.4°C, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
Z01_P02 3548.00 0.00 0.00 0.00 0.00
Z02_P03 3548.00 0.00 0.00 0.00 0.00
Z03_P04 3548.00 0.00 0.00 0.00 0.00
Z04_P05 3548.00 0.00 0.00 0.00 0.00
Z05_P06 3548.00 0.00 0.00 0.00 0.00
Z06_ESCALERAS 3137.50 410.50 0.00 0.00 0.00
Min 3137.50 0.00 0.00 0.00 0.00
Max 3548.00 410.50 0.00 0.00 0.00
Average 3479.58 68.42 0.00 0.00 0.00
Sum 20877.50 410.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_P02 7916.50 843.50 0.00 0.00 0.00
Z02_P03 7834.00 926.00 0.00 0.00 0.00
Z03_P04 7804.25 955.75 0.00 0.00 0.00
Z04_P05 7809.00 951.00 0.00 0.00 0.00
Z05_P06 7852.00 908.00 0.00 0.00 0.00
Z06_ESCALERAS 7673.25 1086.75 0.00 0.00 0.00
Min 7673.25 843.50 0.00 0.00 0.00
Max 7916.50 1086.75 0.00 0.00 0.00
Average 7814.83 945.17 0.00 0.00 0.00
Sum 46889.00 5671.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_P02 121453.06 446.64 0.00 0.00 0.00
Z02_P03 121564.72 334.98 0.00 0.00 0.00
Z03_P04 121607.66 292.04 0.00 0.00 0.00
Z04_P05 121624.84 274.86 0.00 0.00 0.00
Z05_P06 121590.48 309.22 0.00 0.00 0.00
Z06_ESCALERAS 20035.24 2630.37 0.00 0.00 0.00
Min 20035.24 274.86 0.00 0.00 0.00
Max 121624.84 2630.37 0.00 0.00 0.00
Average 104646.00 714.69 0.00 0.00 0.00
Sum 627876.01 4288.11 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
Z01_P02 3535.00 13.00 0.00 0.00 0.00
Z02_P03 3538.25 9.75 0.00 0.00 0.00
Z03_P04 3539.50 8.50 0.00 0.00 0.00
Z04_P05 3540.00 8.00 0.00 0.00 0.00
Z05_P06 3539.00 9.00 0.00 0.00 0.00
Z06_ESCALERAS 3136.25 411.75 0.00 0.00 0.00
Min 3136.25 8.00 0.00 0.00 0.00
Max 3540.00 411.75 0.00 0.00 0.00
Average 3471.33 76.67 0.00 0.00 0.00
Sum 20828.00 460.00 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
Z01_P02 100.75 05-JAN-04:45 333.50 0.00 0.00
Z02_P03 171.50 08-JAN-03:30 60.00 0.00 0.00
Z03_P04 332.50 14-JAN-20:30 36.25 0.00 0.00
Z04_P05 173.50 08-JAN-05:30 44.50 0.00 0.00
Z05_P06 169.00 08-JAN-01:00 187.25 0.00 0.00
Z06_ESCALERAS 0.00 01-JAN-00:00 4310.75 11558.00 1809.25
Min 0.00 - 36.25 0.00 0.00
Max 332.50 - 4310.75 11558.00 1809.25
Average 157.88 - 828.71 1926.33 301.54
Sum 947.25 - 4972.25 11558.00 1809.25


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
Z01_P02 4118.75 21-JUN-14:45 106.00 0.00 0.00
Z02_P03 4118.75 21-JUN-14:45 90.00 0.00 0.00
Z03_P04 4118.75 21-JUN-14:45 94.25 0.00 0.00
Z04_P05 4118.75 21-JUN-14:45 96.25 0.00 0.00
Z05_P06 4118.75 21-JUN-14:45 96.25 0.00 0.00
Z06_ESCALERAS 4864.25 22-JUL-16:15 59.75 170.89 26.75
Min 4118.75 - 59.75 0.00 0.00
Max 4864.25 - 106.00 170.89 26.75
Average 4243.00 - 90.42 28.48 4.46
Sum 25458.00 - 542.50 170.89 26.75


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°C·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°C·hr] Heating Setpoint Unmet Degree-Hours [°C·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°C·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
Z01_P02 0.18 6.27 0.18 0.20 6.73 0.20
Z02_P03 0.15 5.24 0.15 0.07 2.33 0.07
Z03_P04 0.17 5.77 0.17 0.05 1.64 0.05
Z04_P05 0.17 5.81 0.17 0.06 2.07 0.06
Z05_P06 0.15 4.99 0.15 0.22 7.53 0.22
Z06_ESCALERAS 0.00 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.18 6.27 0.18 0.22 7.53 0.22
Average 0.14 4.68 0.14 0.10 3.38 0.10
Sum 0.82 28.08 0.82 0.59 20.30 0.59


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
Z01_P02 0.00 0.00 0.00 0.00
Z02_P03 0.00 0.00 0.00 0.00
Z03_P04 0.00 0.00 0.00 0.00
Z04_P05 0.00 0.00 0.00 0.00
Z05_P06 0.00 0.00 0.00 0.00
Z06_ESCALERAS 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
Z01_P02 0.00 0.00 0.00 0.00
Z02_P03 0.00 0.00 0.00 0.00
Z03_P04 0.00 0.00 0.00 0.00
Z04_P05 0.00 0.00 0.00 0.00
Z05_P06 0.00 0.00 0.00 0.00
Z06_ESCALERAS 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
None            


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S01_E03 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.18 270.00 90.00 W
Z01_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 59.10 23.64 180.00 90.00 S
Z01_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.17 90.00 90.00 E
Z01_S02_E04 MURO_EXTERIOR 0.40 0.669 0.744 20.08 9.48 0.00 90.00 N
Z01_S02_E09 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 90.00 90.00 E
Z01_S02_E10 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 0.00 90.00 N
Z01_S02_E12 MURO_EXTERIOR 0.40 0.669 0.744 9.22 9.22 0.00 90.00 N
Z01_S03_E03 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 270.00 90.00 W
Z01_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 12.61 11.01 0.00 90.00 N
Z01_S04_E04 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 90.00 90.00 E
Z01_S04_E07 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 270.00 90.00 W
Z01_S01_TB02 EF TBW_1_85U_ 0.40 0.500 0.541 3.60 3.60 180.00 90.00 S
Z01_S01_TB03 FF TBW_0_15577U_ 0.40 3.274 6.420 55.58 55.58 180.00 90.00 S
Z01_S02_E04_G1_TB2_LATERALES V TBW_0_6U_ 0.40 1.334 1.667 5.83 5.83 180.00 90.00 S
Z01_S01_E01 SUELO (INV) 0.40 0.485 0.535 343.76 343.76 90.00 180.00  
Z02_S01_E03 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.18 270.00 90.00 W
Z02_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 59.10 23.64 180.00 90.00 S
Z02_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.17 90.00 90.00 E
Z02_S02_E03 MURO_EXTERIOR 0.40 0.669 0.744 20.08 16.24 0.00 90.00 N
Z02_S02_E08 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 90.00 90.00 E
Z02_S02_E09 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 0.00 90.00 N
Z02_S02_E11 MURO_EXTERIOR 0.40 0.669 0.744 9.22 9.22 0.00 90.00 N
Z02_S03_E04 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 270.00 90.00 W
Z02_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 12.61 11.01 0.00 90.00 N
Z02_S04_E04 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 90.00 90.00 E
Z02_S04_E07 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 270.00 90.00 W
Z02_S01_TB02 EF TBW_1_85U_ 0.40 0.500 0.541 3.60 3.60 180.00 90.00 S
Z02_S01_TB03 FF TBW_0_15577U_ 0.40 3.274 6.420 41.35 41.35 180.00 90.00 S
Z02_S02_E03_G1_TB1_INFERIOR V TBW_0_6U_ 0.40 1.334 1.667 5.06 5.06 180.00 90.00 S
Z03_S01_E03 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.18 270.00 90.00 W
Z03_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 59.10 23.64 180.00 90.00 S
Z03_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.17 90.00 90.00 E
Z03_S02_E03 MURO_EXTERIOR 0.40 0.669 0.744 20.08 16.24 0.00 90.00 N
Z03_S02_E08 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 90.00 90.00 E
Z03_S02_E09 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 0.00 90.00 N
Z03_S02_E11 MURO_EXTERIOR 0.40 0.669 0.744 9.22 9.22 0.00 90.00 N
Z03_S03_E03 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 270.00 90.00 W
Z03_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 12.61 11.01 0.00 90.00 N
Z03_S04_E04 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 90.00 90.00 E
Z03_S04_E07 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 270.00 90.00 W
Z03_S01_TB02 EF TBW_1_85U_ 0.40 0.500 0.541 3.60 3.60 180.00 90.00 S
Z03_S01_TB03 FF TBW_0_15577U_ 0.40 3.274 6.420 41.38 41.38 180.00 90.00 S
Z03_S02_E03_G1_TB1_INFERIOR V TBW_0_6U_ 0.40 1.334 1.667 5.06 5.06 180.00 90.00 S
Z04_S01_E03 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.18 270.00 90.00 W
Z04_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 59.10 23.64 180.00 90.00 S
Z04_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 43.81 9.17 90.00 90.00 E
Z04_S02_E03 MURO_EXTERIOR 0.40 0.669 0.744 20.08 16.24 0.00 90.00 N
Z04_S02_E08 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 90.00 90.00 E
Z04_S02_E09 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 0.00 90.00 N
Z04_S02_E11 MURO_EXTERIOR 0.40 0.669 0.744 9.22 9.22 0.00 90.00 N
Z04_S03_E03 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 270.00 90.00 W
Z04_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 12.61 11.01 0.00 90.00 N
Z04_S04_E04 MURO_EXTERIOR 0.40 0.669 0.744 13.91 13.91 90.00 90.00 E
Z04_S04_E07 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 270.00 90.00 W
Z04_S01_TB02 EF TBW_1_85U_ 0.40 0.500 0.541 3.60 3.60 180.00 90.00 S
Z04_S01_TB03 FF TBW_0_15577U_ 0.40 3.274 6.420 41.38 41.38 180.00 90.00 S
Z04_S02_E03_G1_TB1_INFERIOR V TBW_0_6U_ 0.40 1.334 1.667 5.06 5.06 180.00 90.00 S
Z05_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 44.54 9.33 270.00 90.00 W
Z05_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 60.09 24.03 180.00 90.00 S
Z05_S01_E06 MURO_EXTERIOR 0.40 0.669 0.744 44.54 9.33 90.00 90.00 E
Z05_S02_E03 MURO_EXTERIOR 0.40 0.669 0.744 20.42 16.58 0.00 90.00 N
Z05_S02_E08 MURO_EXTERIOR 0.40 0.669 0.744 1.98 1.98 90.00 90.00 E
Z05_S02_E09 MURO_EXTERIOR 0.40 0.669 0.744 10.66 10.66 0.00 90.00 N
Z05_S02_E11 MURO_EXTERIOR 0.40 0.669 0.744 9.37 9.37 0.00 90.00 N
Z05_S03_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.14 14.14 270.00 90.00 W
Z05_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 12.82 11.22 0.00 90.00 N
Z05_S04_E04 MURO_EXTERIOR 0.40 0.669 0.744 14.14 14.14 90.00 90.00 E
Z05_S04_E07 MURO_EXTERIOR 0.40 0.669 0.744 8.75 8.75 270.00 90.00 W
Z05_S01_TB02 EF TBW_1_85U_ 0.40 0.500 0.541 3.66 3.66 180.00 90.00 S
Z05_S01_TB03 FF TBW_0_15577U_ 0.40 3.274 6.420 20.69 20.69 180.00 90.00 S
Z05_S01_TB13 FC TBW_0_51667U_ 0.40 1.501 1.935 20.46 20.46 180.00 90.00 S
Z05_S02_E03_G1_TB1_INFERIOR V TBW_0_6U_ 0.40 1.334 1.667 5.06 5.06 180.00 90.00 S
Z05_S01_E02 CUBIERTA 0.40 0.385 0.406 7.29 7.29 180.00 0.00  
Z05_S01_E03 CUBIERTA 0.40 0.385 0.406 345.84 345.84 180.00 0.00  
Z06_S01_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.09 14.09 0.00 90.00 N
Z06_S01_E04 MURO_EXTERIOR 0.40 0.669 0.744 6.83 6.83 270.00 90.00 W
Z06_S01_E05 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 180.00 90.00 S
Z06_S01_E06 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 270.00 90.00 W
Z06_S01_E07 MURO_EXTERIOR 0.40 0.669 0.744 3.28 3.28 180.00 90.00 S
Z06_S01_E08 MURO_EXTERIOR 0.40 0.669 0.744 9.11 9.11 90.00 90.00 E
Z06_S02_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.09 13.04 0.00 90.00 N
Z06_S02_E05 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 180.00 90.00 S
Z06_S02_E06 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 270.00 90.00 W
Z06_S02_E08 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 90.00 90.00 E
Z06_S03_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.09 13.04 0.00 90.00 N
Z06_S03_E05 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 180.00 90.00 S
Z06_S03_E06 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 270.00 90.00 W
Z06_S03_E08 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 90.00 90.00 E
Z06_S04_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.09 13.04 0.00 90.00 N
Z06_S04_E05 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 180.00 90.00 S
Z06_S04_E06 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 270.00 90.00 W
Z06_S04_E08 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 90.00 90.00 E
Z06_S05_E03 MURO_EXTERIOR 0.40 0.669 0.744 14.09 13.04 0.00 90.00 N
Z06_S05_E05 MURO_EXTERIOR 0.40 0.669 0.744 10.49 10.49 180.00 90.00 S
Z06_S05_E06 MURO_EXTERIOR 0.40 0.669 0.744 1.95 1.95 270.00 90.00 W
Z06_S05_E08 MURO_EXTERIOR 0.40 0.669 0.744 8.61 8.61 90.00 90.00 E
Z06_S06_E03 MURO_EXTERIOR 0.40 0.669 0.744 15.50 14.45 0.00 90.00 N
Z06_S06_E05 MURO_EXTERIOR 0.40 0.669 0.744 11.54 11.54 180.00 90.00 S
Z06_S06_E06 MURO_EXTERIOR 0.40 0.669 0.744 2.15 2.15 270.00 90.00 W
Z06_S06_E08 MURO_EXTERIOR 0.40 0.669 0.744 9.47 9.47 90.00 90.00 E
Z06_S01_TB03 FS TBW_1_85U_ 0.40 0.500 0.541 1.41 1.41 180.00 90.00 S
Z06_S01_TB04 FF TBW_0_15577U_ 0.40 3.274 6.420 16.82 16.82 180.00 90.00 S
Z06_S02_E03_G1_TB1_INFERIOR V TBW_0_6U_ 0.40 1.334 1.667 6.15 6.15 180.00 90.00 S
Z06_S01_E01 SUELO (INV) 0.40 0.485 0.535 11.53 11.53 90.00 180.00  
Z06_S06_E02 CUBIERTA 0.40 0.385 0.406 9.68 9.68 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 90.00 90.00 E
Z01_S02_E06 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 0.00 90.00 N
Z01_S01_E02 FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 0.00  
Z02_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 90.00 90.00 E
Z02_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 0.00 90.00 N
iz-Z01_S01_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 180.00  
Z02_S01_E02 FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 0.00  
Z03_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 90.00 90.00 E
Z03_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 0.00 90.00 N
iz-Z02_S01_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 180.00  
Z03_S01_E02 FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 0.00  
Z04_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 90.00 90.00 E
Z04_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 0.00 90.00 N
iz-Z03_S01_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 180.00  
Z04_S01_E02 FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 0.00  
Z05_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.44 6.44 90.00 90.00 E
Z05_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.33 3.33 0.00 90.00 N
iz-Z04_S01_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 353.73 353.73 180.00 180.00  
iz-Z01_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 270.00 90.00 W
iz-Z01_S02_E06 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 180.00 90.00 S
iz-Z02_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 270.00 90.00 W
iz-Z02_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 180.00 90.00 S
iz-Z03_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 270.00 90.00 W
iz-Z03_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 180.00 90.00 S
iz-Z04_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.33 6.33 270.00 90.00 W
iz-Z04_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.28 3.28 180.00 90.00 S
iz-Z05_S02_E04 PARTICION_INTERIOR 0.40 2.550 6.552 6.44 6.44 270.00 90.00 W
iz-Z05_S02_E05 PARTICION_INTERIOR 0.40 2.550 6.552 3.33 3.33 180.00 90.00 S
iz-Z06_S01_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 90.00 180.00  
iz-Z06_S02_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 90.00 180.00  
iz-Z06_S03_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 90.00 180.00  
iz-Z06_S04_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 90.00 180.00  
iz-Z06_S05_E02 iz-FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 90.00 180.00  
Z06_S01_E02 FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 270.00 0.00  
Z06_S02_E02 FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 270.00 0.00  
Z06_S03_E02 FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 270.00 0.00  
Z06_S04_E02 FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 270.00 0.00  
Z06_S05_E02 FORJADO_INTERIOR 0.40 2.244 5.674 10.75 10.75 270.00 0.00  
Z01_P02 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 175.47   0.00 90.00 N
Z01_S01_E06 FURNITURE PARTICION_INTERIOR 0.40   6.552 151.77   0.00 90.00 N
Z02_P03 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 175.47   0.00 90.00 N
Z02_S01_E06 FURNITURE PARTICION_INTERIOR 0.40   6.552 151.77   0.00 90.00 N
Z03_P04 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 175.47   0.00 90.00 N
Z03_S01_E06 FURNITURE PARTICION_INTERIOR 0.40   6.552 151.77   0.00 90.00 N
Z04_P05 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 175.47   0.00 90.00 N
Z04_S01_E06 FURNITURE PARTICION_INTERIOR 0.40   6.552 151.77   0.00 90.00 N
Z05_P06 FURNITURE FURNIT_INTERNALMASS 0.40   3.600 175.47   0.00 90.00 N
Z05_S01_E07 FURNITURE PARTICION_INTERIOR 0.40   6.552 154.30   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
Z01_S01_E03_G1 WINDOW Z01_S01_E03 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z01_S01_E03 270.00 90.00 W
Z01_S01_E04_G1 WINDOW2 Z01_S01_E04 (199MM) 28.62 6.84 0.00 35.46 35.46 3.004 0.727 0.661 6.122 0.000 CurtainWall 2.420 0.499 0.424 Yes Z01_S01_E04 180.00 90.00 S
Z01_S01_E05_G1 WINDOW3 Z01_S01_E05 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z01_S01_E05 90.00 90.00 E
Z01_S02_E04_G1 WINDOW4 PUERTA_ACCESO_A_EDIFICIO_165_170_ (52MM) 3.80 0.42 0.00 4.23 4.23 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.048 0.666 0.594 No Z01_S02_E04 0.00 90.00 N
Z01_S02_E04_G2 WINDOW5 N_VESTIBULO_255_260_ (245MM) 4.14 2.23 0.00 6.38 6.38 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.086 0.470 0.377 No Z01_S02_E04 0.00 90.00 N
Z01_S04_E03_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z01_S04_E03 0.00 90.00 N
Z02_S01_E03_G1 WINDOW7 Z02_S01_E03 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z02_S01_E03 270.00 90.00 W
Z02_S01_E04_G1 WINDOW8 Z02_S01_E04 (199MM) 28.62 6.84 0.00 35.46 35.46 3.004 0.727 0.661 6.122 0.000 CurtainWall 2.420 0.499 0.424 Yes Z02_S01_E04 180.00 90.00 S
Z02_S01_E05_G1 WINDOW9 Z02_S01_E05 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z02_S01_E05 90.00 90.00 E
Z02_S02_E03_G1 WINDOW10 N_220_225_ (132MM) 1.45 0.79 0.00 2.24 2.24 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.065 0.579 0.498 No Z02_S02_E03 0.00 90.00 N
Z02_S03_E05_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z02_S02_E03 0.00 90.00 N
Z02_S04_E03_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z02_S04_E03 0.00 90.00 N
Z03_S01_E03_G1 WINDOW11 Z03_S01_E03 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z03_S01_E03 270.00 90.00 W
Z03_S01_E04_G1 WINDOW12 Z03_S01_E04 (199MM) 28.62 6.84 0.00 35.46 35.46 3.004 0.727 0.661 6.122 0.000 CurtainWall 2.420 0.499 0.424 Yes Z03_S01_E04 180.00 90.00 S
Z03_S01_E05_G1 WINDOW13 Z03_S01_E05 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z03_S01_E05 90.00 90.00 E
Z03_S02_E03_G1 WINDOW10 N_220_225_ (132MM) 1.45 0.79 0.00 2.24 2.24 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.065 0.579 0.498 No Z03_S02_E03 0.00 90.00 N
Z03_S03_E04_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z03_S02_E03 0.00 90.00 N
Z03_S04_E03_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z03_S04_E03 0.00 90.00 N
Z04_S01_E03_G1 WINDOW14 Z04_S01_E03 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z04_S01_E03 270.00 90.00 W
Z04_S01_E04_G1 WINDOW15 Z04_S01_E04 (199MM) 28.62 6.84 0.00 35.46 35.46 3.004 0.727 0.661 6.122 0.000 CurtainWall 2.420 0.499 0.424 Yes Z04_S01_E04 180.00 90.00 S
Z04_S01_E05_G1 WINDOW16 Z04_S01_E05 (191MM) 28.80 5.83 0.00 34.63 34.63 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.929 0.462 0.393 Yes Z04_S01_E05 90.00 90.00 E
Z04_S02_E03_G1 WINDOW10 N_220_225_ (132MM) 1.45 0.79 0.00 2.24 2.24 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.065 0.579 0.498 No Z04_S02_E03 0.00 90.00 N
Z04_S03_E04_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z04_S02_E03 0.00 90.00 N
Z04_S04_E03_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z04_S04_E03 0.00 90.00 N
Z05_S01_E04_G1 WINDOW17 Z05_S01_E04 (193MM) 29.30 5.91 0.00 35.21 35.21 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.931 0.460 0.392 Yes Z05_S01_E04 270.00 90.00 W
Z05_S01_E05_G1 WINDOW18 Z05_S01_E05 (202MM) 29.10 6.96 0.00 36.05 36.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 2.425 0.497 0.421 Yes Z05_S01_E05 180.00 90.00 S
Z05_S01_E06_G1 WINDOW19 Z05_S01_E06 (193MM) 29.30 5.91 0.00 35.21 35.21 2.302 0.671 0.601 3.777 0.000 CurtainWall 1.931 0.460 0.392 Yes Z05_S01_E06 90.00 90.00 E
Z05_S02_E03_G1 WINDOW10 N_220_225_ (132MM) 1.45 0.79 0.00 2.24 2.24 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.065 0.579 0.498 No Z05_S02_E03 0.00 90.00 N
Z05_S03_E04_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z05_S02_E03 0.00 90.00 N
Z05_S04_E03_G1 WINDOW6 N_160_165_ (118MM) 1.04 0.56 0.00 1.60 1.60 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.062 0.594 0.514 No Z05_S04_E03 0.00 90.00 N
Z06_S02_E03_G1 WINDOW20 N_105_110_ (99MM) 0.68 0.37 0.00 1.05 1.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.058 0.614 0.537 No Z06_S02_E03 0.00 90.00 N
Z06_S03_E03_G1 WINDOW20 N_105_110_ (99MM) 0.68 0.37 0.00 1.05 1.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.058 0.614 0.537 No Z06_S03_E03 0.00 90.00 N
Z06_S04_E03_G1 WINDOW20 N_105_110_ (99MM) 0.68 0.37 0.00 1.05 1.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.058 0.614 0.537 No Z06_S04_E03 0.00 90.00 N
Z06_S05_E03_G1 WINDOW20 N_105_110_ (99MM) 0.68 0.37 0.00 1.05 1.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.058 0.614 0.537 No Z06_S05_E03 0.00 90.00 N
Z06_S06_E03_G1 WINDOW20 N_105_110_ (99MM) 0.68 0.37 0.00 1.05 1.05 3.004 0.727 0.661 6.122 0.000 CurtainWall 3.058 0.614 0.537 No Z06_S06_E03 0.00 90.00 N
Total or Average             564.58 2.572 0.693 0.624                      
North Total or Average             39.21 3.004 0.727 0.661                      
Non-North Total or Average             525.37 2.539 0.690 0.621                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
WINDOW:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z01_S01_E03 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW2:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT Z01_S01_E04 (199MM) 1.946 0.711 0.434 CurtainWall 2.420 0.075 0.279
WINDOW3:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z01_S01_E05 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW7:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z02_S01_E03 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW8:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT Z02_S01_E04 (199MM) 1.946 0.711 0.434 CurtainWall 2.420 0.075 0.279
WINDOW9:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z02_S01_E05 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW11:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z03_S01_E03 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW12:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT Z03_S01_E04 (199MM) 1.946 0.711 0.434 CurtainWall 2.420 0.075 0.279
WINDOW13:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z03_S01_E05 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW14:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z04_S01_E03 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW15:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT Z04_S01_E04 (199MM) 1.946 0.711 0.434 CurtainWall 2.420 0.075 0.279
WINDOW16:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z04_S01_E05 (191MM) 1.626 0.657 0.321 CurtainWall 1.929 0.068 0.210
WINDOW17:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z05_S01_E04 (193MM) 1.626 0.657 0.321 CurtainWall 1.931 0.068 0.209
WINDOW18:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT Z05_S01_E05 (202MM) 1.946 0.711 0.434 CurtainWall 2.425 0.076 0.277
WINDOW19:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT Z05_S01_E06 (193MM) 1.626 0.657 0.321 CurtainWall 1.931 0.068 0.209


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
Z01_S01_E03_G1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
Z01_S01_E04_G1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
Z01_S01_E05_G1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
Z01_S02_E04_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z01_S02_E04_G2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z01_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z02_S01_E03_G1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
Z02_S01_E04_G1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
Z02_S01_E05_G1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
Z02_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z02_S03_E05_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z02_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z03_S01_E03_G1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
Z03_S01_E04_G1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
Z03_S01_E05_G1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
Z03_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z03_S03_E04_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z03_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z04_S01_E03_G1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
Z04_S01_E04_G1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
Z04_S01_E05_G1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
Z04_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z04_S03_E04_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z04_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z05_S01_E04_G1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
Z05_S01_E05_G1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
Z05_S01_E06_G1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
Z05_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z05_S03_E04_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z05_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z06_S02_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z06_S03_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z06_S04_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z06_S05_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Z06_S06_E03_G1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
Z01_S01_E03_G1 WSC_CTRL_1_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z01_S01_E04_G1 WSC_CTRL_1_2_FACTOR_SOLAR_VERANO Interior Shade WINDOW2:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z01_S01_E05_G1 WSC_CTRL_1_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW3:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z02_S01_E03_G1 WSC_CTRL_2_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW7:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z02_S01_E04_G1 WSC_CTRL_2_2_FACTOR_SOLAR_VERANO Interior Shade WINDOW8:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z02_S01_E05_G1 WSC_CTRL_2_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW9:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z03_S01_E03_G1 WSC_CTRL_3_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW11:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z03_S01_E04_G1 WSC_CTRL_3_2_FACTOR_SOLAR_VERANO Interior Shade WINDOW12:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z03_S01_E05_G1 WSC_CTRL_3_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW13:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z04_S01_E03_G1 WSC_CTRL_4_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW14:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z04_S01_E04_G1 WSC_CTRL_4_2_FACTOR_SOLAR_VERANO Interior Shade WINDOW15:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z04_S01_E05_G1 WSC_CTRL_4_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW16:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z05_S01_E04_G1 WSC_CTRL_5_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW17:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z05_S01_E05_G1 WSC_CTRL_5_2_FACTOR_SOLAR_VERANO Interior Shade WINDOW18:WSC_MAT_2_FACTOR_SOLAR_VERANO:INT AlwaysOff No
Z05_S01_E06_G1 WSC_CTRL_5_1_FACTOR_SOLAR_VERANO Interior Shade WINDOW19:WSC_MAT_1_FACTOR_SOLAR_VERANO:INT AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
Z01_P02_IG2 LIGHTS Z01_P02 Z01_P02 GENERAL 4.0985 350.94 1438.34 1 SCHED4 68.04 68.04 68.04 0.0000 Y 5103.23
Z01_P02_IG3 LIGHTS Z01_P02 Z01_P02 GENERAL 0.4458 350.94 156.46 1 SCHED4 68.04 68.04 68.04 0.0000 Y 555.12
Z01_P02_IG4 LIGHTS Z01_P02 Z01_P02 GENERAL 0.1155 350.94 40.54 1 SCHED4 68.04 68.04 68.04 0.0000 Y 143.83
Z01_P02_IG5 LIGHTS Z01_P02 Z01_P02 GENERAL 0.2500 350.94 87.73 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.28
Z02_P03_IG2 LIGHTS Z02_P03 Z02_P03 GENERAL 4.0985 350.94 1438.34 1 SCHED4 68.04 68.04 68.04 0.0000 Y 5103.23
Z02_P03_IG3 LIGHTS Z02_P03 Z02_P03 GENERAL 0.3115 350.94 109.33 1 SCHED4 68.04 68.04 68.04 0.0000 Y 387.91
Z02_P03_IG4 LIGHTS Z02_P03 Z02_P03 GENERAL 0.2498 350.94 87.67 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.05
Z02_P03_IG5 LIGHTS Z02_P03 Z02_P03 GENERAL 0.2500 350.94 87.73 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.28
Z03_P04_IG2 LIGHTS Z03_P04 Z03_P04 GENERAL 4.0985 350.94 1438.34 1 SCHED4 68.04 68.04 68.04 0.0000 Y 5103.23
Z03_P04_IG3 LIGHTS Z03_P04 Z03_P04 GENERAL 0.3115 350.94 109.33 1 SCHED4 68.04 68.04 68.04 0.0000 Y 387.91
Z03_P04_IG4 LIGHTS Z03_P04 Z03_P04 GENERAL 0.2498 350.94 87.67 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.05
Z03_P04_IG5 LIGHTS Z03_P04 Z03_P04 GENERAL 0.2500 350.94 87.73 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.28
Z04_P05_IG2 LIGHTS Z04_P05 Z04_P05 GENERAL 4.0985 350.94 1438.34 1 SCHED4 68.04 68.04 68.04 0.0000 Y 5103.23
Z04_P05_IG3 LIGHTS Z04_P05 Z04_P05 GENERAL 0.3115 350.94 109.33 1 SCHED4 68.04 68.04 68.04 0.0000 Y 387.91
Z04_P05_IG4 LIGHTS Z04_P05 Z04_P05 GENERAL 0.2498 350.94 87.67 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.05
Z04_P05_IG5 LIGHTS Z04_P05 Z04_P05 GENERAL 0.2500 350.94 87.73 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.28
Z05_P06_IG2 LIGHTS Z05_P06 Z05_P06 GENERAL 4.0985 350.94 1438.34 1 SCHED4 68.04 68.04 68.04 0.0000 Y 5103.23
Z05_P06_IG3 LIGHTS Z05_P06 Z05_P06 GENERAL 0.3115 350.94 109.33 1 SCHED4 68.04 68.04 68.04 0.0000 Y 387.91
Z05_P06_IG4 LIGHTS Z05_P06 Z05_P06 GENERAL 0.2498 350.94 87.67 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.05
Z05_P06_IG5 LIGHTS Z05_P06 Z05_P06 GENERAL 0.2500 350.94 87.73 1 SCHED4 68.04 68.04 68.04 0.0000 Y 311.28
Z06_ESCALERAS_IG2 LIGHTS Z06_ESCALERAS Z06_ESCALERAS GENERAL 0.2649 65.25 17.29 1 SCHED4 68.04 68.04 68.04 0.0000 Y 61.34
Z06_ESCALERAS_IG3 LIGHTS Z06_ESCALERAS Z06_ESCALERAS GENERAL 1.2351 65.25 80.59 1 SCHED4 68.04 68.04 68.04 0.0000 Y 285.94
Interior Lighting Total       1.2187 7149.37 8713.25               30914.64


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
Exterior Lighting Total 0.00           0.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
None                  


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP2 [W/W] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [W] Rated Sensible Capacity [W] Rated Power[W] Rated COP [W/W] Rated Air Dry-bulb Temperature [C] Rated Air Wet-bulb Temperature [C] Rated Water Temperature [C] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
None        


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
None                      


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None            



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
Z01_P02 23260.17 23260.17 66.28 1.603 1.603 SUMMER 7/22 17:00:00 25.00 25.00 0.00801 35.20 0.00850 0.702 0.00
Z02_P03 21811.13 21811.13 62.15 1.507 1.507 SUMMER 7/22 17:00:00 25.00 25.00 0.00803 35.20 0.00850 0.702 0.00
Z03_P04 21755.21 21755.21 61.99 1.503 1.503 SUMMER 7/22 17:00:00 25.00 25.00 0.00803 35.20 0.00850 0.702 0.00
Z04_P05 21773.39 21773.39 62.04 1.504 1.504 SUMMER 7/22 17:00:00 25.00 25.00 0.00803 35.20 0.00850 0.702 0.00
Z05_P06 22167.43 22167.43 63.17 1.525 1.525 SUMMER 7/23 17:00:00 25.00 25.00 0.00803 35.00 0.00805 0.702 0.00
Z06_ESCALERAS 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
Z01_P02 16961.65 16961.65 48.33 0.471 0.702 WINTER 12/27 07:00:00 20.00 19.98 0.01299 -0.30 0.00316 0.702 0.00
Z02_P03 9737.94 9737.94 27.75 0.274 0.702 WINTER 12/27 07:00:00 20.00 19.99 0.01250 -0.30 0.00316 0.702 0.00
Z03_P04 8865.48 8865.48 25.26 0.250 0.702 WINTER 12/23 07:00:00 20.00 19.99 0.01300 -0.60 0.00312 0.702 0.00
Z04_P05 9421.37 9421.37 26.85 0.265 0.702 WINTER 12/27 07:00:00 20.00 19.99 0.01241 -0.30 0.00316 0.702 0.00
Z05_P06 12595.90 12595.90 35.89 0.351 0.702 WINTER 12/27 07:00:00 20.00 19.97 0.00950 -0.30 0.00316 0.702 0.00
Z06_ESCALERAS 0.0 0.0 0.0 0.0 0.0 N/A N/A 0.0 0.0 0.0 0.0 0.0 0.0 0.0
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
None                  


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
None                                                                



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
None                                                                                                                                                                            



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
Z01_P02 2758.00 2351.25 1677.75
Z02_P03 2736.25 2261.50 1551.75
Z03_P04 2702.00 2243.00 1490.50
Z04_P05 2739.25 2250.25 1531.00
Z05_P06 2843.75 2301.25 1674.00
Z06_ESCALERAS 3016.75 3127.00 2678.75
Facility 3511.25 3128.00 2685.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
Z01_P02 0.00 0.00 0.00 0.00
Z02_P03 0.00 0.00 0.00 0.00
Z03_P04 0.00 0.00 0.00 0.00
Z04_P05 0.00 0.00 0.00 0.00
Z05_P06 0.00 0.00 0.00 0.00
Z06_ESCALERAS 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
Z01_P02 34.36 34.36 1052.82 2.253 0.000 0.000 0.000
Z02_P03 34.36 34.36 1052.82 2.253 0.000 0.000 0.000
Z03_P04 34.36 34.36 1052.82 2.253 0.000 0.000 0.000
Z04_P05 34.36 34.36 1052.82 2.253 0.000 0.000 0.000
Z05_P06 34.36 34.36 1070.52 2.215 0.000 0.000 0.000
Z06_ESCALERAS 6.39 6.39 198.99 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
Z01_P02 34.36 34.36 1052.82 2.204 0.000 0.000 0.000
Z02_P03 34.36 34.36 1052.82 2.209 0.000 0.000 0.000
Z03_P04 34.36 34.36 1052.82 2.210 0.000 0.000 0.000
Z04_P05 34.36 34.36 1052.82 2.210 0.000 0.000 0.000
Z05_P06 34.36 34.36 1070.52 2.172 0.000 0.000 0.000
Z06_ESCALERAS 6.39 6.39 198.99 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
Z01_P02   34.36 34.36 1052.82 350.94   0.000
Z02_P03   34.36 34.36 1052.82 350.94   0.000
Z03_P04   34.36 34.36 1052.82 350.94   0.000
Z04_P05   34.36 34.36 1052.82 350.94   0.000
Z05_P06   34.36 34.36 1070.52 350.94   0.000
Z06_ESCALERAS   6.39 6.39 198.99 65.25   0.000
Total Facility   178.17 178.17 5480.79 1819.97 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
Z01_P02 8965049.50 0.00 8965049.50 0.00 8965049.50 8965049.50 0.00 3548.00 0.00 0.00
Z02_P03 8965049.50 0.00 8965049.50 0.00 8965049.50 8965049.50 0.00 3548.00 0.00 0.00
Z03_P04 8965049.50 0.00 8965049.50 0.00 8965049.50 8965049.50 0.00 3548.00 0.00 0.00
Z04_P05 8965049.50 0.00 8965049.50 0.00 8965049.50 8965049.50 0.00 3548.00 0.00 0.00
Z05_P06 8965049.50 0.00 8965049.50 0.00 8965049.50 8965049.50 0.00 3548.00 0.00 0.00
Z06_ESCALERAS 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 44825247.50 0.00 44825247.50 0.00 44825247.50 44825247.50 0.00 3548.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
Z01_P02 0.7019 0.0000 0.7019 0.0000 0.7019 0.7019 0.00 3548.00 0.00
Z02_P03 0.7019 0.0000 0.7019 0.0000 0.7019 0.7019 0.00 3548.00 0.00
Z03_P04 0.7019 0.0000 0.7019 0.0000 0.7019 0.7019 0.00 3548.00 0.00
Z04_P05 0.7019 0.0000 0.7019 0.0000 0.7019 0.7019 0.00 3548.00 0.00
Z05_P06 0.7019 0.0000 0.7019 0.0000 0.7019 0.7019 0.00 3548.00 0.00
Z06_ESCALERAS 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.00 0.00 0.00
Total Facility 3.5094 0.0000 3.5094 0.0000 3.5094 3.5094 0.00 3548.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
None                


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
None              


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
None                    


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
None                    



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Surfaces by Class

Total Outdoors
Wall 120 100
Floor 11 2
Roof 12 3
Internal Mass 10 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 35 35
Door 0 0
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 0
Conditioned Zones 6
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 667
Defaulted Fields 517
Fields with Defaults 2200
Autosized Fields 12
Autosizable Fields 36
Autocalculated Fields 0
Autocalculatable Fields 342



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 59972.28 0.00 01-JAN-00:15 16903.11 01-JAN-06:15
Electricity:Building 59972.28 0.00 01-JAN-00:15 16903.11 01-JAN-06:15
Electricity:Zone:Z01_P02 11716.63 0.00 01-JAN-00:15 3302.32 01-JAN-06:15
Electricity:SpaceType:GENERAL 59972.28 0.00 01-JAN-00:15 16903.11 01-JAN-06:15
InteriorLights:Electricity 30914.64 0.00 01-JAN-00:15 8713.25 01-JAN-06:15
InteriorLights:Electricity:Zone:Z01_P02 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
InteriorLights:Electricity:SpaceType:GENERAL 30914.64 0.00 01-JAN-00:15 8713.25 01-JAN-06:15
1:InteriorLights:Electricity 30914.64 0.00 01-JAN-00:15 8713.25 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z01_P02 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
1:InteriorLights:Electricity:SpaceType:GENERAL 30914.64 0.00 01-JAN-00:15 8713.25 01-JAN-06:15
Electricity:Zone:Z02_P03 11716.63 0.00 01-JAN-00:15 3302.32 01-JAN-06:15
InteriorLights:Electricity:Zone:Z02_P03 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z02_P03 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
Electricity:Zone:Z03_P04 11716.63 0.00 01-JAN-00:15 3302.32 01-JAN-06:15
InteriorLights:Electricity:Zone:Z03_P04 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z03_P04 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
Electricity:Zone:Z04_P05 11716.63 0.00 01-JAN-00:15 3302.32 01-JAN-06:15
InteriorLights:Electricity:Zone:Z04_P05 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z04_P05 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
Electricity:Zone:Z05_P06 11716.63 0.00 01-JAN-00:15 3302.32 01-JAN-06:15
InteriorLights:Electricity:Zone:Z05_P06 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z05_P06 6113.47 0.00 01-JAN-00:15 1723.07 01-JAN-06:15
Electricity:Zone:Z06_ESCALERAS 1389.11 0.00 01-JAN-00:15 391.52 01-JAN-06:15
InteriorLights:Electricity:Zone:Z06_ESCALERAS 347.28 0.00 01-JAN-00:15 97.88 01-JAN-06:15
1:InteriorLights:Electricity:Zone:Z06_ESCALERAS 347.28 0.00 01-JAN-00:15 97.88 01-JAN-06:15
InteriorEquipment:Electricity 29057.63 0.00 01-JAN-00:15 8189.86 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z01_P02 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
InteriorEquipment:Electricity:SpaceType:GENERAL 29057.63 0.00 01-JAN-00:15 8189.86 01-JAN-06:15
General:InteriorEquipment:Electricity 29057.63 0.00 01-JAN-00:15 8189.86 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z01_P02 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
General:InteriorEquipment:Electricity:SpaceType:GENERAL 29057.63 0.00 01-JAN-00:15 8189.86 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z02_P03 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z02_P03 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z03_P04 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z03_P04 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z04_P05 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z04_P05 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z05_P06 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z05_P06 5603.16 0.00 01-JAN-00:15 1579.24 01-JAN-06:15
InteriorEquipment:Electricity:Zone:Z06_ESCALERAS 1041.83 0.00 01-JAN-00:15 293.64 01-JAN-06:15
General:InteriorEquipment:Electricity:Zone:Z06_ESCALERAS 1041.83 0.00 01-JAN-00:15 293.64 01-JAN-06:15
Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z01_P02 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z01_P02 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z02_P03 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z02_P03 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z03_P04 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z03_P04 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z04_P05 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z04_P05 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z05_P06 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z05_P06 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
ElectricityPurchased:Plant 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
Cogeneration:ElectricityPurchased 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
General:Cogeneration:ElectricityPurchased 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
ElectricityNet:Plant 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
Cogeneration:ElectricityNet 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15
General:Cogeneration:ElectricityNet 59972.28 0.00 01-JAN-00:15 16903.11 04-JAN-06:15


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [kWh] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [kWh] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
DistrictCooling:Facility 70879.40 0.00 01-JAN-00:15 224790.54 23-JUL-15:15
DistrictCooling:HVAC 70879.40 0.00 01-JAN-00:15 224790.54 23-JUL-15:15
Cooling:DistrictCooling 70879.40 0.00 01-JAN-00:15 224790.54 23-JUL-15:15
General:Cooling:DistrictCooling 70879.40 0.00 01-JAN-00:15 224790.54 23-JUL-15:15


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
Water:Plant 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
WaterSystems:Water 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
General:WaterSystems:Water 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
MainsWater:Facility 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
MainsWater:Plant 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
WaterSystems:MainsWater 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15
General:WaterSystems:MainsWater 109.56 0.00 05-JAN-06:15 0.00 04-JAN-06:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kWh] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 123333.68 0.00 01-JAN-00:15 165144.23 15-JAN-06:15
EnergyTransfer:Building 123333.68 0.00 01-JAN-00:15 165144.23 15-JAN-06:15
EnergyTransfer:Zone:Z01_P02 24687.37 0.00 01-JAN-00:15 41374.12 15-JAN-06:15
Heating:EnergyTransfer 17848.99 0.00 01-JAN-00:15 150951.18 15-JAN-06:15
Heating:EnergyTransfer:Zone:Z01_P02 5402.24 0.00 01-JAN-00:15 38581.66 15-JAN-06:15
General:Heating:EnergyTransfer 17848.99 0.00 01-JAN-00:15 150951.18 15-JAN-06:15
General:Heating:EnergyTransfer:Zone:Z01_P02 5402.24 0.00 01-JAN-00:15 38581.66 15-JAN-06:15
Cooling:EnergyTransfer 105484.69 0.00 01-JAN-00:15 156418.78 23-JUL-15:15
Cooling:EnergyTransfer:Zone:Z01_P02 19285.13 0.00 01-JAN-00:15 31418.59 23-JUL-15:15
General:Cooling:EnergyTransfer 105484.69 0.00 01-JAN-00:15 156418.78 23-JUL-15:15
General:Cooling:EnergyTransfer:Zone:Z01_P02 19285.13 0.00 01-JAN-00:15 31418.59 23-JUL-15:15
EnergyTransfer:Zone:Z02_P03 24488.79 0.00 01-JAN-00:15 32649.19 23-JUL-15:15
Heating:EnergyTransfer:Zone:Z02_P03 2969.12 0.00 01-JAN-00:15 28537.46 15-JAN-06:15
General:Heating:EnergyTransfer:Zone:Z02_P03 2969.12 0.00 01-JAN-00:15 28537.46 15-JAN-06:15
Cooling:EnergyTransfer:Zone:Z02_P03 21519.67 0.00 01-JAN-00:15 31524.81 23-JUL-15:15
General:Cooling:EnergyTransfer:Zone:Z02_P03 21519.67 0.00 01-JAN-00:15 31524.81 23-JUL-15:15
EnergyTransfer:Zone:Z03_P04 24828.67 0.00 01-JAN-00:15 32377.42 23-JUL-15:15
Heating:EnergyTransfer:Zone:Z03_P04 2528.43 0.00 01-JAN-00:15 26156.34 15-JAN-06:15
General:Heating:EnergyTransfer:Zone:Z03_P04 2528.43 0.00 01-JAN-00:15 26156.34 15-JAN-06:15
Cooling:EnergyTransfer:Zone:Z03_P04 22300.24 0.00 01-JAN-00:15 31252.60 23-JUL-15:15
General:Cooling:EnergyTransfer:Zone:Z03_P04 22300.24 0.00 01-JAN-00:15 31252.60 23-JUL-15:15
EnergyTransfer:Zone:Z04_P05 24704.91 0.00 01-JAN-00:15 32186.40 23-JUL-15:15
Heating:EnergyTransfer:Zone:Z04_P05 2792.05 0.00 01-JAN-00:15 26996.77 15-JAN-06:15
General:Heating:EnergyTransfer:Zone:Z04_P05 2792.05 0.00 01-JAN-00:15 26996.77 15-JAN-06:15
Cooling:EnergyTransfer:Zone:Z04_P05 21912.86 0.00 01-JAN-00:15 31061.26 23-JUL-15:15
General:Cooling:EnergyTransfer:Zone:Z04_P05 21912.86 0.00 01-JAN-00:15 31061.26 23-JUL-15:15
EnergyTransfer:Zone:Z05_P06 24623.94 0.00 01-JAN-00:15 33900.76 15-JAN-06:15
Heating:EnergyTransfer:Zone:Z05_P06 4157.15 0.00 01-JAN-00:15 30678.95 15-JAN-06:15
General:Heating:EnergyTransfer:Zone:Z05_P06 4157.15 0.00 01-JAN-00:15 30678.95 15-JAN-06:15
Cooling:EnergyTransfer:Zone:Z05_P06 20466.79 0.00 01-JAN-00:15 31161.52 23-JUL-15:15
General:Cooling:EnergyTransfer:Zone:Z05_P06 20466.79 0.00 01-JAN-00:15 31161.52 23-JUL-15:15
EnergyTransfer:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Heating:EnergyTransfer:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
General:Cooling:EnergyTransfer:Zone:Z06_ESCALERAS 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
DistrictHeating:Facility 97593.75 580.85 02-JUL-13:15 239995.01 15-JAN-06:15
DistrictHeating:Plant 5974.85 580.85 02-JUL-13:15 755.11 01-JAN-06:15
WaterSystems:DistrictHeating 5974.85 580.85 02-JUL-13:15 755.11 01-JAN-06:15
General:WaterSystems:DistrictHeating 5974.85 580.85 02-JUL-13:15 755.11 01-JAN-06:15
DistrictHeating:HVAC 91618.91 0.00 01-JAN-00:15 239239.90 15-JAN-06:15
Heating:DistrictHeating 91618.91 0.00 01-JAN-00:15 239239.90 15-JAN-06:15
General:Heating:DistrictHeating 91618.91 0.00 01-JAN-00:15 239239.90 15-JAN-06:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kWh] HVAC Zone Eq & Other Sensible Air Cooling [kWh] HVAC Terminal Unit Sensible Air Heating [kWh] HVAC Terminal Unit Sensible Air Cooling [kWh] HVAC Input Heated Surface Heating [kWh] HVAC Input Cooled Surface Cooling [kWh] People Sensible Heat Addition [kWh] Lights Sensible Heat Addition [kWh] Equipment Sensible Heat Addition [kWh] Window Heat Addition [kWh] Interzone Air Transfer Heat Addition [kWh] Infiltration Heat Addition [kWh] Opaque Surface Conduction and Other Heat Addition [kWh] Equipment Sensible Heat Removal [kWh] Window Heat Removal [kWh] Interzone Air Transfer Heat Removal [kWh] Infiltration Heat Removal [kWh] Opaque Surface Conduction and Other Heat Removal [kWh]
Z01_P02 5402.256 -19285.17 0.000 0.000 0.000 0.000 7472.458 6113.473 5603.160 38294.876 0.000 3.000 1.125 0.000 -12882.76 0.000 -431.26 -30290.03
Z02_P03 2969.131 -21519.76 0.000 0.000 0.000 0.000 7472.458 6113.473 5603.160 37428.580 0.000 5.276 1.122 0.000 -12948.94 0.000 -527.98 -24595.40
Z03_P04 2528.438 -22300.34 0.000 0.000 0.000 0.000 7472.458 6113.473 5603.160 37302.436 0.000 5.606 2.623 0.000 -13132.63 0.000 -559.59 -23033.01
Z04_P05 2792.057 -21912.96 0.000 0.000 0.000 0.000 7472.458 6113.473 5603.160 37345.004 0.000 5.825 1.688 0.000 -13041.96 0.000 -565.62 -23811.45
Z05_P06 4157.279 -20466.99 0.000 0.000 0.000 0.000 7472.458 6113.473 5603.160 38227.303 0.000 31.205 0.579 0.000 -12597.30 0.000 -2730.68 -25809.91
Z06_ESCALERAS 0.000 0.000 0.000 0.000 0.000 0.000 1389.403 347.277 1041.830 461.046 0.000 165.911 0.020 0.000 -346.46 0.000 -2202.26 -856.74
Total Facility 17849.161 -105485.22 0.000 0.000 0.000 0.000 38751.692 30914.644 29057.632 189059.243 0.000 216.822 7.157 0.000 -64950.05 0.000 -7017.39 -128396.54


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
Z01_P02 23-JUL-15:15 0.00 -204778.67 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 12073.98 0.00 0.00 187296.27 0.00 -0.00 0.00 0.00 0.00
Z02_P03 23-JUL-15:15 0.00 -206857.94 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 11588.61 0.00 0.00 189860.91 0.00 -0.00 0.00 0.00 0.00
Z03_P04 23-JUL-15:15 0.00 -205209.16 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 11599.58 0.00 0.00 188201.16 0.00 -0.00 0.00 0.00 0.00
Z04_P05 23-JUL-15:15 0.00 -204074.41 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 11605.80 0.00 0.00 187060.19 0.00 -0.00 0.00 0.00 0.00
Z05_P06 23-JUL-15:15 0.00 -207496.53 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 11784.64 0.00 0.00 190303.47 0.00 -0.00 0.00 0.00 0.00
Z06_ESCALERAS - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 23-JUL-15:15 0.00 -1028416.70 0.00 0.00 0.00 0.00 10922.11 8713.25 8189.86 58940.39 0.00 743.94 940907.15 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
Z01_P02 15-JAN-06:15 310974.42 0.00 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 0.00 0.00 0.00 0.00 0.00 -3336.13 0.00 0.00 -313046.71
Z02_P03 15-JAN-06:15 236629.38 0.00 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 0.00 0.00 0.00 0.00 0.00 -3680.73 0.00 0.00 -238357.07
Z03_P04 15-JAN-06:15 218899.52 0.00 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 0.00 0.00 0.00 0.00 0.00 -3818.23 0.00 0.00 -220489.71
Z04_P05 15-JAN-06:15 225246.45 0.00 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 0.00 0.00 0.00 0.00 0.00 -3776.74 0.00 0.00 -226878.13
Z05_P06 15-JAN-06:15 257961.88 0.00 0.00 0.00 0.00 0.00 2106.10 1723.07 1579.24 0.00 0.00 0.00 0.00 0.00 -3665.06 0.00 0.00 -259705.24
Z06_ESCALERAS - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-JAN-06:15 1249711.65 0.00 0.00 0.00 0.00 0.00 10922.11 8713.25 8189.86 0.00 0.00 0.00 0.00 0.00 -18372.81 0.00 -1455.25 -1257708.81



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
None                            


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
None                            


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                            


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                            


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** D3_peninsula - ESP CTE_DB_HE WMO#=
Total gross floor area [m2] 1819.97
Principal Heating Source District Heat


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
Z01_P02 350.94 350.94 0.00 68.04
Z02_P03 350.94 350.94 0.00 68.04
Z03_P04 350.94 350.94 0.00 68.04
Z04_P05 350.94 350.94 0.00 68.04
Z05_P06 350.94 350.94 0.00 68.04
Z06_ESCALERAS 65.25 65.25 0.00 68.04
Totals 1819.97 1819.97 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [kWh] Natural Gas Demand [W] Gasoline Use [kWh] Gasoline Demand [W] Diesel Use [kWh] Diesel Demand [W] Coal Use [kWh] Coal Demand [W] Fuel Oil No 1 Use [kWh] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [kWh] Fuel Oil No 2 Demand [W] Propane Use [kWh] Propane Demand [W] Other Fuel 1 Use [kWh] Other Fuel 1 Demand [W] Other Fuel 2 Use [kWh] Other Fuel 2 Demand [W] District Cooling Use [kWh] District Cooling Demand [W] District Heating Use [kWh] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91618.91 239239.90
Cooling -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70879.40 224790.54 0.00 0.00
Interior Lighting -- 1 30914.64 8713.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- General 29057.63 8189.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5974.85 755.11
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kWh] Total Energy Use [kWh]
Electricity 29057.63 59972.28
Natural Gas 0.00 0.00
Additional 0.00 168473.15
Total 29057.63 228445.43


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kWh]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/m2]
Interior Lighting (All) 16.99
Space Heating 0.00
Space Cooling 0.00
Fans (All) 0.00
Service Water Heating 0.00
Receptacle Equipment 15.97
Miscellaneous (All) 32.95
Subtotal 32.95


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kWh/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.53
Space Heating 40.11
Space Cooling 31.03
Fans (All) 0.00
Service Water Heating 2.62
Receptacle Equipment 12.72
Miscellaneous -0.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
SCHED2_FLOW_RATE_FRACTION 8760. 8760.
SCHED4 3548. 3548.
SCHED5 5212. 5212.
WORK EFF SCH 0. 0.
CLOTHING SCH 8760. 8760.
AIR VELO SCH 1200. 8760.
SUMMERNIGHTVENTILATION SCH 976. 976.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
SCHED0_CTE THERMOSTAT_Z01_P02 SETPOINT January 20.00 365 -50.00 365
SCHED1_CTE THERMOSTAT_Z01_P02 SETPOINT July 25.00 365 100.00 365
THERMOSTAT_Z06_ESCALERAS HEATING SETPOINT TEMPERATURE THERMOSTAT_Z06_ESCALERAS SETPOINT January -50.00 365 -50.00 365
THERMOSTAT_Z06_ESCALERAS COOLING SETPOINT TEMPERATURE THERMOSTAT_Z06_ESCALERAS SETPOINT July 100.00 365 100.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2026-07-17 12:05:41

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None